9.3 ANTI CONDENSATION SWITCH (OPTIONAL)
This appliance has the option to switch from an electronic intermittent pilot
ignition (IPI) to a standing pilot (ACS) for cold climates.
The anti condensation switch (standing pilot) is
located in the center of the control panel. Using
your
fi
nger,
fl
ip the switch up for standing pilot, or
down for intermittent pilot ignition.
Adjust the pilot screw to provide properly sized
fl
ame. Turn in a
clockwise direction to reduce the gas
fl
ow.
Check Pressure Readings:
Inlet pressure can be checked by turning screw (A) counter-
clockwise 2 or 3 turns and then placing pressure gauge tubing
over the test point. Gauge should read 7” (minimum 4.5”) water
column for natural gas or 13” (11” minimum) water column for
propane. Check that main burner is operating on “HI”.
Outlet pressure can be checked the same as above using
screw (B). Gauge should read 3.5” water column for natural
gas or 10” water column for propane. Check that main burner
is operating on “HI”.
AFTER TAKING PRESSURE READINGS, BE SURE TO
TURN SCREWS CLOCKWISE FIRMLY TO RESEAL. DO
NOT OVERTORQUE.
Leak test with a soap and water solution.
39.1A
A
B
PILOT SCREW
FLAME MUST ENVELOP
UPPER 3/8” TO 1/2” OF
FLAME SENSOR
PILOT
BURNER
ELECTRODE
FLAME
SENSOR
This appliance has an air shutter that has been factory set open according
to the chart below:
Regardless of venturi orientation, closing the air shutter will cause a more
yellow flame, but can lead to carboning. Opening the air shutter will cause a
more blue flame, but can cause flame lifting from the burner ports. The
flame may not appear yellow immediately; allow 15 to 30 minutes for the
final flame colour to be established.
AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A QUALIFIED
INSTALLER!
AIR
SHUTTER
OPENING
VENTURI
BURNER
ORIFICE
49.1
VENTURI ADJUSTMENT CHART
FUEL
CLHD45
NG
1/32”
LP
1/8”
10.0 ADJUSTMENT
10.1 PILOT BURNER ADJUSTMENT
10.2 VENTURI ADJUSTMENT