PROGRAMMING

 

 

Smoke Time.

  The length of time that the Smoke Screen 

will produce ‘smoke’ can be varied 

between 15 seconds and 6 minutes.  The delivery smoke time setting is 15 seconds, which is 
equivalent to approximately 75 cubic metres of smoke.  The smoke time is set as follows: 
 

 

Change Dip Switch 2 to ‘ON’ (LED should alternate Red / Green to indicate in programming 
mode). 
 

 

Press the ‘PB1’ button for 10 seconds. When the buzzer beeps twice the timer is set to 15 
seconds. 
 

  Each subsequent press of 

the ‘PB1’ button will extend the smoke time by 15 seconds, up to 

a maximum of 6 minutes. 
 

  When the required smoke 

time setting is reached change Dip Switch 2 to ‘OFF’. 

 

 

If a mistake is made in programming the run time change Dip Switch 2 to ‘OFF’ and start 
again.  

 

UPS Monitoring.

  The Sentinel S30 can be set to monitor the UPS (if fitted) and enable the UPS 

relay output.  To alternate UPS monitoring between on and off follow this procedure: 
 

 

Change Dip Switch 2 to ‘ON’ (LED should alternate Red / Green to indicate in programming 
mode). 

 

Press ‘PB2’ for 10 seconds.  When the buzzer beeps twice the UPS monitoring has been 
changed between on and off.  

 

When finished change Dip Switch 2 to ‘OFF’. 

 

Note: If there is a UPS fault or no UPS is fitted the LED will flash twice every 5 seconds 
accompanied by 3 short beeps every 30 seconds.  

 

Trigger Mode.

  The delivery settings of the 3 sets of input connections on the Smoke Screen 

(Alarm Set, Trigger and Hold Off) 

are normally closed going open to activate (Dip 1 set to ‘ON’).  

These can be chang

ed to normally open going closed to activate by changing Dip 1 to ‘OFF’. 

 

OPERATION

 

 
While the Smoke Screen is heating up the LED indicator will be Red.  If any of the access panels are 
open the LED indicator will flash yellow once every 5 seconds; a tamper indication will prevent the 
Smoke Screen from producing smoke.  When the Smoke Screen reaches the correct working 
temperature, all tamper circuits are closed and a full Smoke Fluid Bag has been correctly installed, the 
LED Indicator will go Green. 
 

Stopping smoke.

  

If the ‘Hold-Off’ is closed during an activation the Smoke Screen will continue to 

produce smoke for the set Smoke Time.  An activation can only be stopped by closing the ‘Alarm Set’ 
and/or the ‘Trigger’. 
 

Re-triggering smoke 

(Hold-off attached)

.

  If, after it has made smoke for the pre-set time, the Smoke 

Screen receives another hold-off alarm with 

open ‘Alarm Set’ and ‘Trigger’ inputs it will ‘re-trigger’ and 

make smoke again. 
 

 

Summary of Contents for SENTINEL S30

Page 1: ...Page 1 of 16 SENTINEL S30 INSTALLATION AND OPERATION MANUAL Version 16 December 2013 CAN T SEE IT CAN T STEAL IT ...

Page 2: ...l help Once again thank you for your decision we hope that it s one that never needs to be tested Carl Gibbard Managing Director HOW DOES YOUR SMOKE SCREEN WORK Your Smoke Screen heats a non toxic fluid under pressure to create smoke or more accurately a thermally generated fog that obscures visibility to discourage intruders from entering your premises This fog is very persistent and will stay su...

Page 3: ...lation procedure 5 Access 6 Mounting 6 Controlling the smoke 7 Circuit board layout 8 Generic connection diagram 8 Un interrupted Power Supply UPS 9 Tamper 9 Fluid management 9 Programming 10 Operation 10 Testing 11 LED and sound indications 12 Action after every activation 13 Servicing and fluid replenishment 13 FAQ 13 Installer notes 14 ...

Page 4: ...tic STANDARD INSTALLATION A standard installation is configured in the following way The Smoke Screen wall or ceiling mounted in the appropriate location A Hold off PIR or similar device located within the same area as the Smoke Screen providing a confirmation signal to the Smoke Screen to start smoke production A Set command supplied by an Alarm Control Panel or equivalent in the form of an N C N...

