4.1.3.11.9 Setting the upper humidity alarm value
Note: This setting is available only if the humidity alert function is activated (see chapter 4.1..11.7).
Select “
RH Low
” in the internal control settings menu, then press the
<Set>
key.
In the upcoming modification dialogue set the desired lower humidity alarm value for tirggering a
humidity alert.
Factory setting:
33 %rH
Options:
20 ... 95 %rH
4.1.4 Setting the capacity limitation
Select “
Power Limit
” in the settings menu, then press the
<Set>
key.
In the upcoming modification dialogue set the desired capacity limitation in % of the maximum ca-
pacity of the humidifier.
Factory setting:
100 %
Setting range:
30...100 %
The water management settings menu appears.
Press the
< >
and
< >
keys in order to select the individual settings and press the
<Set>
key to
call up the modification dialogue for the selected setting. Please refer to the following chapters for
further information on the individual water management settings.
4.1.5 Water management settings
Select “
Water Mngm.
” in the settings menu, then press the
<Set>
key.
Internal Settings
Limit-Band :15
Lim-Damp :5
RH Alerts :On
Lim.Setpoint:80
RH High :75
RH Low :33
Esc
Set
Controls
Controlsign.:0-10V
Limitsignal :0-10V
Short CD :Off
Unit Type :Set
Time Prop. :Off
Int.Settings:Set
Esc
Set
Settings
Controls :Set
Power Limit :100
Water Mngm. :Set
Language :English
Remote Test :Set
Date :01.10.08
Esc
Set
Esc
Set
RH Low
33 %rH
33 %rH
Settings
Controls :Set
Power Limit :100
Water Mngm. :Set
Language :English
Remote Test :Set
Date :01.10.08
Esc
Set
Esc
Set
Power Limit
100 %
100 %
Settings
Power Limit :100
Water Mngm. :Set
Remote Test :Set
Controls :Set
Date :01.10.08
Time :12:12
Esc
Set
Esc
Set
Water Management
BD rate :50%
FTBD :On
FTBD Time :23:30
Drain Cool :Off
FTBD Hours :100
Idle Mode :Set
Summary of Contents for Control GS OC-C Series