Service manual CS3000 

Chapter 3: Interface board  KPK-2 3-38 

The circuit boards of the central unit 

 

 

Document no.: 

S-4-007.875/E 

Prepared: 

1995-03-17  Fia 

Revision: 

R4  2004-03-15  BM 

 
© 2002, Consilium Marine AB  

 

Restarting the board 

Remove the fuse from the board to disconnect the power. When the fuse is put 
back on, the board is restarted. 

Replacing the board 

To replace the KPK-2 follow these steps: 

1.

 

Shut down the central by removing the fuses F3-F6 on the KE-2 rectifier. 

 

WARNING!

  

The power must be disconnected before the board is removed. 

2.

 

Remove the board and replace it with the new board. 

3.

 

Start up the central by inserting F3+F4 and F5+F6 in that order. 

 

 

Summary of Contents for Salwico CS3000

Page 1: ...Fire Alarm System Salwico CS3000 Service manual Ver 6 Consilium...

Page 2: ...umes no legal responsibility for any error or damage resulting from the usage of this document Edition 5 09 1 E August 2009 Document no S 4 007 875 Part no 070073 2004 2009 Consilium Fire Gas AB Consi...

Page 3: ...ard of the control unit Input Output board IKK 4 2 1 Chapter 3 The circuit boards of the central unit Loop processor board SPK 2 3 01 Alarm processor board LPK 2 3 09 Relay board ARK 2 3 13 Input boar...

Page 4: ...Board of the Control Unit describes the functions of the Control unit s circuit board For information regarding the Central unit s various circuit boards refer to The Circuit Boards of the Central Un...

Page 5: ...a unique address in the interval 217 232 The control unit number must correspond with the number defined in the Definition program The control unit address must be set after the system definition is...

Page 6: ...control unit processor board to the system loop The IKK 4 board also includes circuits for transient suppression of all external signals The IKK 4 board is controlled by the control unit board via th...

Page 7: ...ual CS3000 Chapter 2 Input Output board IKK 4 2 2 The circuit board of the control unit Document no S 4 007 875 E Prepared 1995 03 17 Fia Revision R4 2004 03 15 BM 1995 Consilium Marine AB Function Bl...

Page 8: ...all external inputs 7 Outputs Controls the four transistor outputs 8 Buzzer An external buzzer may be connected via a transient protected output The buzzer will be parallel connected to the fire alar...

Page 9: ...repared 1995 03 17 Fia Revision R4 2004 03 15 BM 1995 Consilium Marine AB Technical data Board size 145 x 107 mm Ambient temperature 10 C 70 C Ambient humidity 96 Rh Input power Uin 24 VDC 20 25 Curre...

Page 10: ...o the LPK 2 and proper hardware signals are then activated Handling Indications Model 1 There are nine LEDs on the front panel of the board No 1 green when lit proper voltage supply No 2 yellow when l...

Page 11: ...g the address The address of loop 1 of the board is set with a DIP switch SW1 with 8 switches Bit 1 is set with SW1 1 and bit 8 with SW1 8 The address of loop 2 is automatically set by the system to t...

Page 12: ...2 3 3 The circuit boards of the central unit Document no S 4 007 875 E Prepared 1995 03 17 Fia Revision R4 2004 03 15 BM 2002 Consilium Marine AB Function Block diagram Model 1 Model 2 NB In the diagr...

Page 13: ...he detectors and status information The watchdog supervises the processor and checks for hang ups in the programme execution 6 Address switch The 8 bit address of the SPK 2 i e the loop number is set...

Page 14: ...three functions Power supply loop and processor with memory The power supply provides the board with loop power and power for the logic and the processors The loop part contains electronics for two lo...

Page 15: ...syncronous channel of the processor is used for communication with the LPK These signals are adapted to the RS485 levels and are galvanically separated from the back plane Service plug RS232 channel u...

