28
Electrical connection of the nebulizers
7.3
Connection DRAABE TurboFogNeo 8
The scope of delivery of the quick installation kit (SMB) comprises a pre-packed 3 m supply cable, incl.
plug (socket side) [3], and a junction box [2]. Only the supplied supply cable [3] may be used to connect
the nebulizer.
You must ensure that the protective earth (color: green/yellow) is connected. All cable ends must be
fitted with suitable ferrules.
The TurboFogNeo 8 nebulizer does not require a 24V DC voltage, unlike the other nebulizer types. The
assignment of the corresponding terminals is left free during connection.
Connect the connectors as follows:
Line [1.3]
JZ-600 5x0.5mm²
1)
Line [1.3]
YSLY-JB 5x0.5mm²
1)
Pin assignment
[4] plug/socket
Description / function
1
Brown (BN)
1
Phase L1 (120 or 230 VAC)
2
Black (BK)
-
0 VDC / GND
3
Blue (BU)
2
Neutral conductor N (120 or 230
VAC)
4
Grey (GY)
-
24 VDC
Green/yellow (5)
Green/yellow (GN-YE)
PE (4)
Protective earth
1)
Depending on the selected cable during installation, different cable types may have been selected.
1
2
3
4
1
PE
24 VDC
N
0 VDC
L1
GN-YE
4 / GY
3 / BU
2 / BK
1 / BN
1, L1
2, N
GN/YE, PE
2 3 4 5
JZ-600 /
YSLY-JB
JZ-600 /
YSLY-JB
JZ-600
2
Wago 221-615
5x
4
Fig. 15: Connection DRAABE TurboFogNeo 8
1 supply line (5x0.5 mm²) from the HumPower control unit
2 junction box (maximum 2 nebulisers per junction box)
3 supply line (3x0.5 mm²) with plug connector (socket side)
4 nebuliser connection with socket/pin contact