Service manual CS3000
Chapter 3: Power unit KE-2 3-45
The circuit boards of the central unit
Document no.:
S-4-007.875/E
Prepared:
1995-03-17 Fia
Revision:
R2 2002-08-14 BM
© 1995, Consilium Marine AB
Fuses
There are six fuses on the front panel.
Fuse
no.
Function Rating
F1
Auxilary output
4 AT 6,3 x 32 mm
F2
Auxilary output
4 AT 6,3 x 32 mm
F3
Battery fuse +
16 AT 6,3 x 32 mm
F4
Battery fuse -
16 AT 6,3 x 32 mm
F5
Net fuse
4 AT 6,3 x 32 mm
F6
Net fuse
4 AT 6,3 x 32 mm
WARNING!
When starting up the central first insert fuses F3+F4, and then F5+F6
in that order.