Page 16: ...rs Model 3 JP1 Must always be strapped in normal operation The strap enables the watchdog JP2 Never strapped during normal operation JP1 and JP2 are only strapped differently during production when th...

Page 17: ...nt temperature 10 C to 70 C Ambient humidity 96 Rh Input power Uin 24 VDC 20 25 Current consumption Iin nom 90 mA Iin max 160 mA Output voltage Uut 30 VDC 5 Output current Iut nom 45 mA Iut max 125 mA...

Page 18: ...board No 1 green when lit proper voltage supply No 2 red when lit fire alarm has been given on the fire brigade relay output No 3 yellow when lit fault has been detected No 4 yellow when lit local sy...

Page 19: ...tarting the board Remove the fuse from the board to disconnect the power When the fuse is put back on the board is restarted Replacing the board To replace the LPK 2 follow these steps 1 Disconnect th...

Page 20: ...tion Block diagram OUTPUTS RELAY SYSTEM COM LOOP CSM LPK CSM LPK COM LOOP SYSTEM SYSTEM SYSTEM BUFFERS DATA ADDRESS COM CONTR INT COM BASIC 1 12 10 9 8 8 6 7 2 5 4 3 BLOCK 24 VDC LOOP 2 LOOP 1 ADDRESS...

Page 21: ...ress of the LPK is set 5 Real time clock The real time clock is keeping track of the time in the system The clock has built in registers for seconds minutes hours days week day month and year includin...

Page 22: ...1995 03 17 Fia Revision R4 2004 03 15 BM 2002 Consilium Marine AB Technical data Board size Single Europe board 100 x 160 mm Front panel Anodised aluminium width 6 TE 30 1 mm Ambient temperature 10 C...

Page 23: ...d may be used for monitoring external signals and for supervision of power supply to external units Handling Indications The LED on the front panel of the board is lit every time the board is polled F...

Page 24: ...tch SW1 SW1 1 SW1 2 SW1 3 B1 B2 B3 ON Steady signal to corresponding alarm bell output OFF Pulsed signal to corresponding alarm bell output SW1 4 SW1 5 SW1 6 R1 R2 R3 ON Steady signal to the outputs o...

Page 25: ...iagram INPUT SIG NA LS C O NT RO L BA SIC A LA RM LE D PA NEL SW IT CH DIP PT C B A RR IE R FA ULT BA C K PLA NE PT C uP BUS O PTO ISO L EXT FUSE FA ULT SW IT CH PA NEL 15 14 13 12 17 16 11 10 9 8 7 E...

Page 26: ...utput Two fused and fault supervised outputs for power supply to external devices 7 Relay output Three programmable fused and potential free relay outputs 8 Fire fault output One current sinking progr...

Page 27: ...DC Input current Iin 8 mA at Uin 24 V OneDG 2880 ohm relay coil for 24 VDC activated when low Input voltage Uin max 35 VDC Activation of relay Uactmax 7 2 VDC One external intermittence 10 kohm pull u...

Page 28: ...No 1 green when lit proper voltage supply No 2 green when lit the board is properly polled Fuse The battery voltage is fused If the fuse is blown a signal is activated in the back plane The fuse is ac...

Page 29: ...ion Block diagram INDICATOR LED 4 OPTO ISOLATED INPUTS 4 OPTO ISOLATED INPUTS 4 OPTO ISOLATED INPUTS 4 OPTO ISOLATED INPUTS 4 OPTO ISOLATED INPUTS S INPUT ISOLATED 4 OPTO 9 9 9 9 9 INPUT CONNECTOR 7 8...

Page 30: ...t panel are two green LEDs for indicating 5V power and normal polling 4 Control logic The control logic is used for decoding the address bus and for generating signals to read write the status registe...

Page 31: ...le Europe board 100 x 160 mm Front panel Anodised aluminium width 6 TE 30 1 mm Ambient temperature 10 C 70 C Ambient humidity 96 Rh Input power Uin 24 VDC 20 25 Current consumption Iin nom 15 mA Iin m...

