4-20 mA Inputs
For an externally powered current loop, connect the transmitter to the input
terminals as shown in Figure 8. Refer to
for specific terminal numbers for this application.
Figure 8 Externally Powered Current Loop
The internal overload-protected power supply has sufficient power for three
current loops at 24 V DC (more current loops can be supplied by using a
reduced voltage setting). Connect internally powered current loops as
shown in Figure 9.
Figure 9 Internally Powered Current Loops
Logic Input Connection
These input(s) are designed to be connected to CMOS, TTL, open collector
signals or a voltage free contact switch. A minimum activation time of
300ms is required to guarantee reading of an input.
It is possible to read the status of all the logic inputs via a Modbus register
even if they are not used for a control purpose in the application.
+
-