pag. 15 / 22
SETPOINT menu
SETPOINT (SPn, n=1..32)
UoM
Default
Range
1
Enable
-
OFF
OFF-ON
2
Source
-
Internal measures
Internal measures-(measures node 1-20)
3
Group
-
Instantaneous
Instantaneous-Average-Energies-Digital input-
Counter-Analog input-Math-Energy TB1..16-
Harmonics VL1..VL3- Harmonics IL1..IL3-
Diagnostic
4
Item
-
-
OFF-(measures)
5
High threshold
-
0
-99999999 - +99999999
6
High threshold unit
-
-
(Unit of measures)
7
Low threshold
-
0
-99999999 - +99999999
8
Low threshold unit
-
-
(Unit of measures)
9
Activation delay
s
1
0-100000
10
Deactivation delay
s
1
0-100000
11
Hysteresis
%
0
0-100
12
Logic operation over
-
OFF
OFF-OR-AND
13
Logic operation entry
-
OFF
OFF-OR-AND
14
Operands 1-16
-
15
Operands 16-32
-
16
Action over
-
OFF
Save event-DO change-Increase event-
Increase timer-Work hours
17
Action entry
-
OFF
Save event-DO change
18
DO used
-
OFF
DO1..4-EXT DO
NOTE: this menu is divided into 32 sections, for alarm setpoints SP1..32
1
- If set to ON, the setpoint alarm is enabled.
2
- Measurement source that generates the alarm. Internal measures or measures referred to the external devices (when EMA-D6 will be configured as
Master RS-485).
3
- Measurement group that generates the alarm.
4
- Define which measurement of the device must be compared with limits.
5
- Used to define the upper threshold.
6
- Used to define the unit of measure of the upper threshold.
7
- Used to define the lower threshold.
8
- Used to define the unit of measure of the lower threshold.
9
- Alarm delay on upper threshold.
10
- Alarm delay on lower threshold.
11
- Hysteresis for the previous thresholds.
12
- Logic operation between operands for the upper threshold.
13
- Logic operation between operands for the lower threshold.
14, 15
- Define which setpoint used as operands for the previous thresholds.
16
- Alarm notification:
SAVE EVENT
- Log of alarm inside events list.
DO CHANGE
- When the alarm is tripped, the correspondent digital output is triggered.
INCREASE EVENT
- Increase the number of events above the alarm upper threshold.
INCREASE TIMER
- When the alarm is tripped, the correspondent timer (hh:mm:ss) is activated.
WORK HOURS
- Count of hours above the alarm upper threshold.
17
- Turn off alarm notification:
SAVE EVENT
- Log of turn off alarm inside events list.
DO CHANGE
- When the alarm is turning off, the correspondent digital output is triggered.
18
- If set DO change for the previous menu, define which digital output must be associated with an alarm.
SETPOINT (SPn, n=1..32)
UoM
Default
Range
1
Setpoint description
-
SETPOINT n
(text - 20 char)
NOTE: this menu is divided into 32 sections, for alarm setpoints SP1..32
1 - Alphanumeric description of the setpoint. Free text 20 characters.