Page 32: ...een when lit the board is properly polled Fuse The battery voltage is fused If the fuse is blown a signal is activated in the back plane The fuse is accessible on the front panel of the board and can...

Page 33: ...REGISTER OUTPUT CONNECTOR 9 9 4 OPTO ISOLATED OUTPUTS OUTPUTS ISOLATED 4 OPTO 9 9 4 OPTO ISOLATED OUTPUTS OUTPUTS ISOLATED 4 OPTO 4 OPTO ISOLATED OUTPUTS OUTPUTS ISOLATED 4 OPTO LATCH OUTPUT STATUS O...

Page 34: ...r read buffers and output buffers 5 6 Buffers The address bus the data bus and the control signals are buffered before entering the board 7 Output status The value written to the outputs can be read t...

Page 35: ...e sink outputs Each of the 24 outputs can be individually chosen for source or sink outputs by means of the jumpers on the PCB see picture above The outputs on the PCB are grouped with four outputs in...

Page 36: ...oke detectors on these sections Handling Indications There are nine LEDs on the front panel of the board No 1 green when lit proper voltage supply No 2 red when lit fire alarm in section 1 No 3 yellow...

Page 37: ...2002 Consilium Marine AB Restarting the board Remove the fuse from the board to disconnect the power When the fuse is put back on the board is restarted Replacing the board To replace a board follow t...

Page 38: ...IRE FAULT ALARM SECTION 1 SECTION 4 SECTION 3 SECTION 2 BARRIER OFF LOGIC TEST AND INHIBIT FIRE FAULT AND STATUS DETECTION BARRIER OFF LOGIC TEST AND INHIBIT FIRE FAULT AND STATUS DETECTION BARRIER OF...

Page 39: ...which communicate with the central unit The IDA circuits also controls the sections 5 Control logic Alarms and faults are latched in the GSK 2 board and at reset from the control unit the section is t...

Page 40: ...ngle Europe board 100x160 mm Front panel Anodised aluminium width 6 TE 30 1 mm Ambient temperature 10 C 70 C Ambient humidity 96 Hr Input power Uin 24 VDC 20 25 Current consumption Iin nom 25 mA Iin m...

Page 41: ...tion programme Handling Indications There are ten green LEDs on the front panel of the board No 1 when lit proper voltage supply No 2 when lit the board is properly polled No 3 when lit RS232 channel...

Page 42: ...ove the fuse from the board to disconnect the power When the fuse is put back on the board is restarted Replacing the board To replace the RS232K 2 follow these steps 1 Shut down the central by removi...

Page 43: ...95 03 17 Fia Revision R4 2004 03 15 BM 2002 Consilium Marine AB Function Block diagram UART UART 13 8 IRQ 3 11 14 14 15 12 10 485 485 232 232 UART UART STATUS REGISTER INDICATOR LED 9 7 STATUS REGISTE...

Page 44: ...also indicated by green LEDs 4 Control logic The address bus is decoded and selection signals for the two double serial channels are generated 5 6 Buffers The address bus the data bus and the control...

Page 45: ...E Prepared 1995 03 17 Fia Revision R4 2004 03 15 BM 2002 Consilium Marine AB Technical data Board size Single Europe board 100x160 mm Front panel Anodised aluminium width 6 TE 30 1 mm Ambient tempera...

Page 46: ...he functions of the board are set by the definition programme Handling Indications There are ten green LEDs on the front panel of the board No 1 when lit proper voltage supply No 2 when lit the board...

Page 47: ...ove the fuse from the board to disconnect the power When the fuse is put back on the board is restarted Replacing the board To replace the KPK 2 follow these steps 1 Shut down the central by removing...

Page 48: ...ual CS3000 Chapter 3 Interface board KPK 2 3 39 The circuit boards of the central unit Document no S 4 007 875 E Prepared 1995 03 17 Fia Revision R4 2004 03 15 BM 2002 Consilium Marine AB Function Blo...

