Appendix
—
CPS-MC341-DS1-111 Reference Manual (Hardware)
—
60
—
2.
Power Requirements
System requires a clean, steady power source for reliable performance of the high frequency CPU on
the product, the quality of the power supply is even more important.
CAUTION
If the fluctuation of power supply voltage is beyond the product specifications, connect a
constant voltage transformer.
If the noise is large, connect an isolation transformer (a noise cut transformer).
Never bundle, place nearby or in parallel the power supply cable and the input /output signal
lines.
If lightning surge protection is required, connect the surge protective device (SPD).
Place the surge protective device (SPD) and the product away from each other to ground.
Select appropriate surge protection devices for all of the route.
When you restart the power, give the product for at least one second (or longer) of the power
OFF time.
When you use with the CPS-PWD-15AW12-01 (by CONTEC), instantaneous voltage drop
allowed time is 20 milliseconds or less