background image

48

W415-0570 / E / 04.23.12

SYMPTOM

PROBLEM

TEST SOLUTION

Pilot will not light.

No spark at pilot burner.

 

-

Check if pilot can be lit by a match.

 

-

Check that the wire is connected to the push button igniter.  

 

-

Check if the push button igniter needs tightening.

 

-

Replace the wire if the wire insulation is broken or frayed.

 

-

Replace the electrode if the ceramic insulator is cracked 
or broken.

 

-

Replace the push button ignitor

Out of propane gas.

 

-

Fill the tank.

Spark gap is incorrect.

 

-

Spark gap should be 0.150” to 0.175” (5/32” to 11/64” 
approx.) from the electrode tip and the pilot burner. To 
ensure proper electrode location, tighten securing nut 
(

fi

 nger tight plus 1/4 turn).

No gas at the pilot burner.

 

-

Check that the manual valve is turned on.

 

-

Check the pilot ori

fi

 ce for blockage.

 

-

Replace the valve.

 

-

Call the gas distributor.

Flames are consistently 
too large or too small. 
Carboning occurs.

Unit is over-

fi

 red or under

fi

 red.

 

-

Check pressure readings: 

 

-

Inlet pressure can be checked by turning screw (A) 
counter-clockwise 2 or 3 turns and then placing pressure 
gauge tubing over the test point. Gauge should read 

7” (minimum 4.5”) water column for natural gas or 13” 
(minimum 11”) water column for propane. Check with 
main burner is operating on ‘HI’.

 

-

Outlet pressure can be checked the same as above 
using screw (B). Gauge should read 3.5” water column 
for natural gas or 10” water column for propane. Check 
that main burner is operating on ‘HI’.

 

-

AFTER TAKING PRESSURE READINGS, BE SURE TO 
TURN SCREWS CLOCKWISE FIRMLY TO RESEAL. 
DO NOT OVER  TORQUE.

 

-

Leak test with a soap and water solution.

Flames are very aggressive.

Door is ajar.

 

-

Ensure the mechanical means of securing the door is 
providing a tight seal.

Carbon is being 
deposited on glass, logs 
or combustion chamber 
surfaces.

Air shutter has become 
blocked.

 

-

Ensure air shutter opening is free of lint or other 
obstructions.

Flame is impinging on the logs 
or combustion chamber.

 

-

Check that the logs are correctly positioned.

 

-

Open air shutter to increase the primary air.

 

-

Check the input rate: check the manifold pressure and 
ori

fi

 ce size as speci

fi

 ed by the rating plate values.

 

-

Check that the door gasketing is not broken or missing 
and that the seal is tight.

 

-

Check that both vent liners are free of holes and well 
sealed at all joints.

 

-

Check that minimum rise per foot has been adhered to 
for any horizontal venting.

White / grey 

fi

 lm forms.

Sulphur from fuel is being 
deposited on glass, logs or 
combustion chamber surfaces.

 

-

Clean the glass with a recommended gas appliance 
glass cleaner. 

 

-

DO NOT CLEAN GLASS WHEN HOT.

 

-

If deposits are not cleaned off regularly, the glass may 
become  permanently marked.

Exhaust fumes smelled in 
room, headaches.

Appliance is spilling.

 

-

Ensure exhaust bracket gasket seal.

 

-

Check door seal and relief 

fl

 ap seal.

 

-

Check for chimney blockage.

 

-

Check that chimney is installed to building code.

 

-

Room is in negative pressure; increase fresh air supply.

 

-

Check cap gasket on the 

fl

 ue pipe assembly.

Remote wall switch is in 
’OFF’ position; main burner 
comes on when gas knob 
is turned to ‘ON’ position.

Wall switch is mounted upside down.

 

-

Reverse.

Remote wall switch is grounding.

 

-

Replace.

Remote wall switch wire is grounding.

 

-

Check for ground (short); repair ground or replace wire.

Faulty valve.

 

-

Replace.

42.3_2B

P

I

PILOT

N

O

L

O

T

H

I

L O

F

F O

A

B

PILOT 

BURNER

THERMOCOUPLE

THERMOPILE

Summary of Contents for CDV70NT

Page 1: ...ediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performe...