Page 49: ...cuits Two of the DUARTs are for the RS232 channels and two is for the RS485 channels All parameters such as baud rate parity etc are programmable Contains processor two serial ports which is connected...

Page 50: ...Prepared 1995 03 17 Fia Revision R4 2004 03 15 BM 2002 Consilium Marine AB Technical data Board size Single Europe board 100x160 mm Front panel Anodised aluminium width 6 TE 30 1 mm Ambient temperatur...

Page 51: ...f there are more than one rack inter connected slot 2 in the other racks may be used for other purposes If the interface board GSK 2 is used it may be placed in any available slot with the above excep...

Page 52: ...nit Document no S 4 007 875 E Prepared 1995 03 17 Fia Revision R4 2004 03 15 BM 2002 Consilium Marine AB Technical data Type Standard 19 Height 4 U 177 mm Depth 215 mm Number of slots 14 each 6 TE wid...

Page 53: ...on and controlled by the central unit which controls voltages currents and certain faults Important status data are indicated by LEDs The KE 2 battery has a programmable charging characteristic consis...

Page 54: ...nsilium Marine AB Fuses There are six fuses on the front panel Fuse no Function Rating F1 Auxilary output 4 AT 6 3 x 32 mm F2 Auxilary output 4 AT 6 3 x 32 mm F3 Battery fuse 16 AT 6 3 x 32 mm F4 Batt...

Page 55: ...C Urip 0 2 VDC Output current is of higher priority than battery charging current If the output current exceeds 8 A the battery charging current will decrease The battery charging current is equal to...

Page 56: ...of the following boards the INK 2 RS232K 2 KPK 2 and UTK 2 are set with a DIP switch The setting of the DIP switches and the corresponding hexadecimal addresses are listed below The address set on th...

Page 57: ...ument no S 4 007 875 E Prepared 1995 03 17 Fia Revision R4 2004 03 15 BM 1995 Consilium Marine AB UTK 2 board 3 Address Hex B8 UTK 2 board 4 Address Hex BC UTK 2 board 5 Address Hex C4 UTK 2 board 6 A...

Page 58: ...rked with an asterisk in the summary below 1 CONTROL UNIT MISSING The central unit is missing a control unit after cold start Cause Remedy System loop break Mend the cable Control unit incorrectly add...

Page 59: ...efine the system 6 ADDITIONAL SECTION S An additional section has been found by the central unit after cold start Cause Remedy Wrong definition of number of sections Check the specification and redefi...

Page 60: ...medy Wrong type of section unit Exchange to the correct section unit Two section units have the same address Check the units Hardware fault Exchange the unit A fuse is blown A secondary fault appears...

Page 61: ...ch PCB that is booting is shown in the display Reset the fault 42 BOOT DISABLED A section unit was disconnected by the system during the initialisation Cause Remedy Section unit faulty Exchange the se...

Page 62: ...unit or because a polling cycle takes too long time The fault can appear when a command is given to set outputs for a particular loop unit Localise the faulty unit and replace it Localisation can be...

Page 63: ...etector Clean the detector head according to the recommendations Ionization smoke detector Exchange the detector 93 FUSE CABLE FAULT A fuse in the central unit is blown or there is a cable break Diffe...

Page 64: ...break is in system loop no 2 The fault can only be reset when the central is allowed to communicate on the loop This message can only emanate from the central unit itself FAULT 121 SEC 1 CABLE BREAK C...

Page 65: ...e secondary side Attend to the problem 141 EARTH FAULT Cause Remedy Earth fault between positive terminal and earth See Earth fault at the end of this chapter FAULT 141 POWER EARTH FAULT Earth fault t...

Page 66: ...E Prepared 1995 03 17 Fia Revision R4 2004 03 15 BM 2002 Consilium Marine AB 146 HIGH VOLTAGE Abn condition Cause Remedy Too high system voltage from power unit Test the rectifier and measure the vol...

