32
|
Links XPS Nortec GSTC/ SETC B+
Table 6: Variable Definitions - CONTINUED
Variable Name
R=Read
W=Write
Description
LonWorks SNVT
nvoSet1_
x
R
Analog Value
Reads setpoint for relative humidity
in space. (0%-100%).
SNVT_lev_percent
nvoRHDem2_
x
R
Analog Value
Reads duct %RH or secondary
space %RH, or secondary
%demand to humidifier. (0%-100%)
Choice determined by
nviInputType
_
x.
SNVT_lev_percent
nvoDisable_
x
R
Binary Value
Reads remote disable status.
0=humidifier enabled, 1=humidifier
disabled by network
SNVT_switch
nvoService_
x
R
Binary Value
Reads service requirement status.
0=no service required, 1=service
required
SNVT_switch
nvoStatus_
x
R
Binary Value
Reads humidifier status. 0=standby,
1=humidifying
SNVT_switch
nvoConnection_x
R
Binary Value
Indicates that the Links module is
communicating with the humidifier
SNVT_switch
nvoKeepWarm_x
R
Binary Value
Indicates that the KeepWarm feature
has been enabled
SNVT_switch
nvo3DayDrain_x
R
Binary Value
Indicates that the 3 day drain feature
has been enabled
SNVT_switch
nviDisable_
x
W
Binary Value
Writes remote disable status.
0=humidifier enabled, 1=humidifier
disabled from network
SNVT_switch
nviInputType_
x
W
Binary Value
Writes the input type status.
0=unit accepts a %demand signal
1=unit is configured for on/off control
SNVT_switch
nviNetSensor _
x
W
Binary Value
Writes configuration status for
network-enabled sensing or control.
0=%RH or %demand input is not
from the network
1=%RH or %demand input is from
the network
SNVT_switch