4
4.1.5.7 Setting the period of time in idle mode for tank draining
Note: This setting is available only if Idle Mode is set to “Idle Drain” (see chapter 4.1.5.6).
Select “
Idle Drain
” in the water management menu, then press the
<Set>
key.
In the upcoming modification dialogue set the period of time in idle mode after which an automatic
tank draining takes place.
Factory setting:
72 hours
Setting range:
10 ... 100 hours
4.1.5.8 Setting the fill rate correction
This function is used to adjust the fill rate.
Note
:
Adjustments must only be made by factory trained personnel.
Select “
Fill Corr
” in the water management menu, then press the
<Set>
key.
In the upcoming modification dialogue set the fill correction in % of factory set filling rate.
Factory setting:
100%
Setting range:
50 ... 200 %
4.1.5.9 Setting the drain rate
This function is used to adjust the drain rate.
Note
:
Adjustments must only be made by factory trained personnel.
Select “
Drain Corr
” in the water management menu, then press the
<Set>
key.
In the upcoming modification dialogue set the drain correction in % of factory set draining rate.
Factory setting:
100%
Setting range:
50 ... 200 %
Settings
Power Limit :100
Water Mngm. :Set
Remote Test :Set
Controls :Set
Date :01.10.08
Time :12:12
Esc
Set
Water Management
Idle Mode :Set
Idle Drain :72
Fill Corr :100
FTBD :Off
Drain Corr :100
Float Check :23:30
Esc
Set
Esc
Set
Idle Drain Time
72 h
72 h
Settings
Power Limit :100
Water Mngm. :Set
Remote Test :Set
Controls :Set
Date :01.10.08
Time :12:12
Esc
Set
Water Management
Idle Mode :Set
Idle Drain :72
Fill Corr :100
FTBD :Off
Drain Corr :100
Float Check :23:30
Esc
Set
Esc
Set
Fill Rate Correction
100 %
100%
Settings
Power Limit :100
Water Mngm. :Set
Remote Test :Set
Controls :Set
Date :01.10.08
Time :12:12
Esc
Set
Water Management
Idle Mode :Set
Idle Drain :72
Fill Corr :100
FTBD :Off
Drain Corr :100
Float Check :23:30
Esc
Set
Esc
Set
Drain Rate Correction
100 %
100%
Summary of Contents for Control GS OC-C Series