Page 67: ...nits Earth fault Check the earth fault circuit change it if it is faulty If the circuit is working properly check the loops one by one Disconnect the loops one by one see Disconnection Electric isolat...

Page 68: ...32K 2 Main fuse 250 mAT 5x20 mm 83 SPK 2 Main fuse 1AT 5x20 mm 83 UTK 2 Main fuse 250 mAT 5x20 mm 93 ARK 2 F5 Alarm bell output 1 2A 5x20 mm 93 ARK 2 F6 Alarm bell output 1 2A 5x20 mm 93 ARK 2 F7 Alar...

Page 69: ...N SYSTEM There is a fire alarm in the system and the LPK board is not answering 1 MISSING CONTROL UNIT The central unit is missing a control unit after cold start Cause Remedy System loop break Mend t...

Page 70: ...e central unit found an additional loop after cold start Cause Remedy Wrong definition of number of loops Check the specification and redefine the system 7 MISSING LOOP UNIT Fewer loop units have been...

Page 71: ...mporary This fault code is sent when interference in the communication is detected Cause Remedy Bad communication with one or several loop units Exchange the loop unit if the condition remains or retu...

Page 72: ...se Remedy Noisy environment Test the loop Measure the cable resistance See Cable break at the end of this chapter 27 LOOP COMM STOPPED No communication in a loop Cause Remedy A loop unit is faulty Che...

Page 73: ...in the display Reset the fault 42 BOOT DISABLED A loop unit was disconnected by the system during the initialisation Cause Remedy Loop unit faulty Exchange the section unit Address unit on a sub loop...

Page 74: ...ersion Upgrade software version in LPK 64 LOOP POLL FAULT Cause Remedy The communication between the loop units is interrupted either because a hanging for more than 20 seconds on a certain unit or be...

Page 75: ...he boards ARK 2 INK 2 UTK 2 RS232K 2 or KPK 2 is faulty Exchange the board 90 POLLUTED DETECTOR Abnormal condition Cause Remedy Detector head is polluted Optical smoke detector Clean the detector head...

Page 76: ...THERMISTOR FAULT Cause Remedy Thermistor in a heat detector faulty Exchange the detector 103 ION SMOKE CHAMBER FAULT Cause Remedy Ion chamber in an ionization detector faulty Exchange the detector 12...

Page 77: ...cuit isolators will give messages of the type NO ANSWER 22 One message is always CABLE BREAK 121 since the loop is broken The short circuit faults must always be reset before other faults Cause Remedy...

Page 78: ...easure the voltage If necessary exchange the rectifier 146 HIGH VOLTAGE Abnormal condition Cause Remedy Too high system voltage from power unit Test the rectifier and measure the voltage If necessary...

Page 79: ...n wrong position Check for obstruction 170 SENSOR FAULT The detector is giving a too low analogue value Cause Remedy The detector has a faulty sensor element Replace the detector NB This fault could b...

Page 80: ...the cable break A tripped short circuit isolator can cause this fault Check the short circuit isolators 177 CABLE BREAK NEGATIVE SIDE Cause Remedy Check for a cable break on negative lead Mend the cab...

Page 81: ...Remedy There is an overload in the cable Check if too many units are connected to the cable Compare with cable data 184 POWER FAULT Cause Remedy The power supply is lost Check power generation 185 LO...

Page 82: ...is situated after or between these units Earth fault Check the earth fault circuit change it if it is faulty If the circuit is working properly check the loops one by one Disconnect the loops one by...

Page 83: ...rm bell output 1 2A 5x20 mm 93 ARK 2 F6 Alarm bell output 1 2A 5x20 mm 93 ARK 2 F7 Alarm bell output 2 2A 5x20 mm 93 ARK 2 F8 Alarm bell output 2 2A 5x20 mm 93 ARK 2 F9 Alarm bell output 3 2A 5x20 mm...