DIGITAL INPUT menu (optional)
DIGITAL INPUT (INPn, n=1..4)
Default
Range
1
Mode
Status
Status - Counter - Change energy TB - Change
Counter TB - Change energy and counter TB -
External trigger - Reset SP-DO
2
Multiplier
1
1-100000
3
Divisor
1
1-100000
4
Level action
Normally open
Normally open - Normally closed
5
SP-DO reset
-
Setpoint 1...Setpoint 32
6
Unit of measure
-
(Text - 20 char)
7
Description
-
(Text - 20 char)
NOTE: this menu is divided into 4 sections, for digital inputs INP1..4
1
- Function of the input:
Status
- Signal that generates the activation of the input.
Counter
- Signal that causes the increment of the counter.
Change energy TB
- Energy Timeband selection. See Energy timeband chapter.
Change Counter TB
- Counter Timeband selection. See Energy timeband chapter.
Change energy and counter TB
- Energy and Counter Timeband selection. See Energy timeband chapter.
External trigger
- When this input is activated (triggered), the correspondent command is executed.
Reset SP-DO
- When this input is activated (triggered), the correspondent setpoint reset is executed.
2
- Multiplying factor. If digital input is using as input pulses counter, the pulse counter is multiplied by this coefficient.
3
- Dividing factor. If digital input is using as input pulses counter, the pulse counter is divided by this coefficient.
4
- Status on activation of the input. Allows reversing the logic of the input function.
5
- When digital input is using as SP-DO reset, select the number of setpoint to reset.
6
- Description of digital input. Free text 20 characters. If digital input is using as input pulses counter.
7
- Unit of measure of digital input. Free text 20 characters. If digital input is using as input pulses counter.
EXPANSION MODULE ANALOG OUTPUT menu
Expansion Analog Output (AOn, n=1..8)
Default
Range
1
Output type
4…20mA
4…20mA
0…2
0mA
0…10V
0…5V
-
10…10V
-5
…5V
2
Source
Internal
Internal
3
Group
Instantaneous
Instantaneous
4
Item
-
OFF - (measures)
5
MAX value
0
-999999 - +999999
6
MAX unit
-
Unit measure of selected measurement
7
MIN value
0
-999999 - +999999
8
MIN unit
-
Unit measure of selected measurement
Note:
this menu is divided into 8 sections, for external analog outputs board MR-AO
…
8
1
- Defines the type of the analog sensor connected to analog output.
2
- Electrical parameter that controls the value of analog output.
INTERNAL
- Measures provide from device.
3
- Measurements group.
INSTANTANEOUS:
Actual instantaneous values of reading.
4
- Select the electrical parameter from the selected group.
5
- Define the value of the electrical parameter that corresponds to an output to the maximum of the ra
nge (20mA, 10V, +5V, etc…)
7
- Define the value of the electrical parameter that corresponds to an output to the minimum of the range (0mA, 0V, -
5V, etc…)