For aesthetics, the adapter has been designed to accept
a standard matte black 7" stove pipe and the Continental
decorative brass band (standard with the GS-150KT). Both
are available from your Continental dealer.
B-VENT MODEL CS280 ONLY:
Attach the B-Vent label, shown below, in the control
area of the appliance.
COMBUSTION AIR
A CHIMNEY VENTING THIS STOVE SHALL NOT VENT
ANY SOLID FUEL BURNING APPLIANCE.
ALL HORIZONTAL RUNS MUST HAVE A MINIMUM ¼
INCH RISE PER FOOT.
ANY STOVE NEEDS AIR FOR SAFE OPERATION AND
MUST BE INSTALLED IN SUCH A WAY THAT ADEQUATE
COMBUSTION AIR IS AVAILABLE.
ADDING VENT SECTIONS:
For ease of assembly, a
7" telescoping stove pipe may
be installed over the 4" vent
connection of the adapter. Add
vent sections, twist locking
(clockwise) securely, to the
required height. The vent
should extend, at least, 3 feet
above its point of contact with
the roof and, at least, 2 feet
higher than any wall, roof or
building within 10 feet. (This
is a guideline only; local
venting codes should be
followed which may differ in
height and clearance require-
ments.)
Continue with "Gas Installation" Page 13
INSTALLING FLASHING AND STORM
COLLAR
Remove nails
from the shingles
above and to the
sides of the chim-
ney. Place the
flashing over the
vent pipe and
slide it under-
neath the sides
and upper edge
of the shingles.
Ensure that the
vent pipe is properly centered within the flashing, giving a
3/4" margin all around. Fasten to the roof on the top and
sides. DO NOT NAIL through the lower portion of the flash-
ing. Make weather-tight by sealing with caulking. Where
possible, cover the sides and top edges of the flashing
with roofing material.
Apply waterproof caulking around the vent, 1" above the
top of the flashing and push the storm collar down into the
caulking. Attach a rain cap to the top of the last vent section.
ATTACH THIS LABEL IN THE CONTROL AREA OF THE FIREPLACE.
THIS FIREPLACE HAS BEEN CONVERTED TO A ‘B’VENT MODEL.
ATTACHEZ CET ETIQUETTE DANS LA REGION DE CONTROLE DU FOYER.
CE FOYER A ETE CONVERTI A UN MODELE A SYSTEME D’EVACUATION ‘B’.