![Control Techniques Profibus-DP User Manual Download Page 22](http://html.mh-extra.com/html/control-techniques/profibus-dp/profibus-dp_user-manual_2658677022.webp)
22 Issue
Number:
3
#6.15
#6.30
#6.31
#6.32
b0
b1
b2
b3
b4
b5
b6
b7
b8
MO
M1
M2
M3
b13
M5
M6
1
1
0
0
1
0
#1.47
Trip
#1.46
#18.33
#18.32
#18.31
1
0
1
0
1
0
If mask bits M0 and M1 are set to 1, ENABLE and RUN FWD are
updated with the values of b0 and b1 (either 0 or 1) every time the
control word value is received. JOG and RUN REV will not be updated,
even if the values of b2 and b3 change, because their mask bits (M2
and M3) are not set to 1. If M0 and M1 are reset to 0, the values in b0
and b1 will NOT be written to ENABLE and RUN FWD, and these
parameters will remain set to their current state.
The TRIP bit (b4) will cause a “tr52” trip when set to 1, but the trip
cannot be cleared until the TRIP bit (b4) has been reset to 0.
Parameters #18.31 to #18.33 are general user parameters and do not
have mask bits.
Bit Function
Description
0
ENABLE Set to 1 to put the Unidrive in READY mode. (The
hardware ENABLE must also be present.) The RUN
FWD, JOG and RUN REV bits will have no effect
unless the ENABLE bit is set to 1. The Unidrive
outputs are disabled immediately when the ENABLE
bit is reset to 0, and the motor will coast to stop
1 RUN
FWD
Set to 1 to run the motor in the forwards direction.
Reset to 0 to decelerate the motor to a controlled
stop before the Unidrive output stage is disabled
2
JOG
Set to 1 with RUN FWD or RUN REV bit also set to
jog the motor in the appropriate direction. The
Unidrive will ramp the motor to the normal speed or
stop when the JOG bit is reset to 0, depending on the
status of the RUN FWD and RUN REV bits.