background image

 

EMM-R3 VA 

instruction manual 

IM425-U v2.0 

pag. 2 

 

INSTALLATION 

WARNING FOR THE USER 
Read carefully the instructions/indications contained in this manual before installing and using the instrument. 
The instrument described in this manual is intended for use by properly trained staff only. 
SAFETY 
This instrument has been manufactured and tested in compliance with EN 61010-1 standards. In order to maintain these conditions and 
to ensure safe operation, the person must comply with the indications and markings contained in the manual. When the instrument is 
received, before beginning installation, check that it's OK And it has not suffered any damage during transport. When starting 
installations make sure that the operating voltage and mains voltages are compatible with the device instructions. The instrument power 
supply must not be earthen. Only qualified and authorised personnel must carry out maintenance and/or repair. If there is ever the 
suspicious that, that there is a lack of safety, during operation, the instrument must be disconnected and cautions taken against 
accidental use. 

Operation is no longer safe when: The instrument doesn't work. - There is clearly visible damage. - After serious damage 
incurred during transport. - After a storage under unfavourable conditions. 

 

WIRING 

For a correct use of the device, the wiring diagram contained in the present manual must be respected. 
The connections are available on the screw terminal: 
 

- Auxiliary power supply: 

The power supply is take from voltage inputs. 
There are 3 different auxiliary supplies: 
 

Vn 110V = 100-125V 50-60Hz 

 

Vn 230V = 220-240V 50-60Hz 

 

Vn 400V = 380-415V 50-60Hz 

 

In the standard version the voltage is 400V and it’s taken between the phases L2-L3. 

In the following table it’s possible to see the measurable voltage depending of the type of power supply. 

Power supply terminals 

Rated voltage 

Range of measurable voltage 

400V 

300÷500V phase to phase (175÷290V phase-neutral) 

230V 

175÷290V phase to phase (130÷170V phase-neutral) 

L2-L3

 (phase to phase power supply) 

110V 

85÷145V phase to phase (50÷85V phase-neutral) 

230V 

300÷500V phase to phase (175÷290V phase-neutral) 

L3-N

 (phase – neutral power supply) 

110V 

175÷290V phase to phase (100÷170V phase-neutral) 

The standard version allows applying the instrument at all the three-phase network 400V with or without neutral supplied. 
For example for application on single phase 230V it will need the L3-N / 230V. While for applications in medium voltage 
(for example using external voltage transformer 15 / 0.1 kV phase to phase) it will need the version L2-L3 / 110V. 
 

- measuring voltage inputs: 

4 terminals are available for the connection to the 3 phase and 
neutral of the measuring network, the maximum voltage phase to 
phase shouldn't be over 500 V rms and it will always be depending 
on the auxiliary power supply. 
In case of a 3 phase system without neutral, or non-distributed 
neutral, to leave terminal N free. 
It’s possible to use external voltage transformer. In fact the 
transformation rate of the external transducer can be set in the 
SETUP of the instrument and the visualisation allows the reading of 
voltage up to 40,0 kV. 
 

- measuring current inputs: 

4 terminals are available for the connection to 3 external CT’s with 
secondary 5A, it’s possible to use 2 CT’s on 3 wires system (three 
phases Aaron wiring). The use of external CT’s is always necessary. 
The transformation rate of the external transducer can be set in the 
SETUP of the instrument and the visualisation allows the reading of 
voltage up to 9,99 kA. 
 

NOTE: It's a must to respect the phase sequence. The connections between current and voltage phase inputs must not be inverted (for 
example, CT placed on phase L1 must correspond to the I1 input). So as it is not correct to invert S1 and S2 terminals. 
To fix the device at the panel, insert the two brackets into their corresponding grove holes, at the side of the enclosure and fix up the 
screws. It’s better to put an external protection with fuses for the voltage inputs and to use adapted cables for the working currents and 
voltages: section from 0.5 to 2.5 mm

2

ENERGY COUNTERS

PANNELLO POSTERIORE (lato connessioni)

morsettiera a vite

Summary of Contents for EMM-R3 VA

Page 1: ...of all in one for electrical boards switch boards and Gen Sets AVAILABLE MODELS Several models with various optional functions and outputs are available either for flush mounting on front panel and fo...

Page 2: ...70V phase neutral L2 L3 phase to phase power supply 110V 85 145V phase to phase 50 85V phase neutral 230V 300 500V phase to phase 175 290V phase neutral L3 N phase neutral power supply 110V 175 290V p...

Page 3: ...le only for the version with internal CT s P1 P2 S2 P2 P1 P1 P1 P2 S1 S1 S1 S2 N L1 L2 L3 THREE PHASE LINE WITH 4 WIRES AND 3 VT P1 P2 S1 S2 N L SINGLE PHASE LINE If the instruments are used on single...

Page 4: ...alise on display E C LED s for indicating the measures visualised on display E and the eventual multiplier factor of each parameter reading k kilo x1000 D LED for indicating the visualisation of the m...

Page 5: ...cturer considered as the rate between primary and secondary example with VT 15 o 1 kV the value will be 150 In the same way as programming the CT s rate it will be possible to set this value If extern...

Page 6: ...ellation of the peak values Enter in programming mode SETUP press the key B until the message reset appears on the display E then press the key A and the message RES ALL no will appear on display E By...

Page 7: ...isplay with red LED of 10 mm each made of 3 digits of 7 segments 2 keys for selection of measures and programming Mechanical Protection degree IP52 frontal IP20 enclosure and terminals weight approx 0...

Page 8: ...EMM R3 VA instruction manual IM425 U v2 0 pag 8...

Reviews: