414L-M-V3
6.2 ENTERING THE BATCH PARAMETERS
Step
Display
Description
Text
Ref
1
BATCH
OPTION
TEST
END
CAL
Enter Batch Parameters.
Option (if installed)
Check Input Signals.
Exit to normal operation.
Program Setup
Parameters
.
6.3
6.4
6.1
The following steps are displayed if BATCH is selected.
2
TOTAL
Net
Gross
Batch on Gross total; or on Net Total
or Mass.
Net or Mass.
Gross.
3.2
3
BATCH L
xxxxxx
Maximum Batch Size which can be
entered.
Set to 0 if no limit on batch size.
3.2
4
AUTO S
Off
On
xx:xx
Automatic restart feature.
Disable.
Enable.
If enabled, automatically restarts
the batch xx:xx (mins:sec) after
the end of the last batch.
3.2.4
5
START. T
xx:xx
Slow start time.
Time, in (minutes:seconds), when
Relay 2 will energise once the batch
has started.
3.2
Calibration
55