Page 2: ...L AIR TERMINAL INSTALLATION 22 4 3 2 VERTICAL AIR TERMINAL INSTALLATION 23 4 4 GAS INSTALLATION 24 4 5 OPTIONAL WALL SWITCH THERMOSTAT 25 4 6 MOBILE HOME INSTALLATION 25 5 0 FRAMING 26 5 1 MINIMUM CLE...

Page 3: ...ction Louvre see LOUVRE INSTALLATION section Venting see VENTING section Logo see LOGO PLACEMENT section See FINISHING section for Log shipping bracket Decorative panels Charcoal Strip Log placement C...

Page 4: ...tive that the control compartments burners and circulating blower and its passageway in the appliance and venting system are kept clean The appliance and its venting system should be inspected before...

Page 5: ...DOOR OPENED OR REMOVED PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE PROVIDE ADEQUATE VENTILATION NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE OBJECTS PLACED IN FRONT OF T...

Page 6: ...st be electrically connected and grounded in accordance with local codes use the current CSA C22 1 Canadian Electrical Code in Canada or the ANSI NFPA 70 National Electrical code in the United States...

Page 7: ...EXTENSIONS PLUS GRANDES SEE OWNER S INSTRUCTION MANUAL FOR MINIMUM AND MAXIMUM VENT LENGTHS R F RER AU MANUEL D INSTALLATION DE PROPRI TAIRE POUR LES LONGUEURS D VACUATION MINIMALE ET MAXIMALE UN COM...

Page 8: ...the vent air intake system is disassembled reinstall per the instructions provided for the initial installation WARNING RISK OF FIRE MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE...

Page 9: ...on below grade With flexible venting in conjunction with the various terminations use either the 5 foot vent kit GD220 or the 10 foot vent kit GD330 Foroptimumflameappearanceandapplianceperformance ke...

Page 10: ...TION 13 3 4 MIN 36 24 MAXIMUM 49 3 4 MINIMUM PLUS RISE See VENTING section 3 FEET MINIMUM 40 FEET MAXIMUM 16 MINIMUM THE FIRST TWO FEET OF OUTER 7 DIAMETER VENT PIPE FROM THE APPLIANCE MUST BE WRAPPED...

Page 11: ...the periscope kit to locate the air termination above grade The periscope must be installed so that when final grading is completed the bottom air slot is located a minimum 12 above grade The maximum...

Page 12: ...uring buildings P 8 8 Roof must be non combustible without openings Q 3 3 See chart for wider wall dimensions R 6 6 See chart for deeper wall dimensions The terminal shall not be installed on any wall...

Page 13: ...um of 40 feet 4 2 times the vertical rise equal to or greater than the horizontal run 3 times the vertical rise equal to or greater than the horizontal run 3 6 DEFINITIONS 14 1 For the following symbo...

Page 14: ...2 4 5 FT HO 03 three 90 elbows 90 03 270 90 5 4 FT HT HR HO 4 5 5 4 9 9 FT HT VT 9 9 11 20 9 FT Formula 1 HT VT 9 9 11 Formula 2 HT VT 40 FT 20 9 40 Since both formulas are met this vent configuratio...

Page 15: ...6 16 7 FT Formula 1 HT 4 2 VT 4 2 VT 4 2 x 6 25 2 FT 10 7 25 2 Formula 2 HT VT 24 75 FT 16 7 24 75 Since both formulas are met this vent configuration is acceptable 0 5 15 20 100 50 150 12 5 13 75 57...

Page 16: ...following formulas apply Formula 1 HT VT Formula 2 HT VT 40 feet Example V1 5 FT V2 6 FT V3 10 FT VT V1 V2 V3 5 6 10 21 FT H1 8 FT H2 2 5 FT HR H1 H2 8 2 5 10 5 FT HO 03 four 90 elbows 90 03 360 90 8...

Page 17: ...2 1 1 5 4 5 FT H1 6 FT H2 2 FT HR H1 H2 6 2 8 FT HO 03 four 90 elbows 90 03 360 90 8 1 FT HT HR HO 8 8 1 16 1 FT HT VT 16 1 4 5 20 6 FT Formula 1 HT 3VT 3VT 3 x 4 5 13 5 FT 16 1 13 5 Since this formu...

