
414L-M-V3
Not counting.
If the Batcher does not count with the flowmeter connected
and flow passing through it, first check the connections and
then ensure the DIP switches on the rear of the instrument
are set as per section 7.
It is possible to manually test the input circuit of the Batcher
by setting the input configuration for a Reed Switch (see
Section 7) and pulsing across the signal (+) and (-) with a
wire link.
When doing this, the scaling factor should be set to 1 and
the resolution to whole numbers.
Counting erratically
This can be caused by two factors:
- setting the input circuit incorrectly
- lack of shielding on the input.
Shield the input signal with the shield earthed at the
Batch Controller only.
Instrument acting erratically
Erratic operation can be the result of severe
electrical interference.
Considerable attention has
been given to designing the Batch Controller to
withstand electrical interference.
However, in extreme cases, loads may be encountered which
are exceptionally inductive and may require additional
protection.
One measure is to use an RC Suppression Network as
described in Section 8.
Another remedy for this problem is to use an isolating relay
to switch the load, and use the Batcher to drive the
isolating relay.
The isolating relay should be mounted away from the
Batcher and from signal wiring.
76
Trouble Shooting