32
Installation
5.7.2.2 Installation of the humidity sensor and the maximum humidistat
1. Drill the mounting holes (ø2 mm) and the hole (ø16 mm) for the insertion of the sensor into the
ventilation duct (see
and
2. Secure the sensor holder to the ventilation duct with the sheet metal screws supplied.
3. Insert the humidity sensor and the maximum humidistat with the rubber ring and the washer into the
sensor holder and fasten with the lock nut.
Lock nut
Washer
Rubber washer
Sensor bracket
Drill ø16 mm
Drill ø2 mm
60 mm
60 mm
Fig. 16: Installation of the humidity sensor and the maximum humidistat