Page 18: ...ECT VENT COMPONENTS 3 SCREWS MUST ALSO BE USED TO ENSURE THE CONNECTION CANNOT SLIP OFF DO NOT CLAMP THE FLEXIBLE VENT PIPE RISK OF FIRE EXPLOSION OR ASPHYXIATION IMPROPER SUPPORT OF THE ENTIRE VENTIN...

Page 19: ...trated in the ceiling and the roof to provide the minimum 1 clearance between the vent pipe and any combustible material Try to center the vent pipe location midway between two joists to prevent havin...

Page 20: ...quired length needed for the finished wall surface Apply a heavy bead of high temperature sealant W573 0007 Mill Pac not supplied to the inner sleeve of the air terminal Slip the vent pipe a minimum o...

Page 21: ...tor leaving a min 3 4 of the air terminal connector showing above the top of the flashing Slide the flashing underneath the sides and upper edge of the shingles Ensure that the air terminal connector...

Page 22: ...sealant W573 0007 Mill Pac not supplied with the exception of the appliance exhaust flue collar which must be sealed using Mill Pac 25 1 4 3 1 HORIZONTAL AIR TERMINAL INSTALLATION A Move the fireplac...

Page 23: ...f the air terminal connector Place the flashing over the air terminal connector and slide it underneath the sides and upper edge of the shingles Ensure that the air terminal connector is properly cent...

Page 24: ...ovide sufficient movement for shifting the burner assembly on it s side to aid with servicing components F Check for gas leaks by brushing on a soap and water solution Do not use open flame WARNING RI...

Page 25: ...of gas indicated on the rating plate A conversion kit is supplied with the mobile home appliance 29 1 This Mobile Manufactured Home Listed appliance comes factory equipped with a means to secure the u...

Page 26: ...NON COMBUSTIBLE MATERIALS MATERIALS CONSISTING ENTIRELY OF STEEL IRON BRICK TILE CONCRETE SLATE GLASS OR PLASTERS OR ANY COMBINATION THEREOF ARE SUITABLE MATERIALS THAT ARE REPORTED AS PASSING ASTM E...

Page 27: ...o the appliance when installed There must be a 1 inch air gap in addition to the insulation sleeve VERTICAL VENT SECTIONS A minimum of 1 all around the vent pipe on all vertical runs to combustibles i...

Page 28: ...ack painted surface of the ap pliance front and is required for use in conjunction with the GD425 kit This kit is designed to accommodate a noncombustible material to a maximum finished thickness of 3...

Page 29: ...NCE TO COMBUSTIBLE ENCLOSURES COMBUSTIBLE MATERIAL NONCOMBUSTIBLE MATERIAL 2 GAP FROM VENTING 19 1 2 MINIMUM TOP OF UNIT 1 GAP FROM INSULATIONSLEEVE FIRESTOP SPACER STEEL HEADER STAND OFF SPACER 4 3 8...

Page 30: ...e minimum clearances to combustibles are maintained Non combustible material can be used provided the minimum clearances to combustible materials are applied The minimum enclosure volume must be incre...

Page 31: ...RISK OF FIRE MAINTAIN ALL SPECIFIED AIR SPACE CLEARANCES TO COMBUSTIBLES FAILURE TO COMPLY WITH THESE INSTRUCTIONS MAY CAUSE A FIRE OR CAUSE THE APPLIANCE TO OVERHEAT ENSURE ALL CLEARANCES I E BACK S...

Page 32: ...UNTIL COOLED THE DOOR LATCHES ARE PART OF A SAFETY SYSTEM AND MUST BE PROPERLY ENGAGED DO NOT OPERATE THE APPLIANCE WITH LATCHES DISENGAGED FACING AND OR FINISHING MATERIALS MUST NOT INTERFERE WITH AI...

Page 33: ...Y AND DELAYED IGNITION MAY OCCUR THE LOGS ARE FRAGILE AND SHOULD BE HANDLED WITH CARE 76 1A 6 3 LOG SHIPPING BRACKET Before installing the logs you must first remove the log ship ping bracket Loosen t...