Page 5: ...above the floor over the area to be protected and using a straight nozzle The maximum mounting height above floor level is 3 metres and there should be no obstacle within 1 metre of the smoke output nozzle INSTALLATION PROCEDURE 1 Site the Smoke Screen and fix the bracket to the wall or ceiling as appropriate 2 For wall mounting leave minimum 150mm clearance to ceiling 3 Fasten the Smoke Screen to...

Page 6: ...8mm washer 4 x 25mm washer 6 x full nut 2 x drop in anchor 2 x channel nuts Wall mounting The Smoke Screen can be wall mounted to fire horizontally or angled to fire down at 15 30 or 45 degrees using a simple wall bracket 1 that should be attached to a suitable wall using appropriate fixings We recommend as high a position as possible for aesthetic and security anti tamper reasons but no higher th...

Page 7: ...nput connections on the Smoke Screen Alarm Set Trigger and Hold Off that should be connected to clean contacts For the Smoke Screen to produce smoke all 3 sets of connections must be open circuit this can be changed to closed as described under Trigger Mode in the Programming section If one set of connections is closed circuit then the Smoke Screen is prevented from producing smoke Hence the produ...

Page 8: ... Input 4 Ready n c Machine ready ve Ready n o to activate Ground Ready com Set Trigger Set Trigger Intruder Alarm Intruder Alarm Tamper changes state if the S30 case or external tamper is open n c and n o show n are w hen the case is closed Outputs Ready changes state if there is a critical fault n c and n o show n are w hen the S30 is w orking correctly Low changes state if the S30 fluid is low n...

Page 9: ...es not prevent the Smoke Screen from activating FLUID MANAGEMENT Fluid capacity The Smoke Screen can be fitted with a 500ml transparent bag containing Smoke Fluid Fluid monitoring The Fluid Level is monitored using an on board timer that measures the amount of fluid used by timing consumption when the Smoke Screen is activated Each time the bag clamp is unfastened and the fluid bag is replaced the...

Page 10: ...n on and off When finished change Dip Switch 2 to OFF Note If there is a UPS fault or no UPS is fitted the LED will flash twice every 5 seconds accompanied by 3 short beeps every 30 seconds Trigger Mode The delivery settings of the 3 sets of input connections on the Smoke Screen Alarm Set Trigger and Hold Off are normally closed going open to activate Dip 1 set to ON These can be changed to normal...

Page 11: ...rigger contacts are closed Smoke Screen stand alone test The Smoke Screen can be tested when it is ready to operate indicated by a steady green LED by pressing the button on the PCB marked PB1 This produces smoke only whilst the button is pressed NB this does not check that the inputs and connections to the Smoke Screen are correct Note When mains power is switched on even if the Smoke Screen is a...

Page 12: ...Ready n c to open Heater fault On Continuous beep for 30 seconds then 3 short beeps every 5 minutes Nil Smoke Screen heating to operating temperature Alternating None Nil Smoke Screen in Programming Mode On None Ready n c to closed Smoke Screen ready to operate Flashing None Nil Smoke Screen receiving Alarm Set and Trigger signals but waiting for a Hold Off to activate Flashing 1 beep every 2 seco...

Page 13: ...is serviced replenished by an engineer certified by the manufacturer If you are unsure ask the engineer for his certification ID card It is recommended that the Smoke Screen is checked and the fluid changed annually by the installer or Concept Smoke Screen Always ensure that the Smoke Screen has sufficient fluid or it will not produce smoke when needed It is recommended that the installer or Conce...

Page 14: ...Page 14 of 16 INSTALLER NOTES ...

Page 15: ...Page 15 of 16 ...

Page 16: ...Page 16 of 16 Concept Smoke Screen Limited 1 2 North End Swineshead Lincolnshire PE20 3LR United Kingdom Tel 44 0 1205 821111 Fax 44 0 1205 820316 Email info smoke screen co uk www smoke screen co uk ...

Reviews: