20
Operator Interface
2582954_D_EN_1811_Nortec-EL_OM
Nortec EL
Timer Cylinder A (Timer Cylinder B) Tab
Note:
The Timer Cylinder B tab appears only on units with
dual steam cylinders that are set to work in independent
mode. It is identical to the Timer Cylinder A tab.
–
On/Off Timers:
shows the current status of the On/Off tim
-
ers function. Refer to
for more details.
Note:
A
warning message is displayed whenever the humidifier is
turned off by the On/Off timer.
–
Capacity Timers:
shows the current status of the capac
-
ity limitation timer function. Refer to
for more
details.
–
Setpoint Timers
: shows the current status of the setpoint
timers function. Refer to
for more details.
Note:
This field only appears if
or "RH PI".
Service Cylinder A (Service Cylinder B) Tab
Note:
The Service Cylinder B tab appears only on units with
dual steam cylinders, and is identical to the Service Cylinder A
tab.
–
Cylinder A Installed:
shows the date of installation of the
steam cylinder.
–
Cylinder A Hours:
shows the number of operating hours
on the steam cylinder since its installation.
–
Sensor Counter:
shows the number the number of high
water level sensor activations. A high sensor counter value
may indicate the cylinder is nearing end of life or that a
newly installed cylinder is concentrating cylinder water to
optimal level.
Operating Cylinder A Tab
–
Output:
shows the actual output level of steam cylinder A.
–
Current Sensor:
shows the actual current draw (in am
-
peres) by steam cylinder A.
–
Control Mode CH 1/3:
shows the general control mode
setting for the control signals to the humidifier. Select
the field to choose a different control mode – "Demand",
"RH P", "RH PI" or "On/Off". Refer to
details.
–
Control Mode CH 2/4:
shows the general control mode
setting for the high limit input signal to the humidifier.
Select the field to choose a different control mode –
"Demand", "RH P", "RH PI" or "On/Off". Refer to
for more details.
Note:
This field only appears if
Summary of Contents for Nortec EL-Series
Page 74: ...74 Maintenance 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Page 84: ...84 Fault Isolation 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Page 88: ...88 Wiring Diagrams 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Page 93: ...Notes...
Page 94: ......