16
Installation
2596151-C_EN_2010_Condair GS EGMS_IOM
4.3
Installation instructions
4.3.1 Positioning and fitting the exhaust gas distribution pipe
Positioning the exhaust gas distribution pipe
The exhaust gas distribution pipe must be installed at least 1 m upstream of the exhaust air fan in the
middle of the duct wall.
Fitting the exhaust gas distribution pipe
1. Mark the hole for the pipe at the location provided on the duct wall and drill the hole.
Diameter
of hole
Condair GS 23/45
110 mm
1)
Condair GS 65
110 mm
1)
Condair GS 90/130
110 mm
1)
Condair GS 195/260
160 mm
1)
1)
absolutely necessary
Fig. 4: Drilling the feedthrough hole
2. Insert the exhaust gas distribution pipe (outlet holes must point towards the exhaust air fan), align the
fixing flange horizontally with a spirit level. Then fix the flange to the duct wall with the 4 self-tapping
screws.
Note: The end of exhaust gas distribution pipes >800 mm long must be fixed to the duct wall or the
duct ceiling (see detail in
).
=
=
min. 1 m
min. 1 m
Fig. 5: Fixing the exhaust gas distribution pipe