Page 34: ...n log 3 onto the right most grate rail with the charred face to the front Align the groove on the underside of the log with the rail of the grate Push the log back to the pilot housing Log 3 should fi...

Page 35: ...burner 6 9 LOUVRE INSTALLATION A B A B SLOT TAB SLOT HINGE CLIP 57 1A UPPER LOUVRES Insert the louvre tabs into the slots located at the top left and right corners of the unit LOWER LOUVRES Insert the...

Page 36: ...NT NATIONAL ELECTRIC CODE ANSI NFPA NO 70 IN THE UNITED STATES ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RAN OUT WITH THE GLASS DOOR OPENED OR REMOVED 69 2 The NIGHT L...

Page 37: ...e lit until the thermo couple has cooled Allow approximately 60 seconds for the thermocouple to cool When lighting and re lighting the gas knob cannot be turned from pilot to off unless the knob is de...

Page 38: ...Shutter Openings Front LP 1 2 NG 1 4 This appliance has an air shutter that has been factory set open according to the chart below Regardless of venturi orientation closing the air shutter will cause...

Page 39: ...2 OF THERMOCOUPLE THERMOPILE 9 4 RESTRICTING VERTICAL VENTS 77 3 Vertical installations may display a very active flame If this appearance is not desirable the vent exit must be restricted using a re...

Page 40: ...of the ports which may not be burning or are not burning properly D Check to see that the pilot flame is large enough to engulf the flame sensor and or thermocouple thermopile as well as reaches the...

Page 41: ...lf Steel parts only as lamp and lens are spe cial high temperature products When re installing ensure integrity of gasket seal THE FIREBOX MUST BE SEALED NOTE Over tightening the screws could break th...

Page 42: ...t covered by the warranty policy 10 3 BLOWER REPLACEMENT WARNING RISK OF FIRE AND ELECTRICAL SHOCK TURN OFF THE GAS AND ELECTRICAL POWER BEFORE SERVICING THIS APPLIANCE USE ONLY WOLF STEEL APPROVED OP...

Page 43: ...LTD WARNING NOTE Care must be taken when removing and disposing of any broken glass or damaged components Be sure to vacuum up any broken glass from inside the appliance before operation COMPONENTS RE...

Page 44: ...40 W170 0063 STORM COLLAR 41 W263 0054 ROOF FLASHING GD 111 ROOF TERMINAL KIT 8 12 TO 12 12 PITCH 37 W670 0006 VERTICAL CAP 38 W490 0073 INNER OUTER SLEEVE 39 W010 0567 ROOF SUPPORT 40 W170 0063 STORM...

Page 45: ...AB LOUVRE KIT UPPER LOWER ANTIQUE BRASS 62 L38PB LOUVRE KIT UPPER LOWER POLISHED BRASS 62 L38SS LOUVRE KIT UPPER LOWER STAINLESS STEEL 63 KB 35 VARIABLE SPEED SWITCH 64 W500 0033 V S S MOUNTING PLATE...

Page 46: ...46 W415 0570 E 04 23 12 36 38 39 17 14 18 13 49 56 28 23 12 45 44 63 27 67 16 55 6 4 1 2 3 54 9 24 5 68 41 36 15 37 40 42 73 36 53...

Page 47: ...valve Faulty valve Replace Pilot burning no gas to main burner gas knob is on HI wall switch thermostat is on Thermostat or switch is defective Connect a jumper wire across the wall switch terminals i...

Page 48: ...ames are very aggressive Door is ajar Ensure the mechanical means of securing the door is providing a tight seal Carbon is being deposited on glass logs or combustion chamber surfaces Air shutter has...

Page 49: ...ironmental conditions such as rooftops buildings nearby trees hills mountains inadequate vents or ventilation excessive venting configurations insufficient makeup air or negative air pressures which m...

Page 50: ...50 W415 0570 E 04 23 12 14 0 SERVICE HISTORY 43 1...

Page 51: ...51 W415 0570 E 04 23 12 16 0 NOTES 44 1...

Page 52: ...52 W415 0570 E 04 23 12...

Reviews: