Rev. B 06-2019
18
40
30
60
50
80
70
100
90
10
5
0
15 20 25 30 35 40
5
0
15
10
25
20
35
30
10
5
0
15 20 25 30 35 40 45
MTEC.6710.GB-B-1 Operation and maintenance manual HMA/Z series English
HMA/Z
,QGXVWULDOGHKXPLGL¿HUVZLWKWHPSHUDWXUHFRQWURO
3.4 Operation limits
The units MUST be used within the operation limit indicated in the diagrams (see above). the warranty will be inva-
lidated if the units are used in ambient conditions outside the limits reported. If there is the necessity to operate in
GLIIHUHQWFRQGLWLRQVSOHDVHFRQWDFWRXUWHFKQLFDORI¿FH
RH (%)
Room temperature (°C)
The units are designed to operate within false ceiling and/or heated technical room. The units are NOT suitable for
outdoor installations and / or technical room w/o heat (attics, rooms communicating with the outside) as it may form
condensation on the walls and inside the unit cabinet causing damages.
The units are designed to work in clean ambients and with the standard characteristics of the ambient air.
It’s suitable not to install the unit in swimming pools or ambient with polluted and/or aggressive air.
Contact the Company in case of necessity.
Outdoor ambient temperature (°C)
Indoor ambient temperature (°C)
DC-N
,QGXVWULDOGHKXPLGL¿HUVZLWKWHPSHUDWXUHFRQWURO