Rev. B 06-2019
22
A
E
C
D
B
A
E
C
D
B
Mod.
A
B
C
D
E
270
500
500
700
500
200
350
500
500
700
500
200
450
500
500
700
500
200
550
500
500
700
500
200
750
500
500
700
500
200
950
500
500
700
500
200
Mod.
A
B
C
D
E
270
500
500
2500
500
200
350
500
500
2500
500
200
450
500
500
2500
500
200
550
500
500
3000
500
200
750
500
500
3000
500
200
950
500
500
3000
500
200
H1
H2
MTEC.6710.GB-B-1 Operation and maintenance manual HMA/Z series English
HMA/Z
,QGXVWULDOGHKXPLGL¿HUVZLWKWHPSHUDWXUHFRQWURO
4.8 Location and minimum technical clearances
The unit has to be installed such that maintenance and repair is possible. The warranty does not cover costs for the
provision of lifting apparatus, platforms or other lifting systems required to perform repairs during warranty period.
The installation site should be chosen in accordance with EN 378-1 and 378-3 standards. When choosing the
installation site, all risks caused by accidental refrigerant leakage should be taken into consideration.
&RQGHQVDWHGUDLQLQJFRQQHFWLRQV
The connection of the condensate discharge has to be made with a rigid pipe. On the condensate discharge pipe it must be installed a
syphon with a minimum height equal to the suction pressure of the fan.
7KHFRQGHQVDWHGUDLQOLQHVKRXOGKDYHDZDWHUWUDSZKLFKPD\KDYHPLQLPXPÀ\LQJKHLJKWHTXDOWRWKHVXFWLRQRI
the fan, in any case never less than 35 mm.
Discharge pipe
H1
PP
H2
ǻ3PP
Ǽ3
SUHVVXUHGLIIHUHQFH
inside the unit in mm water
column
10 Pa
§
1 mm water column
7KHVLSKRQPXVWEH¿OOHGZLWKZDWHUEHIRUHVWDUWLQJWKHXQLW
DC-N
,QGXVWULDOGHKXPLGL¿HUVZLWKWHPSHUDWXUHFRQWURO