controlair 500-AA Installation, Operation And Maintenance Instructions Download Page 2

441-622-015

Type 500X

Page 2

DANGER, WARNING, CAUTION and NOTE statements

Refers to conditions or hazards which could result in serious personal injury or death.
Refers to conditions or hazards which could result in personal injury.
Refers to conditions or hazards which could result in equipment or property damage.
Alerts you to facts or special instructions.

ALL DANGER, WARNING, AND CAUTION NOTICES MUST BE COMPLIED WITH IN FULL

SPECIFICATIONS

Min./Max. Supply Pressure

Minimum - 3 psig (21 kPa)

Above maximum output

Maximum - 100 psig (700 kPA)

Supply Pressure Sensitivity

<± 0.1% of span per psig

(<± 0.15% of span per 10 kPa)

Linearity

<± 0.75% of span

Repeatability

< 0.5% of span

Hysteresis

< 1.0% of span

Flow Rate

4.5 scfm (7.6 m3/hr ANR) at

25 psig (175 kPa) supply

12.0 scfm (20.0 m3/hr ANR) at

100 psig (700 kPa) supply

Maximum Air Consumption

.05 scfm (.07 m3/hr) midrange typical

Port Sizes

1/4 NPT (Pneumatic)

1/2 NPT (Electric)

1. DESCRIPTION and INSTALLATION

1.1 Description

1.1.1 The ControlAir Type 500X converts a current or voltage input signal to a linearly proportional pneumatic output

pressure. This versatile instrument is designed for control applications that require a high degree of reliability and

repeatability at an economical cost.

1.2 Principle of Operation

1.2.1 The Type 500X is a force balance device in which a coil is suspended in the field of a magnet by a flexure. Current

flowing through the coil generates axial movement of the coil and flexure. The flexure moves towards the nozzle

and creates back pressure which acts as a pilot pressure to an integral booster relay. Input signal increases (or

decreases for reverse acting) cause proportional output pressure increases.
Zero and Span are calibrated by turning adjust screws on the front face of the unit. Adjustment of the zero screw

repositions the nozzle relative to the flexure. The span adjustment is a potentiometer that controls the amount of

current through the coil.

1.3 Mounting

1.3.1 Unit may be pipe, panel, or bracket mounted. Mounting may be at any angle, though may require field

adjustment. High external vibration may cause output fluctuations. Mounting in a vibration-free area is

recommended.