background image

Contents

Section

Description

Page

1.0

Description & Installation

2

2.0

Operation

3

3.0

Maintenance

5

4.0

Troubleshooting

5

5.0

Warranty

5

Pilot Pressure

Atmospheric Pressure

Supply Pressure

Output Pressure

441-622-015

Type 500X

Page 1

Electropneumatic Transducer (I/P, E/P)

Installation, Operation and

Maintenance Instructions

Type 500X

Ordering Information

Type 500X I/P Transducers

Output Range

Part Number

Input

psi

kPa

Impedance

500-AA

4-20 mA

3-9

20-60

90 Ohms

500-AB

4-20 mA

9-15

60-100

90 Ohms

500-AC

4-20 mA

3-15

20-100

180 Ohms

500-AD

4-20 mA

3-27

20-185

220 Ohms

500-AE

4-20 mA

6-30

40-200

220 Ohms

500-AF

4-20 mA

1-17

7-117

250 Ohms

500-BC

10-50 mA

3-15

20-100

70 Ohms

500-BD

10-50 mA

3-27

20-185

85 Ohms

500-BE

10-50 mA

6-30

40-200

85 Ohms

500-AG

4-20 mA

2-60*

14-420

225 Ohms

500-AH

4-20 mA

3-120*

20-830

260 Ohms

500-BF

0-60 mA

2-120*

15-830

220 Ohms

Type 500X E/P Transducers

Output Range

Part Number

Input

psi

kPa

Impedance

500-CC

0-5 VDC

3-15

20-100

615 Ohms

500-CD

0-5 VDC

3-27

20-185

530 Ohms

500-CE

0-5 VDC

6-30

40-200

530 Ohms

500-DC

1-9 VDC

3-15

20-100

985 Ohms

500-DD

1-9 VDC

3-27

20-185

840 Ohms

500-DE

1-9 VDC

6-30

40-200

840 Ohms

500-CF

0-5 VDC

2-60*

14-420

500 Ohms

500-EH

0-10 VDC

3-120*

20-830

805 Ohms

*Output shown is as calibrated at the factory. Large span adjustment capability

allows recalibration to achieve output ranges from 3-35 psig (20-240 kPa) with 2-

60 psig unit to 3-145 psig (20-1000 kPa) with 2-120 psig unit.