Conlog BEC21 Installation Manual Download Page 6

 

Procedure 

 

 

1.

 

Before setting up the appliance, check it for any externally visible damage. 

Under no circumstances should you use a damaged appliance. A damaged 

appliance could be dangerous 

 

2.

 

Remove Terminal Tamper cover (Figure2) 

 

3.

 

Mark wall and drill mounting holes (Figure 4) 

 

4.

 

Mount meter on the wall and secure 

 

5.

 

Ensure upstream breaker is in the off position  

 

6.

 

Connect the incoming live supply to L LINE (Figure 3

).

 

 

7.

 

Connect the incoming neutral supply to N LINE (Figure 3

)

 

 

8.

 

Connect the outgoing live supply to L LOAD (Figure 3

)

 

 

9.

 

Connect the outgoing neutral supply to N LOAD (Figure 3

)

 

 

10.

 

Ensure that all terminal screws are securely tightened, all cables are securely 
held in place and that no bare wiring is exposed 

 

11.

 

Secure the terminals & enclosure by threading steel wire through the security 
holes and crimping (If required)   

 

12.

 

The meter must be installed on a solid flat surface with a 4mm screw 

 

13.

 

For indoor use only, can be installed in an enclosure or stand alone 

 
 
 
 
 
 
 
 
 
 

Summary of Contents for BEC21

Page 1: ......

Page 2: ...afety Information 3 Safety and Maintenance Instructions 4 Installation 5 Diagrams and Illustrations 5 Procedure 6 Testing the Meter Installation and Sealing the Device 7 Cabling Specifications 7 Displ...

Page 3: ...ical Contractor No responsibility is assumed by Conlog Pty Ltd for any consequences arising out of the use of this material An installation electrician or electrical contractor is one who has skills a...

Page 4: ...ls are used for the installation Ensure that the meter is installed in a dry location and is not exposed to water or moisture No sharp objects to be used to press the keypad If keypad is damaged pleas...

Page 5: ...iagrams and Illustrations Figure 2 Terminal Cover Remove terminal screw before mounting the meter and insert the terminal screw on to the terminal cover Figure 1 Product Layout Figure 3 Terminals Figu...

Page 6: ...ve supply to L LINE Figure 3 7 Connect the incoming neutral supply to N LINE Figure 3 8 Connect the outgoing live supply to L LOAD Figure 3 9 Connect the outgoing neutral supply to N LOAD Figure 3 10...

Page 7: ...to the serial number printed on the meter label and card to confirm that the numbers match 6 Turn on an appliance or light in the consumer s premises to ensure that the consumer has electricity In so...

Page 8: ...alised contact Conlog E02 Meter not calibrated contact Conlog E03 Internal error contact Conlog E04 No supply voltage present E05 Reserved for future use E06 Reserved for future use E07 Communication...

Page 9: ...it Status LED Rate LED 1000 imp kWh Terminals Layout Live Neutral Neutral Load Type Cage clamp Maximum size 16mm Interrogation Type Near Field Communication NFC Compliance Standards IEC 62052 11 IEC 6...

Reviews: