25
2596151-C_EN_2010_Condair GS EGMS_IOM
Monitoring devices' electrical connection
5
Monitoring devices' electrical connection
5.1
Electrical diagram
F2
Fuse (6 A, fast) 24 VAC power supply
H1 Remote operating and error notification
J1
Jumper (if no monitoring devices are connected)
JP2 Jumper voltage output 24 VDC or 10 VDC (
Jumper must
be set to 24 VDC
)
JP3 Jumper (to set output A3 to 5 Vdc, max. 500 mA)
JP4 Jumper (to set output A3 to 24 Vdc, max. 150 mA)
K1
External safety chain
Q
External service switch or connection plug
RJ45 Modbus communication interface (for detailed information
see separate documentation)
S1
Tank emptying input (24 VAC)
1 2 3 4 5 6 7 8
J1
A2
CH2
A1
CH1
K1
B1
B2
B3
0…10 mADC
2…20 mADC
0…20 mADC
4…20 mADC
0…10 VDC
2…10 VDC
0…5 VDC
1…5 VDC
A3
S1
JP3: 5 Vdc, max. 500 mA
JP4: 24 Vdc, max.150 mA
24 VAC
SL
CH1
CH2
24 VDC / 10 VDC
FTBD
Condair GS
GND
GND
B5
B4
L-
24 VDC
N- 14 12 11
2 (N
C)
3 (NO
)
1 (C
OM
)
9
JP
2
10V
24V
JP2
1
2
3
Incoming air monitor
Exhaust air monitor
Fig. 15: Electrical diagram
A1
Control or sensor signal CH1
(Signals can be configured using the control software)
A2
Limiter signal CH2
(Signals can be configured using the control software)
A3
24 Vdc (JP4) or 5 Vdc (JP3) output
B1
Incoming air maximum hygrostat (building side)
B2
Incoming air flow monitor (building side)
B3
Incoming air fan lock (building side)
B4 Exhaust gas management differential pressure switch
B5 Exhaust air flow monitor
F1
External fuse (10 A, slow, building side)
220...240 VAC power supply