Operator Interface
2582954_D_EN_1811_Nortec-EL_OM
Nortec EL
Basic Tab, continued...
–
Control Mode CH 1/3:
allows you to select the general
control mode for the incoming control signal.
Options:
Demand
– control signal is from an
external controller.
RH P
– control signal uses the
internal P (proportional) controller
to interpret sensed humidity into
demand.
RH PI
– control signal uses the inter
-
nal PI (proportional-integral) control
-
ler to interpret sensed humidity into
demand.
On/Off
– control signal is from an
external On/Off humidistat.
–
Control Mode CH 2/4:
allows you to select the general
control mode for the incoming high limit signal.
Note:
This
setting appears only if
Options:
Demand
– control signal is from an
external controller.
RH P
– control signal uses the
internal P (proportional) controller
to interpret sensed humidity into
demand.
RH PI
– control signal uses the inter
-
nal PI (proportional-integral) control
-
ler to interpret sensed humidity into
demand.
On/Off
– control signal is from an
external On/Off humidistat.
Factory setting:
Demand
Note:
Channel 3 and 4 are used to control cylinder B when
is set to "Independent"; otherwise they are
ignored.
Summary of Contents for Nortec EL-Series
Page 74: ...74 Maintenance 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Page 84: ...84 Fault Isolation 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Page 88: ...88 Wiring Diagrams 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Page 93: ...Notes...
Page 94: ......