8.6 Network
Status
Unidrive: #20.50
#20.50 on Unidrive indicates the number of valid messages per second
being received by the node. The Profibus-DP network master controller
addresses every node on the network once per network cycle, and
exchanges the configured amount of information. If a network has been
correctly wired, screened and terminated, there will be very few errors
occurring, and the number of messages per second displayed on each
node should be the same. #20.50 is only updated once per second.
8.7 No
Data
Transfer
If data is not being transferred from the master controller to the
Unidrive, make the following checks:
•
The mapping parameters have been programmed correctly. If an
invalid mapping was entered, it will have been reset to 0.
•
Check that there are no mapping parameter conflicts, i.e. an
analogue input is not trying to control the same parameter as a
cyclic OUT channels.
8.8 Unidrive
Trip
Codes
The trip codes listed below may be caused by the Profibus-DP
interface. Other trips may occur if a DPL program is loaded. For a full
list of UD70 trips, refer to the UD70 User Guide
Trip
Code
Error
tr52
This code indicates that the trip originate d from the setting of
bit 4 in the control Word
tr56
The UD70 does not contain the correct operating system for
the detected hardware. Download the system file
“IBSPROFI.SYS”. If the trip persists, ensure that the UD73A
and UD70 boards inside the module are properly clipped
together. (This should only be attempted by suitably qualified
personnel!!)
tr57
An illegal operating system call has been made, e.g. WRNET.
CTNet commands cannot be used with Profibus-DP
tr60
This trip indicates that loss of the Profibus-DP network has
been detected. This can be caused by disconnecting the
node form the network, a bad cable connection, or by
resetting or stopping the network master controller
See section 9.3 for details on how to reset the Unidrive using the
Profibus-DP network.