background image

12

W415-0570 / E / 04.23.12

INSTALLATIONS

CANADA

U.S.A.

A

12”

12”

Clearance above grade, veranda porch, deck or balcony.

B

12” 

Δ

9” 

Δ

Clearance to windows or doors that open.

C

12” *

12” *

Clearance to permanently closed windows.

D

18” **

18” **

Vertical clearance to ventilated sof

fi

 ts located above the terminal within a horizontal distance of 2’ from 

the center line of the terminal.

E

12” **

12” **

Clearance to unventilated sof

fi

 t.

F

0”

0”

Clearance to an outside corner wall.

G

0” ***

0” ***

Clearance to an inside 

non

-combustible corner wall or protruding 

non

-combustible obstructions (chimney, etc.).

2” ***

2” ***

Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).

H

3’

3’ ****

Clearance to each side of the center line extended above the meter / regulator assembly to a maximum 
vertical distance of 15’.

I

3’

3’ ****

Clearance to a service regulator vent outlet.

J

12”

9”

Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.

K

6’

3’ †

Clearance to a mechanical air supply inlet.

L

7’ ‡

7’ ****

Clearance above a paved sidewalk or paved driveway located on public property.

M

12” ††

12” ****

Clearance under a veranda, porch or deck.

N

16”

16”

Clearance above the roof.

O

2’ †*

2’ †*

Clearance from an adjacent wall including neighbouring buildings.

P

8’

8’

Roof must be 

non

-combustible without openings.

Q

3’

3’

See chart for wider wall dimensions.

R

6’

6’

See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an open-
ing between the terminal and the open side of the structure.

S

12”

12”

Clearance under a covered balcony

Δ

The terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.

*

Recommended to prevent condensation on windows and thermal breakage

**

It is recommended to use a heat shield and to maximize the distance to vinyl clad sof

fi

 ts.

***

The periscope requires a minimum 18 inches clearance from an inside corner.

****

This is a recommended distance. For additional requirements check local codes.

3 feet above if within 10 feet horizontally.

A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.

††

Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the 

fl

 oor.

†*

Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.

††*

Permitted only if the balcony is fully open on a minimum of one side.

12.1C

NOTE:  Clearances are in accordance with local installation codes and the requirements of the gas supplier.

COVERED BALCONY APPLICATIONS 

††*

Q

MIN

R

MAX

MAX

R

= 3 feet

= 2 x 

”

 

 feet

Q

ACTUAL

R

Q

S

G

P

3.4  VENT TERMINAL CLEARANCES

Summary of Contents for CDV70NT

Page 1: ...ediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performe...

Page 2: ...L AIR TERMINAL INSTALLATION 22 4 3 2 VERTICAL AIR TERMINAL INSTALLATION 23 4 4 GAS INSTALLATION 24 4 5 OPTIONAL WALL SWITCH THERMOSTAT 25 4 6 MOBILE HOME INSTALLATION 25 5 0 FRAMING 26 5 1 MINIMUM CLE...

Page 3: ...ction Louvre see LOUVRE INSTALLATION section Venting see VENTING section Logo see LOGO PLACEMENT section See FINISHING section for Log shipping bracket Decorative panels Charcoal Strip Log placement C...

Page 4: ...tive that the control compartments burners and circulating blower and its passageway in the appliance and venting system are kept clean The appliance and its venting system should be inspected before...

Page 5: ...DOOR OPENED OR REMOVED PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE PROVIDE ADEQUATE VENTILATION NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE OBJECTS PLACED IN FRONT OF T...

Page 6: ...st be electrically connected and grounded in accordance with local codes use the current CSA C22 1 Canadian Electrical Code in Canada or the ANSI NFPA 70 National Electrical code in the United States...

Page 7: ...EXTENSIONS PLUS GRANDES SEE OWNER S INSTRUCTION MANUAL FOR MINIMUM AND MAXIMUM VENT LENGTHS R F RER AU MANUEL D INSTALLATION DE PROPRI TAIRE POUR LES LONGUEURS D VACUATION MINIMALE ET MAXIMALE UN COM...

Page 8: ...the vent air intake system is disassembled reinstall per the instructions provided for the initial installation WARNING RISK OF FIRE MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE...

Page 9: ...on below grade With flexible venting in conjunction with the various terminations use either the 5 foot vent kit GD220 or the 10 foot vent kit GD330 Foroptimumflameappearanceandapplianceperformance ke...

Page 10: ...TION 13 3 4 MIN 36 24 MAXIMUM 49 3 4 MINIMUM PLUS RISE See VENTING section 3 FEET MINIMUM 40 FEET MAXIMUM 16 MINIMUM THE FIRST TWO FEET OF OUTER 7 DIAMETER VENT PIPE FROM THE APPLIANCE MUST BE WRAPPED...

Page 11: ...the periscope kit to locate the air termination above grade The periscope must be installed so that when final grading is completed the bottom air slot is located a minimum 12 above grade The maximum...

Page 12: ...uring buildings P 8 8 Roof must be non combustible without openings Q 3 3 See chart for wider wall dimensions R 6 6 See chart for deeper wall dimensions The terminal shall not be installed on any wall...

Page 13: ...um of 40 feet 4 2 times the vertical rise equal to or greater than the horizontal run 3 times the vertical rise equal to or greater than the horizontal run 3 6 DEFINITIONS 14 1 For the following symbo...

Page 14: ...2 4 5 FT HO 03 three 90 elbows 90 03 270 90 5 4 FT HT HR HO 4 5 5 4 9 9 FT HT VT 9 9 11 20 9 FT Formula 1 HT VT 9 9 11 Formula 2 HT VT 40 FT 20 9 40 Since both formulas are met this vent configuratio...

Page 15: ...6 16 7 FT Formula 1 HT 4 2 VT 4 2 VT 4 2 x 6 25 2 FT 10 7 25 2 Formula 2 HT VT 24 75 FT 16 7 24 75 Since both formulas are met this vent configuration is acceptable 0 5 15 20 100 50 150 12 5 13 75 57...

Page 16: ...following formulas apply Formula 1 HT VT Formula 2 HT VT 40 feet Example V1 5 FT V2 6 FT V3 10 FT VT V1 V2 V3 5 6 10 21 FT H1 8 FT H2 2 5 FT HR H1 H2 8 2 5 10 5 FT HO 03 four 90 elbows 90 03 360 90 8...

Page 17: ...2 1 1 5 4 5 FT H1 6 FT H2 2 FT HR H1 H2 6 2 8 FT HO 03 four 90 elbows 90 03 360 90 8 1 FT HT HR HO 8 8 1 16 1 FT HT VT 16 1 4 5 20 6 FT Formula 1 HT 3VT 3VT 3 x 4 5 13 5 FT 16 1 13 5 Since this formu...

Page 18: ...ECT VENT COMPONENTS 3 SCREWS MUST ALSO BE USED TO ENSURE THE CONNECTION CANNOT SLIP OFF DO NOT CLAMP THE FLEXIBLE VENT PIPE RISK OF FIRE EXPLOSION OR ASPHYXIATION IMPROPER SUPPORT OF THE ENTIRE VENTIN...

Page 19: ...trated in the ceiling and the roof to provide the minimum 1 clearance between the vent pipe and any combustible material Try to center the vent pipe location midway between two joists to prevent havin...

Page 20: ...quired length needed for the finished wall surface Apply a heavy bead of high temperature sealant W573 0007 Mill Pac not supplied to the inner sleeve of the air terminal Slip the vent pipe a minimum o...

Page 21: ...tor leaving a min 3 4 of the air terminal connector showing above the top of the flashing Slide the flashing underneath the sides and upper edge of the shingles Ensure that the air terminal connector...

Page 22: ...sealant W573 0007 Mill Pac not supplied with the exception of the appliance exhaust flue collar which must be sealed using Mill Pac 25 1 4 3 1 HORIZONTAL AIR TERMINAL INSTALLATION A Move the fireplac...

Page 23: ...f the air terminal connector Place the flashing over the air terminal connector and slide it underneath the sides and upper edge of the shingles Ensure that the air terminal connector is properly cent...

Page 24: ...ovide sufficient movement for shifting the burner assembly on it s side to aid with servicing components F Check for gas leaks by brushing on a soap and water solution Do not use open flame WARNING RI...

Page 25: ...of gas indicated on the rating plate A conversion kit is supplied with the mobile home appliance 29 1 This Mobile Manufactured Home Listed appliance comes factory equipped with a means to secure the u...

Page 26: ...NON COMBUSTIBLE MATERIALS MATERIALS CONSISTING ENTIRELY OF STEEL IRON BRICK TILE CONCRETE SLATE GLASS OR PLASTERS OR ANY COMBINATION THEREOF ARE SUITABLE MATERIALS THAT ARE REPORTED AS PASSING ASTM E...

Page 27: ...o the appliance when installed There must be a 1 inch air gap in addition to the insulation sleeve VERTICAL VENT SECTIONS A minimum of 1 all around the vent pipe on all vertical runs to combustibles i...

Page 28: ...ack painted surface of the ap pliance front and is required for use in conjunction with the GD425 kit This kit is designed to accommodate a noncombustible material to a maximum finished thickness of 3...

Page 29: ...NCE TO COMBUSTIBLE ENCLOSURES COMBUSTIBLE MATERIAL NONCOMBUSTIBLE MATERIAL 2 GAP FROM VENTING 19 1 2 MINIMUM TOP OF UNIT 1 GAP FROM INSULATIONSLEEVE FIRESTOP SPACER STEEL HEADER STAND OFF SPACER 4 3 8...

Page 30: ...e minimum clearances to combustibles are maintained Non combustible material can be used provided the minimum clearances to combustible materials are applied The minimum enclosure volume must be incre...

Page 31: ...RISK OF FIRE MAINTAIN ALL SPECIFIED AIR SPACE CLEARANCES TO COMBUSTIBLES FAILURE TO COMPLY WITH THESE INSTRUCTIONS MAY CAUSE A FIRE OR CAUSE THE APPLIANCE TO OVERHEAT ENSURE ALL CLEARANCES I E BACK S...

Page 32: ...UNTIL COOLED THE DOOR LATCHES ARE PART OF A SAFETY SYSTEM AND MUST BE PROPERLY ENGAGED DO NOT OPERATE THE APPLIANCE WITH LATCHES DISENGAGED FACING AND OR FINISHING MATERIALS MUST NOT INTERFERE WITH AI...

Page 33: ...Y AND DELAYED IGNITION MAY OCCUR THE LOGS ARE FRAGILE AND SHOULD BE HANDLED WITH CARE 76 1A 6 3 LOG SHIPPING BRACKET Before installing the logs you must first remove the log ship ping bracket Loosen t...

Page 34: ...n log 3 onto the right most grate rail with the charred face to the front Align the groove on the underside of the log with the rail of the grate Push the log back to the pilot housing Log 3 should fi...

Page 35: ...burner 6 9 LOUVRE INSTALLATION A B A B SLOT TAB SLOT HINGE CLIP 57 1A UPPER LOUVRES Insert the louvre tabs into the slots located at the top left and right corners of the unit LOWER LOUVRES Insert the...

Page 36: ...NT NATIONAL ELECTRIC CODE ANSI NFPA NO 70 IN THE UNITED STATES ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RAN OUT WITH THE GLASS DOOR OPENED OR REMOVED 69 2 The NIGHT L...

Page 37: ...e lit until the thermo couple has cooled Allow approximately 60 seconds for the thermocouple to cool When lighting and re lighting the gas knob cannot be turned from pilot to off unless the knob is de...

Page 38: ...Shutter Openings Front LP 1 2 NG 1 4 This appliance has an air shutter that has been factory set open according to the chart below Regardless of venturi orientation closing the air shutter will cause...

Page 39: ...2 OF THERMOCOUPLE THERMOPILE 9 4 RESTRICTING VERTICAL VENTS 77 3 Vertical installations may display a very active flame If this appearance is not desirable the vent exit must be restricted using a re...

Page 40: ...of the ports which may not be burning or are not burning properly D Check to see that the pilot flame is large enough to engulf the flame sensor and or thermocouple thermopile as well as reaches the...

Page 41: ...lf Steel parts only as lamp and lens are spe cial high temperature products When re installing ensure integrity of gasket seal THE FIREBOX MUST BE SEALED NOTE Over tightening the screws could break th...

Page 42: ...t covered by the warranty policy 10 3 BLOWER REPLACEMENT WARNING RISK OF FIRE AND ELECTRICAL SHOCK TURN OFF THE GAS AND ELECTRICAL POWER BEFORE SERVICING THIS APPLIANCE USE ONLY WOLF STEEL APPROVED OP...

Page 43: ...LTD WARNING NOTE Care must be taken when removing and disposing of any broken glass or damaged components Be sure to vacuum up any broken glass from inside the appliance before operation COMPONENTS RE...

Page 44: ...40 W170 0063 STORM COLLAR 41 W263 0054 ROOF FLASHING GD 111 ROOF TERMINAL KIT 8 12 TO 12 12 PITCH 37 W670 0006 VERTICAL CAP 38 W490 0073 INNER OUTER SLEEVE 39 W010 0567 ROOF SUPPORT 40 W170 0063 STORM...

Page 45: ...AB LOUVRE KIT UPPER LOWER ANTIQUE BRASS 62 L38PB LOUVRE KIT UPPER LOWER POLISHED BRASS 62 L38SS LOUVRE KIT UPPER LOWER STAINLESS STEEL 63 KB 35 VARIABLE SPEED SWITCH 64 W500 0033 V S S MOUNTING PLATE...

Page 46: ...46 W415 0570 E 04 23 12 36 38 39 17 14 18 13 49 56 28 23 12 45 44 63 27 67 16 55 6 4 1 2 3 54 9 24 5 68 41 36 15 37 40 42 73 36 53...

Page 47: ...valve Faulty valve Replace Pilot burning no gas to main burner gas knob is on HI wall switch thermostat is on Thermostat or switch is defective Connect a jumper wire across the wall switch terminals i...

Page 48: ...ames are very aggressive Door is ajar Ensure the mechanical means of securing the door is providing a tight seal Carbon is being deposited on glass logs or combustion chamber surfaces Air shutter has...

Page 49: ...ironmental conditions such as rooftops buildings nearby trees hills mountains inadequate vents or ventilation excessive venting configurations insufficient makeup air or negative air pressures which m...

Page 50: ...50 W415 0570 E 04 23 12 14 0 SERVICE HISTORY 43 1...

Page 51: ...51 W415 0570 E 04 23 12 16 0 NOTES 44 1...

Page 52: ...52 W415 0570 E 04 23 12...

Reviews: