W415-1706 / A / 07.13.17
EN
42
finishing
COMBUSTIBLE
NON-COMBUSTIBLE
COMBUSTIBLE
NON-COMBUSTIBLE
14”
(35.6cm)
K
32 13/16”
(83.3cm)
2 3/4”
(70mm)
2 3/4”
(70mm)
L
K
CBL36-1
37 1/16”
(94.1cm)
CBL46
48”
(121.9cm)
DOOR WITH
SAFETY
BARRIER
4” (101.6mm)
6” (152.4mm)
2” (50.8mm)
0” (0mm)
5” (127mm)
3”(76.2mm)
FIREPLACE
OPENING
11.3 installing non-combustible board
• Non-combustible facing material must not project more than 4” (102mm) from the face of the door (all three
sides). If greater projections are desired, increase the clearance to the sides and top by 2” (51mm) for every
additional 1” (25mm) of projection. If using an optional surround, the same rule applies, starting from the top
of the surround. Ensure clearances are maintained for surround removal, as it must lift off the appliance for
maintenance.
!
WARNING
L
CBL36-1
31 9/16”
(80.2cm)
CBL46
42 1/2”
(107.9cm)