EMM-R3 VA 

instruction manual 

IM425-U v2.0 

pag. 5 

 

MENU OF INSTRUMENT PROGRAMMING (SETUP) 

For a correct use of the instruments it’s necessary to program the transformation rate of the CT’s and the transformation 
rate of the eventually voltage transformers. The values set are hold also in absence of the auxiliary power supply. 
 

- Programming of the transformation rate of the external CT’s 

The programming of the CT’s rate considered as the rate between 
primary and secondary (example: with CT 1000/5, we must set 200), 
must be done with the push-button on the front panel. 
After the connecting the power supply to the instrument and waiting few 
seconds (all LED’s will glow and the first indication of the firmware 
appears on the display and all segments will glow later), press and keep 
pressing the key 

A

 during 5 seconds, when the message 

set up

 will 

appear on the display 

E

. By pressing the key 

A

 again it will appear the 

message 

CT

 (current transformer) and the value of the transformation 

rate (set to 1 by the manufacturer). 
To increase the value press the 

B

 button or 

A

 button reduce the value 

(the variation is unit for unit). 
To increase the speed up the value setting, it’s necessary to hold pressed 
the 

B

 or 

A

 button, the variation will happen successively by tens and 

hundreds. 
To come back to increase or to reduce the value on unit by unit way, it’s 
necessary to release and to press the key again. 
To confirm the value set press the 

A

 button; in this way the instrument will pass to the successive programming. 

If no key is pressed during a 10-second interval of time, the instrument will exit automatically from programming, without 
saving the selected value. 
 

- Programming of the transformation rate of the external voltage transformers 

After the precedent programming, the message 

VT

 (voltage transformer) will appear on display 

E

 together with the value 

of the transformation rate of the external VT (set to 1 by the manufacturer), considered as the rate between primary and 
secondary (example with VT 15/o.1 kV the value will be 150). 
In the same way as programming the CT’s rate, it will be possible to set this value. If external VT are not used the value 
to set will be 1. 
To confirm the value press the 

A

 button. The instrument will exit from programming and it will enter in the visualisation 

modality. 
 

-Activating or cancelling the automatic scrolling 

This allows selecting ON for activating or OFF for cancelling the automatic scrolling of the measures visualisation. 
 

MEASURES VISUALISATION 

The measures reading is visualised on the display 

E

, showing the three phase measures (L1, L2 y L3 respectively) of the 

indicated parameter by the 

C

 LED. For measuring the phase to phase voltage (V 

L-L

), the three measures are understood 

L1-L2

, V 

L2-L3

, V 

L3-L1 respectively, as indicated on the front plate.

 

The selection of the parameter to be visualised is made by pressing the key 

B

. It will be indicated by the 

LED. 

By pressing the key 

A,

 the selected parameters will be visualised on display 

E

, as three phase values (average of the 

individual phases for voltages and currents) with the corresponding lighting of the LED, placed internally in the key. In 
This case, by pressing the key 

B

 it will be possible to show: either the three-phase voltage, calculated as the average of 

the phase voltage, or the phase to phase voltages (it will be indicated by the corresponding LED 

C

). In the mode of 

visualisation of the three-phase system (LED 

Σ

L glowing), we will have following lights and readings: 

- LED 

V

L-N

 or (

V

L-L

) and the display 

L1

 will show the average phase voltage (or average phase to phase) 

- LED 

A

 and the display 

L2

 will show the average current 

- LED 

Hz

 and the display L3 will show the frequency on line L1 

By pressing the 

A

 key again, it will return to visualise the phase values. 

Please note that the unit value may be expressed in kilo, when the corresponding LED 

are glowing (indicated in the 

front plate as 

k

). 

The visualised frequency is referred to the line L1.

 

B

C

C

E

A

L1

L2

L3

Σ

L

V

L-N

V

L-L

A

electrical  multi meter

L1-2

L2-3

L3-1

MAX

Hz

k

max

avg

k

D

Summary of Contents for EMM-R3 VA

Page 1: ...of all in one for electrical boards switch boards and Gen Sets AVAILABLE MODELS Several models with various optional functions and outputs are available either for flush mounting on front panel and fo...

Page 2: ...70V phase neutral L2 L3 phase to phase power supply 110V 85 145V phase to phase 50 85V phase neutral 230V 300 500V phase to phase 175 290V phase neutral L3 N phase neutral power supply 110V 175 290V p...

Page 3: ...le only for the version with internal CT s P1 P2 S2 P2 P1 P1 P1 P2 S1 S1 S1 S2 N L1 L2 L3 THREE PHASE LINE WITH 4 WIRES AND 3 VT P1 P2 S1 S2 N L SINGLE PHASE LINE If the instruments are used on single...

Page 4: ...alise on display E C LED s for indicating the measures visualised on display E and the eventual multiplier factor of each parameter reading k kilo x1000 D LED for indicating the visualisation of the m...

Page 5: ...cturer considered as the rate between primary and secondary example with VT 15 o 1 kV the value will be 150 In the same way as programming the CT s rate it will be possible to set this value If extern...

Page 6: ...ellation of the peak values Enter in programming mode SETUP press the key B until the message reset appears on the display E then press the key A and the message RES ALL no will appear on display E By...

Page 7: ...isplay with red LED of 10 mm each made of 3 digits of 7 segments 2 keys for selection of measures and programming Mechanical Protection degree IP52 frontal IP20 enclosure and terminals weight approx 0...

Page 8: ...EMM R3 VA instruction manual IM425 U v2 0 pag 8...

Reviews: