pag. 17 / 22
LOGIC EXPRESSION menu
LOGIC EXPRESSION n (n=1..8)
UoM
Default
Range
1
Enable
-
NO
YES-NO
2
Compute timing
sec/min
1 sec
1-2-3-5-6-10-12-15-20-30 sec
1-2-6-5-6-10-12-15-20-30-60 min
End of day
End of week
End of month
3
Source 1
-
-
Internal measures-(measures node 1-20)
4
Group 1
-
-
Instantaneous-Average-Energies-
Digital inputs-Counters-Analog input-Math
5
Item 1
-
-
OFF-(measures)
6
Multiplier 1
-
1
1-100000
7
Divisor 1
-
1
1-100000
8
Operation
-
Sum
Sum-Subtraction-Multiplication-Division
9
Source 2
-
-
Internal measures-(measures node 1-20)
10
Group 2
-
-
Instantaneous-Average-Energies-
Digital inputs-Counters-Analog input-Math
11
Item 2
-
-
OFF-(measures)
12
Multiplier 2
-
1
1-100000
13
Divisor 2
-
1
1-100000
NOTE: this menu is divided into 8 sections, for logic expression LE1..8
1
- Expression enabled.
2
- Selection of refresh calculation. Expression value is updated with the results of the last calculation.
3
- First measurement source. Internal measures or measures referred to the external devices (when EMA-D6 will be configured as Master RS-485).
4
- First measurement group that generates the alarm.
5
- Define which measurement of the device as the first operand.
6
- Multiplying factor referred to previous measurement.
7
- Dividing factor referred to previous measurement.
8
- Math operation between first and second operands.
9, 10, 11, 12, 13
- (see above).
Power factor rules