Before  activating  and  commissioning  fill  the  tank  with  extinguishing  agent  or  check  the  extinguishing 
agent top it up, if necessary.  
The  equipment  can  be  controlled  by  elements  on  the  front  panel  or  remotely  by  inputs  on  the  rear 
panel. 
The location of the control elements and signal lamps on the front panel is shown in Fig. No.:2. 
All control elements and signal lamps are marked with a functional description - functional label. 
 

 

 
 

             

 

 

Table No. 2 : 

Operation 

Activity: 

Signalling 

LED diode 

colou

state 

IN

ST

AL

LAT

IO

N

 -

 A

CT

IV

A

TI

O

N

 

Inlet (13) 

 

Connection of AC supply to the inlet. The system is 
under pressure, the GU1 source supplies 12V DC 
voltage

 

 

SYSTEM READY 

 

 

The battery is not connected inside the box, is missing 
or has insufficient capacity 

BATTERY 

 

--- 

--- 

The battery is connected, electrically disconnected 

BATTERY 

 

S50% 

GB1 

battery 

connection  

Using an up to 3mm diameter rod (ball point pen) 
lightly  press  the  micro  switch  to  the  left  of  the 
communication  connector.  The  internal  relay  is 
activated (a click is heard) and connects the battery to 
the system. 
 

BATTERY 

 

De-aerating  the 
pump  

after  adding  fuel  or  after  handling  the  equipment 
outside the 19 “frame. 

 

 

 

Press TEST + MUTE, the pump is activated, the system 
is pressurized after disconnecting the pressure switch 
(max. 10 sec.) 

PUMP 

The 10 sec limit is exceeded and it is not pressurized.  
Repeat the procedure if it is not pressurized. If there is 
no pressure, then the pump or transport route of the 
extinguishing agent has failed 
 

PUMP 

TES

T  

    

   

    

 

Equipment test  
(without 
extinguishing) 

Press  the  “TEST  ”button  to  block  the  pump  and 
electromagnetic  valve  to  prevent  the  extinguishing 
agent escaping. The other processes run as with a real 
fire and extinguishing 

TEST 

Spraying  testing  gas  into  the  suction  hole  or  near  it 
will activate the smoke sensor 

EXTINGUISHING 

S50% 

Hole 

 

internal button for connecting batteries

 

Hole 

 

internal button for disconnecting batteries, on the lower side - 

about 1.5 cm from the left side of the box and 4 cm from the face. 

 

Obr.č. 2 

Summary of Contents for LES-RACK-M1

Page 1: ...dures for assembling commissioning operating and maintenance of the LES RACK M1 fire extinguisher The equipment must only be used for the described applications with the approved extinguishing agent F...

Page 2: ...19 Temperatures 20 Mail 21 Outputs 21 Date and time 22 Logs 22 Download 22 INSTALLATION 23 General provisions 23 Safety provisions 23 Assembling the equipment 23 Filling adding extinguishing liquid 23...

Page 3: ...g to the operating conditions and the maintenance plan In necessary the maintenance and service must be documented Device operators of must announce all changes and modifications of the monitored and...

Page 4: ...n in Fig 1 The fire fighting equipment consists of Tank with extinguishing agent 1 consisting of non pressure stainless storage vessel 1 filled with the extinguishing agent FK 5 1 12 dodekafluor 2 met...

Page 5: ......

Page 6: ...he energy requirements of the system during extinguishing AC inlet 13 for connecting the DC source 14 to 230V AC distribution network Control board 16 the heart of the system It concentrates and evalu...

Page 7: ...ress the micro switch to the left of the communication connector The internal relay is activated a click is heard and connects the battery to the system BATTERY G S De aerating the pump after adding f...

Page 8: ...at the same time by switching the micro switch in the left lower part of the box which is accessible from the bottom after partially ejecting the box about 5 cm from the 19 frame BATTERY R S50 Extingu...

Page 9: ...with the cap connect the external equipment on the rear face and insert the equipment back into the frame Secure The system error signal goes off FAULT SYSTEM Press TEST MUTE the pump is activated th...

Page 10: ...would escape outside the monitored space and its concentration for effectively extinguishing a fire would be insufficient The integrity of the circuit of the door contact is continuously monitored Th...

Page 11: ...ectors or other extinguishing equipment The inputs marked with the text Sensor 1 to Sensor 3 are for this The sensitivity of the external sensors circuits is also continuously monitored The connection...

Page 12: ...the network EXTINGUISHING R S50 3 seconds delay before extinguishing activated R S Extinguishing in progress or terminated Y S Extinguishing blocked door open FAULT SENSOR R S Fault sensor PUMP G S Th...

Page 13: ...operators by the extinguishing agent as well as decomposition products mainly by regular training The start of the fire extinguisher may be accompanied by a loud noise that could cause fright but not...

Page 14: ...isplayed To repeat the login close the browser and run it again it is its property and it is not possible to do otherwise NOTE Transferred login data is not encrypted ATTENTION The display may not be...

Page 15: ...state is displayed when MAJOR system error MINOR is in yellow The battery is disconnected from the system but it is present The fan is not rotating The level is low Here the state is displayed when Th...

Page 16: ...Network...

Page 17: ...IP address exchange address Gate must be typed even if it is not used Primary and secondary DNS if mail is used SNMP trap1 2 IP SNMP address of the server...

Page 18: ...ed Group extinguish group for common extinguishing If the exchanges have the same group with the exception of 0 if extinguishing is activated on any of them extinguishing on the others is activated Us...

Page 19: ...or failure sends the trap Mail change of the state or error sends e mail Error Major error is assigned to Major Error Minor error is assigned to Minor State Major the state is assigned to Mirror Stat...

Page 20: ...he line and press the Read sensor button and press the Save button Then select the temperature type the line disconnect the first sensor and connect the second sensor read serial number and save Repea...

Page 21: ...User Password SMTP server requires login To addressee of the mail From sender of the mail must be typed Subject Subject of the message Outputs Relay_ window used to change the name of the output The n...

Page 22: ...Date and time Logs Lists events from the newest to the oldest Download MIB opens the MIB file window LOG opens events window...

Page 23: ...the box From the front the skid has 3 holes with M5 threads with the same pitch as the 1U drilling in the 19 bar Fix the bar to the rear wall of the front 19 bar using the conical headed M5 bolt The r...

Page 24: ...network and operated connect the battery It must be connected for at least 12 hours to charge the backup source battery After charging the equipment must be disconnected and then it is possible to pu...

Page 25: ...are properly located and undamaged Inspection of signal lamps on the front panel Inspection after 1 month Checking that all staff who could work with equipment are properly trained and have appropriat...

Reviews:

Related manuals for LES-RACK-M1