Appendix
—
CPS-MC341-DS1-111 Reference Manual (Hardware)
—
59
—
Installation Environment Requirements
Item
CPS-MC341-DS1-111
Operating ambient temperature -20 - +60°C
Operating ambient humidity
10 - 90%RH (No condensation)
Non-operating ambient
temperature
-20 - +60°C
Non-operating ambient humidity 10 - 90%RH (No condensation)
Floating dust particles
Not to be excessive
Corrosive gases
None
Line-noise
resistance
Line noise
AC Line/±2kV *4
Signal Line /±1kV(IEC61000-4-4 Level 3, EN61000-4-4 Level 3)
Static
electricity
resistance
Touch /±4kV(IEC61000-4-2 Level 2, EN61000-4-2 Level 2)
Air /±8kV(IEC61000-4-2 Level 3, EN61000-4-2 Level 3)
Vibration
resistance
Sweep
resistance
10 - 57Hz *5 /semi-amplitude vibration 0.15mm, 57 - 150Hz/2.0G
40minutes each in X, Y, and Z directions (JIS C60068-2-6-compliant,
IEC60068-2-6-compliant)
Shock resistance
15G half-sine shock for 11ms in X, Y, and Z directions
(JIS C 60068-2-27 –compliant, IEC 60068-2-27 -compliant)
Grounding
Class D grounding (previous class 3 grounding), SG-FG/ non-conduction
Standard
VCCI Class A, FCC Class A,
CE Marking (EMC Directive Class A, RoHS Directive), UL
*4 When you use the CPS-PWD15AW12-01 (optional product).
*5 When you use an optional power product: 10-55Hz (See the manual of optional power product