1
st
Issue 11/06 13
DMP054E
Digital UIs
Note: Only dry (voltage free) contacts can be monitored. Maximum count frequency is once every
two seconds.
1.Connect one wire from field contact to desired input terminal (8, 9, 10, 11, 12, 13, 14, 15, 16 or
17). Polarity is not important.
2.Connect other wire to one UI common (COM) terminal (31, 32, 33, 34, 35, 36, 37, 38, 39 or 40).
3.Make certain input configuration jumper is in Digital position.
Relay Output Wiring
The Relay Outputs are normally open voltage-free line relays for 230Vac switching, 5A loads. Each
load must be externally powered.
Note: The selected wire gauge must be consistent with load current rating.
1.Review the Precautions section.
2.Connect one wire from load to be switched to desired input terminal (47, 49, 51, 53, 55 or 57).
3.Connect other side of load to output terminal (48, 50, 52, 54, 56 or 58).
Analogue Output (AO) Wiring
AO1 to AO4 supply from 0 to 10Vdc to modulate a voltage controlled device.
•
Minimum input impedance for a device or actuator operated by an AO is 10kO.
•
The maximum current that a 0-10Vdc output can source is 1mA.
•
Review the Precautions section. Connect positive signal wire to desired output terminal (3, 4, 5
or 6).
Connect negative signal wire to the corresponding AO COM terminal (26, 27, 28 or 29).