Continental Fireplaces CLHD45N Installation And Operating Instructions Manual Download Page 34

34

W415-0895 / C / 03.13.12

6.4 GLASS 

EMBERS

NOTE: Care must be taken to ensure glass embers are kept .250” clear of the pilot area on the media 
tray and aren’t interfering with the pilot operation. 
Glass embers must not cover burner ports.
When the fl ames impinge on the glass, the glass may discolour slightly and the edges may soften.

74.2A

Evenly spread the glass media onto the media tray, ensuring no glass media falls onto the burner. If this hap-
pens, insert a clean bag into your vacuum cleaner and vacuum out the glass media. Replacement glass can 
be purchased from your local authorized dealer / distributor.

CLEANING GLASS MEDIA

Glass media may have a 

fi

 ne oil residue that needs to be cleaned prior to installation. Clean the glass with mild

dish soap, drain, rinse thoroughly and dry before placing around the burner.

CLEAN THE GLASS MEDIA PRIOR TO INSTALLATION. BEFORE APPLYING THE CLEANED GLASS, ENSURE 

THAT IT IS DRY.

DO NOT CHANGE OR SUBSTITUTE THE GLASS MEDIA MATERIAL PROVIDED WITH THIS APPLIANCE. IF 

REPLACING, USE ONLY THE REPLACEMENT GLASS MEDIA AVAILABLE FROM YOUR AUTHORIZED 

DEALER / DISTRIBUTOR.

!

WARNING

PILOT 

AREA

BURNER 

PORTS

Summary of Contents for CLHD45N

Page 1: ...your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualifi...

Page 2: ...NAL INSTALLATION 22 4 6 VERTICAL AIR TERMINAL INSTALLATION 22 4 7 USING FLEXIBLE VENTING 23 4 8 MOBILE HOME INSTALLATION 23 4 9 GAS INSTALLATION 24 5 0 FRAMING 25 5 1 MINIMUM CLEARANCE TO COMBUSTIBLE...

Page 3: ...IBLE ENCLOSURES section for drywall or other combustible material Framing see FRAMING section Side Wall Venting see VENTING section Framing see FRAMING section Enclosures see the section MINIMUM CLEAR...

Page 4: ...vented gas fired appliance Do not burn wood or other materials in the appliance It is imperative that the control compartments burners and circulating blower and its passageway in the appliance and v...

Page 5: ...5 W415 0895 C 03 13 12 2 1 DIMENSIONS 40 13 16 40 13 16 39 3 16 25 5 16 17 13 16 1 3 8 4 3 4 ELECTRICAL INLET ON LEFT SIDE GAS INLET 18 7 8 46 1 4 7 34 1 16 19 7 8 1 37 13 16 4 39 5 16 42 7 10 1 8...

Page 6: ...where the vent will pass through the house without cutting a floor or roof joist If the appliance is installed directly on carpeting vinyl tile or other combustible material other than wood flooring t...

Page 7: ...it is used Expansion contraction noises during heating up and cooling down cycles are normal and are to be expected NOTE The protective wrap on plated parts is best removed when the assembly is at roo...

Page 8: ...IL UTILISER AVEC LES PORTES VITR ES HOMOLOGU ES SEULEMENT AVEC CETTE UNIT AVERTISSEMENT 1 287 3 6 7 33 5 8 81 0 7e5 8 9 17 175 5 EN CONTACT AVEC LES FLAMMES AUTRE QUE CELUI QUI EST FOURNI AVEC CET APP...

Page 9: ...rigid flexible components with the following termination kits wall terminal kit GD222 GD222R or 1 12 to 7 12 pitch roof terminal kit GD110 8 12 to 12 12 roof terminal kit GD111 flat roof terminal kit...

Page 10: ...IMUM 16 MINIMUM 37 13 16 8 MINIMUM 18 MAXIMUM FLEX VENT 24 MAXIMUM RIGID VENT 45 13 16 MINIMUM PLUS RISE 3 2 TYPICAL VENT INSTALLATIONS See VENTING section 37 13 16 NOTE There MUST be a 25 reduction i...

Page 11: ...air slot is located a minimum 12 above grade The maximum allowable vent length is 10 for a fireplace and 8 for a stove 9 1A 12 MIN TO GRADE 24 MINIMUM 3 3 1 PERISCOPE TERMINATION 3 3 2 CORNER TERMINA...

Page 12: ...jacent wall including neighbouring buildings P 8 8 Roof must be non combustible without openings Q 3 3 See chart for wider wall dimensions R 6 6 See chart for deeper wall dimensions The terminal shall...

Page 13: ...ontal run 3 times the vertical rise equal to or greater than the horizontal run 3 5 VENT APPLICATION FLOW CHART 14 1 For the following symbols used in the venting calculations and examples are greater...

