background image

Dissimilar Metals

Do not connect dissimilar metals on the inlet and outlet nipples. Dielectric Unions should be
used. Another solution is to use brass or cast iron fittings between the boiler and any copper
fittings that you may be using. Failure to do so will result in galvanic corrosion and cause the
inlet and/or outlet nipples to fail over time.

This is not covered under the warranty.

Pump Installation

The circulation pump should be positioned as close to the boiler as possible, with the delivery
arranged to pump out of the tank outlet on the upper left side of the boiler (see Fig. 3)

The pump is powered by the boiler through terminals PL and PN located on the 120 volt
terminal block (lower right terminal block see Fig. 4 and Fig. 5). The pump starts when the
thermostat   terminals   on   the   control  board   are  closed,   and   stops   when  these   terminals   are
opened.

If desired, the pump may be operated continuously during the heating season. Should you
decide to wire the pump in this manner, it should be wired to the same supply circuit as the
boiler to prevent the pump from being turned off while the boiler is still powered.

Thermostat Connection

The   thermostat   connection   is   24   volt   AC.  

Only connect the thermostat after all

other   work   is   complete,   and   the   entire   heating   system   is   thoroughly
purged of air.

 The thermostat is connected to the terminals T1 and T2 on the control circuit

board (see Fig. 4 and Fig. 5). In zoned systems, the end switches of all the zone valves may be
connected in parallel and hooked up to the thermostat connection on the control board. For a
typical system (see Fig. 6).

Thermostats described as “Power Stealing” or as “Parasitic Thermostats”
must not be used.

Thermostat Cycle Length and Anticipator

Electronic   thermostats   typically   have   provisions   for   the   cycle   length,   and   type   of   heating
system. The instructions for the thermostat should be followed.

Older thermostats with anticipators should be set to 0.2 amps. Failure to correctly adjust this
setting may result in unsatisfactory comfort conditions, and could result in damage to the
thermostat.
In zoned systems where the thermostat is controlling a zone valve, or circulation pump and not
the boiler, the anticipator should be set to match the current draw of the zone valve being used.

7

Summary of Contents for CEB Series

Page 1: ... an appropriate antifreeze Do not use any other liquids especially methanol automotive antifreeze or any kind of oil Do not exceed 50 antifreeze LION BOILERS CEB Series Boiler Installation Manual TM CEB V12 0 Printed in Canada ...

Page 2: ...2 ...

Page 3: ... single phase power to terminals L1 and L2 and connection of a neutral conductor to the N terminal see Fig 4 Three phase models require connection of three phase power of the correct voltage to the L1 L2 and L3 terminals and a 120 volt 15 amp supply to the terminals SL and SN see Fig 5 Introduction Your Electric Boiler has been designed to exacting specifications to provide controlled efficient he...

Page 4: ...25 208 3 31 2 40 32 CEB 208 15 14 7 208 3 40 8 60 48 CEB 208 22 22 5 208 3 62 5 100 80 CEB 208 30 29 4 208 3 81 6 125 100 CEB 600 9 9 600 3 8 7 15 12 CEB 600 15 14 7 600 3 14 1 20 16 CEB 600 18 18 600 4 17 3 30 24 CEB 600 24 23 7 600 5 22 8 30 24 CEB 600 30 29 4 600 3 28 3 40 32 Control Voltage 24 Volts AC Tank Capacity Approx 2 Gallons Shipping Weight about 85 pounds Inlet and Outlet pipe size 1 ...

Page 5: ...sure will decrease at a rate of 0 433 psi per foot above the fill point An expansion tank must be included to allow for approximately 4 expansion of the water in the entire heating system As the water in the system is heated the pressure will increase but a properly sized expansion tank will prevent the pressure from exceeding the recommended operating pressure The radiators or floor system should...

Page 6: ...suitable for floor or wall mount only faces indicated as Zero Clearance may be mounted against combustible surfaces 5 Units must be mounted straight as shown in Fig 2 with the outlet at the top and the inlet on the bottom See Up Arrow on label on side of boiler 6 The circulation pump should be connected to the outlet side of the boiler see Fig 3 Mechanical Installation 1 Refer to Fig 3 for a typic...

Page 7: ...it as the boiler to prevent the pump from being turned off while the boiler is still powered Thermostat Connection The thermostat connection is 24 volt AC Only connect the thermostat after all other work is complete and the entire heating system is thoroughly purged of air The thermostat is connected to the terminals T1 and T2 on the control circuit board see Fig 4 and Fig 5 In zoned systems the e...

Page 8: ...cially true in the spring and fall when it is not so cold outside The actual temperature setting you need to set it to will be determined by the type of heating system the boiler is installed in The range of the aquastat is from 70 to 180º F Start Up A new system must be thoroughly cleaned flushed and drained then refilled with clean water Foreign material circulating through the system could be d...

Page 9: ... Check all valves Check for flow stoppage or air locks Boiler rapid cycles Check anticipator setting Check pump circulation Boiler operates continuously Check anticipator setting Boiler noisy Oversized pump Flow rate too high Flow rate too low Pump location incorrect Boiler not heating enough Insufficient capacity Burnt Elements Flow rate too low Pressure too high Defective expansion tank Defectiv...

Page 10: ...e that Boiler The obligation of the Manufacturer to repair replace or refund the purchase price exists provided the defective part or complete unit is returned to the Manufacturer ANY AND ALL TRANSPORTATION COSTS WILL BE BORNE BY THE PURCHASER Repair replacement or refund of any defective part or unit shall be considered as complete fulfillment of this warranty THIS WARRANTY DOES NOT APPLY TO 1 La...

Page 11: ...FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS LIMITED WARRANTY THE MANUFACTURER S LIABILITY ON ANY CLAIM OF ANY KIND INCLUDING NEGLIGENCE WITH RESPECT TO THE GOODS OR SERVICES COVERED HEREUNDER SHALL IN NO WAY EXCEED THE PURCHASE PRICE OF THE BOILER OR PART THEREOF WHICH GIVES RISE TO THE CLAIM IN NO EVENT SHALL THE MANUFACTURER BE LIABLE FOR SPECIAL INCIDENTAL INDI...

Page 12: ...12 ...

Page 13: ...13 ...

Page 14: ...14 ...

Page 15: ...15 ...

Page 16: ...16 ...

Page 17: ...17 ...

Page 18: ...at any of the elements then the element relay for that element is stuck on and needs to be replaced 2 Check the fuse on models equipped with a fuse a Remove the fuse located inside the boiler Check it for continuity Replace with a new fuse of the correct type if necessary b Otherwise replace the existing fuse 3 Check that there is 24 volt AC power on the secondary side of the transformer This is w...

Page 19: ...f the element relay indicator lights come on but the power relays do not come on then the low water cut off or the high limit control may be preventing them from coming on This may be due to a faulty component or may be an actual low water or high temperature condition A faulty low water cut off will prevent both the low water indicator and the high limit indicator lights from coming on A faulty h...

Page 20: ...nts but no heat then with the all the power disconnected to the boiler check the resistance of each element with an ohm meter to see if is correct Replace any elements as necessary If the element is open circuit and the cause is unknown it is advisable to also change the relay connected to that element If you have gone through the above steps and the boiler is still not working please contact us f...

Reviews: