5
o
Maximum CAT5/6 Extension Cable Run Length: 90 meters or 300 feet (1000 feet when
connected via dry contact inputs).
o
Radionuclide = Am-241
o
Type of substance (sealed / unsealed) = It is sealed
o
Physical form (solid / liquid / gas) = Solid.
o
Activity in Becquerel’s? = Less than 37,000 Becquerel’s.
1.4.
Smoke Detector OIDs:
o
For normal state, return value = 2
o
For alarm state, return value = 4
o
Note: You can test the smoke detector by holding down the test button until the audible
alarm occurs - about 5 sec. The smoke detector will then send an alarm signal to the unit.
Important:
The Web interface settings for the smoke detector are:
Direction:
Input
Normal State:
Open/+5 Volts
2.
Important Safety Information
Observe and follow all local and national electrical and building codes for installation.
This smoke detector is designed to be used inside a single room only. In multi-room buildings, each
individual room should have its own smoke detector. This smoke detector is not a substitute for a
complete fire alarm system.
Smoke may not reach the smoke detector for many reasons. For example, if a fire starts in a remote
part of a building or home, on another level, wall, roof, or on the other side of a closed door, smoke
may not reach the smoke detector in time to alert personnel. In other words the smoke detector will
not promptly detect a fire except in the area or room in which it is installed.
The smoke detectors can only sound their alarms when they detect smoke. The smoke detectors
detect combustion particles in the air. They do not sense heat, flame or gas. This smoke detector is
designed to give an audible warning of a developing fire. However, many fires are fast-burning,
explosive, or intentional. Others are caused by carelessness or safety hazards. So always keep in mind
that smoke may not reach the smoke detector alarm QUCKLY ENOUGH.
The smoke detectors have limitations. This smoke detector is not foolproof and is not warranted to
protect lives or property from fire. Smoke alarms are not a substitute for insurance. Business owners
are responsible for insuring their own lives and property. In addition it is possible for the smoke alarm
to fail at any time. For this reason, you must test the smoke detectors weekly and replace them every
10 years.
Summary of Contents for RMS-I-DE-01
Page 1: ...RMS I DE 01 Smoke Detector...