Page 14: ...T HT VT 9 9 11 20 9 FT Formula 1 HT VT 9 9 11 Formula 2 HT VT 40 FT 20 9 40 Since both formulas are met this vent configuration is acceptable See graph to determine the required vertical rise VT for t...

Page 15: ...2 x 6 25 2 FT 10 7 25 2 Formula 2 HT VT 24 75 FT 16 7 24 75 Since both formulas are met this vent configuration is acceptable 0 5 15 20 100 50 150 12 5 8 57 147 2 The shaded area within the lines rep...

Page 16: ...xample V1 5 FT V2 6 FT V3 10 FT VT V1 V2 V3 5 6 10 21 FT H1 8 FT H2 2 5 FT HR H1 H2 8 2 5 10 5 FT HO 03 four 90 elbows 90 03 360 90 8 1 FT HT HR HO 10 5 8 1 18 6 FT HT VT 18 6 21 39 6 FT Formula 1 HT...

Page 17: ...1 4 5 20 6 FT Formula 1 HT 3VT 3VT 3 x 4 5 13 5 FT 16 1 13 5 Since this formula is not met this vent configuration is unacceptable Formula 2 HT VT 40 feet 20 6 40 Since only formula 2 is met this vent...

Page 18: ...ce NOTE A vent adaptor will be required directly off the appliance Follow vent manufacturer s installation instructions Different manufacturer s venting components must not be combined Once the prefer...

Page 19: ...NS RISK OF FIRE DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE REMOVE INSULATION TO ALLOW FOR THE INSTALLATION OF THE ATTIC SHIELD AND TO MAINTAIN CLEARANCES TO COMBUSTIBLES 68 2A W...

Page 20: ...distributor See accessories to order specific kits required A Determine the air terminal location cut and frame a square opening as illustrated in the ceiling and the roof to provide the minimum 1 cl...

Page 21: ...position Measure the vent length required between terminal and appliance taking into account the additional length needed for the finished wall surface and any 1 overlaps between venting components B...

Page 22: ...enetrate the roof when fastened If the attic space is tight we recommend threading the Wolf Steel vent pipe collar or equivalent loosely onto the air terminal connector vent pipe assembly as it is pas...

Page 23: ...dealer distributor for the appropriate securing kit For mobile home installations the appliance must be fastened in place It is recommended that the appliance be secured in all installations Always t...

Page 24: ...on a soap and water solution Do not use open flame WARNING RISK OF FIRE EXPLOSION OR ASPHYXIATION ENSURE THERE ARE NO IGNITION SOURCES SUCH AS SPARKS OR OPEN FLAMES SUPPORT GAS CONTROL WHEN ATTACHING...

Page 25: ...Y CAUSE OVER HEATING AND FIRE PREVENT CONTACT WITH SAGGING OR LOOSE INSULATION OR FRAMING AND OTHER COMBUSTIBLE MATERIALS BLOCK OPENING INTO THE CHASE TO PREVENT ENTRY OF BLOWN IN INSULATION MAKE SURE...

Page 26: ...0 8 41 DO NOT BUILD INTO THIS AREA IT MUST BE LEFT CLEAR TO PROVIDE ADEQUATE CLEARANCE FOR THE VENT IN THIS 14 WIDE AREA CENTERED ALONG THE FRONT OF THE FIREPLACE NO COMBUSTIBLES ARE ALLOWED FIREPLACE...

Page 27: ...imum of 1 all around the vent pipe on all vertical runs to combustibles is required except for clearances in appliance enclosures Vertical vent sections within enclosures require a minimum clearance o...

Page 28: ...ed that the enclosure be ventilated at the top and bottom to circulate the hot air 5 1 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES See VENTING section 56 MIN ENCLOSURE HEIGHT TOP OF FIREPLACE OPENING...

Page 29: ...29 W415 0895 C 03 13 12 Finishing material may be secured directly to the appliance body where practical COMBUSTIBLE NON COMBUSTIBLE TOP OF APPLIANCE OPENING 46 30 16 14 42 2...

Page 30: ...o combustibles are maintained Non combustible material can be used provided the minimum clearances to combustible materials are applied The minimum enclosure volume must be increased by no less than t...

Page 31: ...h A 25 5 16 B 6 2 C 8 4 D 10 6 E 12 8 E D C B A TOP OF APPLIANCE OPENING WARNING RISK OF FIRE MAINTAIN ALL SPECIFIED AIR SPACE CLEARANCES TO COMBUSTIBLES FAILURE TO COMPLY WITH THESE INSTRUCTIONS MAY...

Page 32: ...r is secured to the top front edge of the firebox with two latches Pull the handles of the latches forward then lift the latches out from the door frame to release the top of the door Next pivot the d...

Page 33: ...33 W415 0895 C 03 13 12 2 1 6 2 LOGO PLACEMENT Place trim as shown into the slots of the right and left brackets behind the access panel LEFT BRACKET SHOWN 6 3 TRIM INSTALLATION...

Page 34: ...ag into your vacuum cleaner and vacuum out the glass media Replacement glass can be purchased from your local authorized dealer distributor CLEANING GLASS MEDIA Glass media may have a fine oil residue...

Page 35: ...E THE WIRE HARNESS PROVIDED IN THE BLOWER KIT IS A UNIVERSAL HARNESS WHEN INSTALLED ENSURE THAT ANY EXCESS WIRE IS CONTAINED PREVENTING IT FROM MAKING CONTACT WITH MOVING OR HOT OBJECTS 51 5 7 1 ACCES...

Page 36: ...AL section C Remove the fourteen screws from the valve train assembly Carefully lift the valve train assembly and turn off the manual shut off valve see GAS IN STALLATION section NOTE A new gasket may...

Page 37: ...r Ensure that the wires are routed safely away from hot objects and retained from the blower impellers Attach and secure the variable speed switch to the corner post However this is difficult to acces...

Page 38: ...TO THE ELECTRICAL CIRCUIT RISK OF ELECTRICAL SHOCK OR EXPLOSION DO NOT WIRE 110V TO THE VALVE OR TO THE APPLIANCE WALL SWITCH INCORRECT WIRING WILL DAMAGE CONTROLS ALL WIRING SHOULD BE DONE BY A QUAL...

Page 39: ...he appliance and remove the junction box assembly B Remove the one screw that secures the junction box to the junction box plate and slide off the clip C Route the supply wire through the 7 8 hole of...

Page 40: ...ND CONNECT TO OPTIONAL THERMOSTAT IPI BOARD DC SUPPLY TRANSFORMER VALVE ELECTRONIC This appliance comes equipped with a battery back up If this backup is used install 4 AA batteries not supplied into...

Page 41: ...WARNING IF YOU DO NOT FOLLOW THESE INSTRUC TIONS EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE INITIAL LIGHTING OF THE PILOT AND MAIN BURNERS MUST BE...

Page 42: ...using screw B Gauge should read 3 5 water column for natural gas or 10 water column for propane Check that main burner is operating on HI AFTER TAKING PRESSURE READINGS BE SURE TO TURN SCREWS CLOCKWIS...

Page 43: ...ant to periodically perform a visual check of the pilot and burner flames Compare them to the illustration provided If any flames appear abnormal call a service person FLAME MUST ENVELOP UPPER 3 8 TO...

Page 44: ...of the ports which may not be burning or are not burning properly D Check to see that the pilot flame is large enough to engulf the flame sensor and or thermocouple thermopile as well as reaches the...

Page 45: ...ormal cleaning procedures given but require specialized techniques Contact you local authorized dealer distributor for complete cleaning instructions HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTI...

Page 46: ...a glass cleaner or vinegar and towel to clean If not cleaned properly before operating for the first time the marks can cause permanent blemishes on the plating After the plating is cured the fingerpr...

Page 47: ...D WITH THIS APPLIANCE MAY RESULT IN PROPERTY DAMAGE OR PERSONAL INJURY WARNING 12 0 REPLACEMENTS COMPONENTS REF PART NO DESCRIPTION 1 W475 0680 CEMENT BOARD 2 W010 2222 BLACK DOOR FRAME 3 W010 2109 AS...

Page 48: ...RM MULTI COLOURED RIVER ROCKS 40 GA 72 HOT AIR EXHAUST KIT 41 GA 70 EXTENSION KIT 5FT 42 GA 566 HOT AIR DISTRIBUTION KIT 43 MKGK GLASS EMBERS BLACK 43 MKGB GLASS EMBERS BLUE 43 MKGR GLASS EMBERS RED 4...

Page 49: ...49 W415 0895 C 03 13 12 1 3 5 4 15 14 7 16 13 2 7 9 8 10 11...

Page 50: ...50 W415 0895 C 03 13 12 28 29 56 36 AT TE NT ION CH AU D CA UT ION HO T 32 31 30 42 41 40 57 37 21 22 23 27 25 26 24...

Page 51: ...into the module Check voltage of the transformer under load at the spade connections on the module with the ON OFF switch in the ON position Acceptable readings of a good transformer are between 6 2...

Page 52: ...me rectification Verify correct pilot orifice is installed and inlet gas specifications to manual Remember the flame carries the rectification current not the gas If the flame lifts from pilot hood th...

Page 53: ...r plate See RESTRICTING VENTS section if applicable Main burner flame is a blue lazy transparent flame Blockage in vent Remove blockage In really cold conditions ice buildup may occur on the terminal...

Page 54: ...ironmental conditions such as rooftops buildings nearby trees hills mountains inadequate vents or ventilation excessive venting configurations insufficient makeup air or negative air pressures which m...

Page 55: ...55 W415 0895 C 03 13 12 15 0 SERVICE HISTORY 43 1...

Page 56: ...56 W415 0895 C 03 13 12...

Reviews: