Service Manual CS3000
Appendix B: Fault codes
B-5
Fault codes
Document no.:
S-4-007.875/E
Prepared:
1995-03-17 Fia
Revision:
R4 2004-03-15 BM
©
2002, Consilium Marine AB
62
DEFINITION DATA ERROR
A fault has been discovered in the memory where the system definition is
stored.
Cause
Remedy
Faulty LPK-2.
Replace LPK.
Error in definition data.
Download new definition data.
Wrong software version.
Upgrade software version in
LPK.
64
LOOP POLL FAULT
Cause
Remedy
The communication between the
loop units is interrupted either
because a hanging for more than
20 seconds on a certain unit or
because a polling cycle takes too
long time.
The fault can appear when a
command is given to set outputs
for a particular loop unit.
Localise the faulty unit and
replace it. Localisation can be
done e.g. by interval-halving
technique.
81 MAINS
FAULT
Mains power failure.
Cause
Remedy
Mains power missing.
Attend to the problem.
Fuses are blown in the system.
Exchange the fuses.
Cable break.
Mend the cable. See
Cable
break
at the end of this chapter.
FAULT (81) 1 POWER MAINS FAULT
Mains power failure in the power unit.
83 FUSE
FAULT
A fuse in the central unit is blown. Different messages are displayed depending
on the location of the fuse.
Cause
Remedy
A fuse is blown. In the display is
shown which fuse is blown.
Exchange the fuse. See
Fuses
at
the end of this chapter.