background image

 

 

 

TES

T  

 

 

 

After  the  3  seconds  command  extinguishing  starts 
accompanied  by  an  acoustic  signal.  The  sound  signal 
can  be  deactivated  by  the  “MUTE  ”button.  After 
extinguishing  ,  the  smoke  sensor  is  activated  and  it 
must be deactivated by the “RESET ”signal 

EXTINGUISHING 

Pressing the “RESET ”switch activates the operation of 
system restoration 

SYSTEM READY 

EXTINGUISHING 

.

 



After  the  termination  of  the  system  restoration 
process  by  reset,  the  system  is  ready  for  normal 
operation. The state is signalled. 

EXTINGUISHING 

SYSTEM READY 

BATTERY 

---       

 


G      

---   

 


If the horn was deactivated by “MUTE”, press “MUTE ”
again to activate it. The “MUTE ”signal lamp goes off. 
 

MUTE 

 

 

--- 

 

 

--- 

DI

SCO

N

N

ECT

IN

G

 T

H

EQUIPMEN

Disconnecting 
batteries 

If the equipment was disconnected from the network 
supply  for  a  long  time,  the  battery  will  be  gradually 
discharged.  In  this  case  electrically  disconnect  the 
batteries  from  the  system.  This  can  be  done  in  two 
ways: 

-

 

by pressing “TEST ”+ “RESET ”at the same time 

-

 

by switching the micro switch in the left lower 
part  of  the  box  which  is  accessible  from  the 
bottom after partially ejecting the box (about 
5 cm ) from the 19 “frame. 

 
 
 
 
 
 

BATTERY 

 
 
 
 

 
 
 
 
 
 

 
 
 
 
 
 

S50% 

 

Extinguishing 

After filling the tank with the extinguishing agent, mounting the equipment in the 19 “frame, testing it 
and connecting the batteries, the equipment is ready for normal operation. 

 

Table No. 3 : 

Operation 

Activity: 

Signalling 

LED diode 

colou

state 

EX

TI

N

G

UI

SHI

N

G

 

Activation 

 

The signal to activate “Extinguishing ”can be done in 
several ways i.e.: 

-

 

by the LES-RACK-M1 internal sensor  

-

 

by the external manual button 

-

 

by a signal from the external sensors

 

-

 

by a command through the network

 

After activation for 3 seconds

 

 
 
 
 
 
 
 
 

EXTINGUISHING 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

S50% 

Extinguishing 

After 3 seconds the extinguishing command is 
activated. The electromagnetic valve is opened and 
the pump is activated.  
Selected output relays are activated. 
The extinguishing is accompanied by an acoustic 
signal. The sound signal can be deactivated by the 
“MUTE ”button.  
After pressing the “MUTE ”button, the internal and 
external horns are deactivated 

EXTINGUISHING 

VALVE 

PUMP 

 
 

MUTE 

 

 

 
 
 

 

 

 
 
 

Summary of Contents for LES-RACK-M1

Page 1: ...dures for assembling commissioning operating and maintenance of the LES RACK M1 fire extinguisher The equipment must only be used for the described applications with the approved extinguishing agent F...

Page 2: ...19 Temperatures 20 Mail 21 Outputs 21 Date and time 22 Logs 22 Download 22 INSTALLATION 23 General provisions 23 Safety provisions 23 Assembling the equipment 23 Filling adding extinguishing liquid 23...

Page 3: ...g to the operating conditions and the maintenance plan In necessary the maintenance and service must be documented Device operators of must announce all changes and modifications of the monitored and...

Page 4: ...n in Fig 1 The fire fighting equipment consists of Tank with extinguishing agent 1 consisting of non pressure stainless storage vessel 1 filled with the extinguishing agent FK 5 1 12 dodekafluor 2 met...

Page 5: ......

Page 6: ...he energy requirements of the system during extinguishing AC inlet 13 for connecting the DC source 14 to 230V AC distribution network Control board 16 the heart of the system It concentrates and evalu...

Page 7: ...ress the micro switch to the left of the communication connector The internal relay is activated a click is heard and connects the battery to the system BATTERY G S De aerating the pump after adding f...

Page 8: ...at the same time by switching the micro switch in the left lower part of the box which is accessible from the bottom after partially ejecting the box about 5 cm from the 19 frame BATTERY R S50 Extingu...

Page 9: ...with the cap connect the external equipment on the rear face and insert the equipment back into the frame Secure The system error signal goes off FAULT SYSTEM Press TEST MUTE the pump is activated th...

Page 10: ...would escape outside the monitored space and its concentration for effectively extinguishing a fire would be insufficient The integrity of the circuit of the door contact is continuously monitored Th...

Page 11: ...ectors or other extinguishing equipment The inputs marked with the text Sensor 1 to Sensor 3 are for this The sensitivity of the external sensors circuits is also continuously monitored The connection...

Page 12: ...the network EXTINGUISHING R S50 3 seconds delay before extinguishing activated R S Extinguishing in progress or terminated Y S Extinguishing blocked door open FAULT SENSOR R S Fault sensor PUMP G S Th...

Page 13: ...operators by the extinguishing agent as well as decomposition products mainly by regular training The start of the fire extinguisher may be accompanied by a loud noise that could cause fright but not...

Page 14: ...isplayed To repeat the login close the browser and run it again it is its property and it is not possible to do otherwise NOTE Transferred login data is not encrypted ATTENTION The display may not be...

Page 15: ...state is displayed when MAJOR system error MINOR is in yellow The battery is disconnected from the system but it is present The fan is not rotating The level is low Here the state is displayed when Th...

Page 16: ...Network...

Page 17: ...IP address exchange address Gate must be typed even if it is not used Primary and secondary DNS if mail is used SNMP trap1 2 IP SNMP address of the server...

Page 18: ...ed Group extinguish group for common extinguishing If the exchanges have the same group with the exception of 0 if extinguishing is activated on any of them extinguishing on the others is activated Us...

Page 19: ...or failure sends the trap Mail change of the state or error sends e mail Error Major error is assigned to Major Error Minor error is assigned to Minor State Major the state is assigned to Mirror Stat...

Page 20: ...he line and press the Read sensor button and press the Save button Then select the temperature type the line disconnect the first sensor and connect the second sensor read serial number and save Repea...

Page 21: ...User Password SMTP server requires login To addressee of the mail From sender of the mail must be typed Subject Subject of the message Outputs Relay_ window used to change the name of the output The n...

Page 22: ...Date and time Logs Lists events from the newest to the oldest Download MIB opens the MIB file window LOG opens events window...

Page 23: ...the box From the front the skid has 3 holes with M5 threads with the same pitch as the 1U drilling in the 19 bar Fix the bar to the rear wall of the front 19 bar using the conical headed M5 bolt The r...

Page 24: ...network and operated connect the battery It must be connected for at least 12 hours to charge the backup source battery After charging the equipment must be disconnected and then it is possible to pu...

Page 25: ...are properly located and undamaged Inspection of signal lamps on the front panel Inspection after 1 month Checking that all staff who could work with equipment are properly trained and have appropriat...