441-622-015 REV 05-23-11

Type 500X

Page 5

3. MAINTENANCE

Under normal circumstances, no maintenance should be required. If clean dry air is not used the orifice can become blocked. To
clean, first turn off supply air, unscrew and remove orifice assembly (large silver screw head located above the out port). Then
unplug orifice by using a wire that has a smaller diameter than 0.015 in. (0.38 mm). Use compressed air to blow out any loose
particles inside the orifice assembly. Screw orifice assembly back into unit.

4. TROUBLESHOOTING

PROBLEM

CHECK

No output or low output

Zero adjustment

Supply pressure too low

Clogged orifice

Leakage

Connections

Low or improper span

Zero and Span adjustments

Supply pressure too low

Output leakage

Erratic operation

Electrical input signal

Loose wires or connections

Liquid in air supply

Lead Wire

Bonnet

O-Ring

O-Ring

Body Subassembly

Circuit

Board

Bottom Plug

Spacer

Pintle Spring