SERIES CHARGING CONTACTS MANUAL
10
SECTION 2 - INSTALLATION
Mounting For Base
1.
Mount the base plate assembly using the provided clearance
holes for socket head cap screws. See
Figure 2-4
.
NOTE
•
Provisions for making electrical connections are provided
on the base plate assembly.
•
Care must be taken when connecting the cable lugs
to ensure the correct phases are clustered together.
Reference the provided drawing for cable lug size. Any
fault condition resulting from improper installation is the
responsibility of the user.
2.
The base plate must be mounted in a suitable enclosure for the
service environment.
3.
For 60Vdc (25Vac) service, per UL583 pollution degree 3 a
minimum clearance of 3.2 mm and creepage of 6.4 mm must
be maintained between each phase, and phase to ground.
NOTE
•
This value may vary based on voltage, enclosure type,
and regional standards.
Bottom of Base Plate Showing Clearance Holes and Minimum
Support Area.
ØD Clearance Hole
Ø2D Minimum Support Area
Figure: 2-4
Bottom of base showing Clearance Holes, and
Minimum Support Area