background image

 

 

 

After inserting the  funnel start  filling or topping up the  extinguishing liquid. Fill slowly as the  inflow 
opening is small. 

 

After filling with the necessary amount of liquid remove the funnel. 

 

After filling, re-screw the filling hole cover and gently tighten 

 

Return the LES-RACK-M1 into the horizontal (working) position and place it back in the box 

 

De-aerate the pump with the “TEST”+ “MUTE ”buttons 

 

CHECKING AND COMMISSIONING 

 

Commissioning 

The procedure for commissioning equipment is given in Table No. 2 “INSTALLATION - ACTIVATION”.

 

 

Checking  

The function of the equipment is checked exclusively in the TEST regime.  
The procedure for commissioning is given in Table No.2 “TEST”. 

 

Disconnecting equipment 

The equipment is disconnected by stopping the supply from the distribution network and, at the same 
time, disconnecting the battery. 
The supply from the distribution network is stopped by disconnecting the circuit breaker (switch) or by 
disconnecting the supply cable from the AC inlet on the equipment. 
The battery is disconnected by pressing and holding the “TEST ”button and pressing the “RESET ”button 
on the front panel of the equipment. 
 

NOTIFICATION: 

   

If equipment is disconnected for more than 4 months it must be connected to the 

network and operated (connect the battery). It must be connected for at least 12 hours to charge the 
backup source (battery). After charging, the equipment must be disconnected and then it is possible to 
put it aside again.

 

 

 

SERVICING 

General requirements 

The LES-RACK-M1 equipment is designed and produced for fully automated operation. The front panel 
contains  the  signal  LED  elements  providing  information  about  the  state  and  running  processes  of  the 
equipment. The list of local signals is given in Table No. 5. 
The cover of the equipment must only be opened by a person authorized by service organization. After 
opening the cover there is a risk of an electric shock. The equipment user must state and train a person 
responsible  for  operation  of  the  equipment,  persons  authorized  to  operate  the  equipment  and 
authorized  maintenance  personnel  who  must  be  familiarized  in  detail  with  this  user  manual.  For 
instructing maintenance employees of other equipment, correct procedures must be put in place so that 
during  their  activities  they  do  not  activate  fire  extinguisher.  It  is  recommended  to  state  that 
unauthorized persons are prohibited or their entrance into premises of the equipment is controlled. 

 

MAINTENANCE 

General provisions 

The  user  must  carry  out  program  inspections,  ensure  planned  repairs  and  keep  records  about 
inspections and repairs. The user must prevent leaks and immediately repair ascertained leaks according 

Summary of Contents for LES-RACK-M1

Page 1: ...dures for assembling commissioning operating and maintenance of the LES RACK M1 fire extinguisher The equipment must only be used for the described applications with the approved extinguishing agent F...

Page 2: ...19 Temperatures 20 Mail 21 Outputs 21 Date and time 22 Logs 22 Download 22 INSTALLATION 23 General provisions 23 Safety provisions 23 Assembling the equipment 23 Filling adding extinguishing liquid 23...

Page 3: ...g to the operating conditions and the maintenance plan In necessary the maintenance and service must be documented Device operators of must announce all changes and modifications of the monitored and...

Page 4: ...n in Fig 1 The fire fighting equipment consists of Tank with extinguishing agent 1 consisting of non pressure stainless storage vessel 1 filled with the extinguishing agent FK 5 1 12 dodekafluor 2 met...

Page 5: ......

Page 6: ...he energy requirements of the system during extinguishing AC inlet 13 for connecting the DC source 14 to 230V AC distribution network Control board 16 the heart of the system It concentrates and evalu...

Page 7: ...ress the micro switch to the left of the communication connector The internal relay is activated a click is heard and connects the battery to the system BATTERY G S De aerating the pump after adding f...

Page 8: ...at the same time by switching the micro switch in the left lower part of the box which is accessible from the bottom after partially ejecting the box about 5 cm from the 19 frame BATTERY R S50 Extingu...

Page 9: ...with the cap connect the external equipment on the rear face and insert the equipment back into the frame Secure The system error signal goes off FAULT SYSTEM Press TEST MUTE the pump is activated th...

Page 10: ...would escape outside the monitored space and its concentration for effectively extinguishing a fire would be insufficient The integrity of the circuit of the door contact is continuously monitored Th...

Page 11: ...ectors or other extinguishing equipment The inputs marked with the text Sensor 1 to Sensor 3 are for this The sensitivity of the external sensors circuits is also continuously monitored The connection...

Page 12: ...the network EXTINGUISHING R S50 3 seconds delay before extinguishing activated R S Extinguishing in progress or terminated Y S Extinguishing blocked door open FAULT SENSOR R S Fault sensor PUMP G S Th...

Page 13: ...operators by the extinguishing agent as well as decomposition products mainly by regular training The start of the fire extinguisher may be accompanied by a loud noise that could cause fright but not...

Page 14: ...isplayed To repeat the login close the browser and run it again it is its property and it is not possible to do otherwise NOTE Transferred login data is not encrypted ATTENTION The display may not be...

Page 15: ...state is displayed when MAJOR system error MINOR is in yellow The battery is disconnected from the system but it is present The fan is not rotating The level is low Here the state is displayed when Th...

Page 16: ...Network...

Page 17: ...IP address exchange address Gate must be typed even if it is not used Primary and secondary DNS if mail is used SNMP trap1 2 IP SNMP address of the server...

Page 18: ...ed Group extinguish group for common extinguishing If the exchanges have the same group with the exception of 0 if extinguishing is activated on any of them extinguishing on the others is activated Us...

Page 19: ...or failure sends the trap Mail change of the state or error sends e mail Error Major error is assigned to Major Error Minor error is assigned to Minor State Major the state is assigned to Mirror Stat...

Page 20: ...he line and press the Read sensor button and press the Save button Then select the temperature type the line disconnect the first sensor and connect the second sensor read serial number and save Repea...

Page 21: ...User Password SMTP server requires login To addressee of the mail From sender of the mail must be typed Subject Subject of the message Outputs Relay_ window used to change the name of the output The n...

Page 22: ...Date and time Logs Lists events from the newest to the oldest Download MIB opens the MIB file window LOG opens events window...

Page 23: ...the box From the front the skid has 3 holes with M5 threads with the same pitch as the 1U drilling in the 19 bar Fix the bar to the rear wall of the front 19 bar using the conical headed M5 bolt The r...

Page 24: ...network and operated connect the battery It must be connected for at least 12 hours to charge the backup source battery After charging the equipment must be disconnected and then it is possible to pu...

Page 25: ...are properly located and undamaged Inspection of signal lamps on the front panel Inspection after 1 month Checking that all staff who could work with equipment are properly trained and have appropriat...

Reviews:

Related manuals for LES-RACK-M1