again (the corresponding led starts to flash) and keep it pressed until 
the led stops flashing, which confirms the successful deletion of all 
codes saved in the system.

Programming buttons 
TX CODE  

Remote control programming

ACCESSORIES DETECTION (BUS LINE)

The control unit automatically detects all the ONE accessories 
wired on the BUS line, checking the type of accessory, its numeric 
identifier ID and the type of operation set (MODE). Always make sure 
to use accessories with different ID for each type of accessory (par: 
ACCESSORY ADDRESS ASSIGNMENT). The system also detects 
the accessories installed on the BUS line:

1 Before the maximum stroke self-learning process (AUTOSET). At 

this stage, the system detects the accessories installed and saves 
the system configuration (e.g.: new installation).

2  Each time you press the RESET button. At this stage, the system 

re-reads the accessories installed, but does not change the initial 
configuration (accessories saved).

NOTE: 

The detection of the accessories is an automatic operation 

that may cause a delay in the system’s configuration proportionate 
to the number of accessories installed.

NOTE:

 Make sure you have set the ID and MODE (operating mode) 

on all accessories installed, before connecting them to the digital 
BUS line.

IMPORTANT! If you want to configure the system with 
ONE app access (requires the use of tablet with wireless 
connection and a K-ONE access key - code ONE KEY), keep 
the MODE dip-switches set to OFF (TYPE 1 operation) for all 
accessories connected to the BUS line.

ADJUSTMENTS FROM COMUNELLO ONE APP

The control unit features an advanced access for additional system 
configuration. Using the (optional) accessory K-ONE (code ONE 
KEY), you can connect to the control unit via Wi-Fi radio and proceed 
to its full configuration following a simple and guided procedure, with 
the aid of the COMUNELLO ONE app that you can download from 
our online store. To use the app COMUNELLO ONE, you will need 
a wifi device (tablet or smartphone) with android or iOS operating 
system. 

Connector for K-ONE module

Configuration via the COMUNELLO ONE app allows you to configure 
and adjust all the parameters of the system in a fast and easy way, 
monitor its operation, manage the list of saved remote controls, copy 
the configuration to another equivalent system and plan maintenance.

ADDITIONAL ADJUSTMENTS FROM THE APP:

Guided procedure to check direction of rotation of the operators and 
change their settings.

Commands

Set the pause time (automatic closing)  

(0”..4 min)

Enable Permanent Close.

Force/Speed

Adjust maximum operator speed during opening cycle  
(10%..100%)
Adjust maximum operator speed during closing cycle  (10%..100%)
Adjust deceleration speed during opening cycle  

(10%..100%)

Adjust deceleration speed during closing cycle  

(10%..100%)

Start Operator 1 deceleration during opening cycle   (  0%..100%)
Start Operator 1 deceleration during closing cycle  

(  0%..100%)

Start Operator 2 deceleration during opening cycle   (  0%..100%)
Start Operator 2 deceleration during closing cycle  

(  0%..100%)

Adjust pedestrian opening  

 

 

(10%..100%)

Enable/Disable Operator Brake
Enable/Disable Soft Stop
Enable/Disable Soft Start
Enable/Disable Release Stroke
Enable/Disable Slam Lock

Remote controls

Read saved codes and set function
Assign a text string for each code
Delete single code
Add a new code
Check the presence of a code

Photocells

Enable/Disable Partial Inversion during Closing cycle
Enable/Disable Partial Inversion during Opening cycle
Enable/Disable Follow-Me
Operation test
Assign a text string for each photocell
Set the MODE (operation) of each photocell

Key switches

Operation test
Assign a text string for each key switch
Set the MODE (operation) of each key switch

Flashing lights

Enable/Disable Closing Pre-Flash
Enable/Disable Opening Pre-Flash
Enable/Disable Fast Flash during Opening cycle
Enable/Disable Fast Flash during Closing cycle
Enable/Disable Flash during Pause
Operation test
Assign a text string for each key flashing light

Interface I/O 

Operation test
Assign a text string for each Interface I/O 
Set the MODE (operation) of each Interface I/O 

Utility output

Set Electric lock activation time   (1”..20”)

Diagnostics

Display the number of Manoeuvres  Performed
Display the number of Operator Hours of operation
Display the number of System Life Hours
Display the number of Resets
Display the number of Stops (STOP commands)
Display the number of Encoder notches

FACTORY RESET

However necessary to restore the configuration as shipped, press 
simultaneously the RESET and STEP BY STEP pushbuttons, then stop 
pressing RESET button, keeping pressing the STEP BY STEP button till the 
AUTOSET led will  blink. Stop pressing the STEP BY STEP button and wait 
until the TX POWER BUS LED starts blinking (about 20’’).

DIAGNOSTICS

Photocell (DS) management in case of a fault

The photocell management (DS) in case of a fault of AT LEAST ONE OF 

Summary of Contents for CU 24V 2M ONE

Page 1: ...AND USER S MANUAL comunello com ISTRUZIONI D USO E DI INSTALLAZIONE INSTALLATIONS UND GEBRAUCHSANLEITUNG INSTRUCIONS D UTILISATION ET D INSTALLATION INSTRUCCIONES DE USO Y DE INSTALACION Control unit...

Page 2: ...Cable type Lenght 1m to 20m Lenght 20m to 50m 1 Main power supply HAR EN50575 CPR 305 2011 2x1 5mm2 2x2 5mm2 6A Motor power supply 2x2 5mm2 2x4 0mm2 2 Flashing light 2x0 5mm2 2x1 0mm2 4A 5A Photocell...

Page 3: ...DER MOTORE n2 MOTOR n2 ENCODER MOTORE n1 MOTOR n1 INGRESSO INPUT 8K2 ANTENNA TRASFORMATORE TRANSFORMER 230 20V 6 5A 32V 0 8A LINEA POWER SUPPLY 2P 230V 50Hz MOTORE n1 MOTOR n1 24V LAMPEGGIANTE FLASHIN...

Page 4: ...4 COMUNELLO Copyright 2019 All rights reserved 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 CN2 CN3 CN4 CN6 CN5 CN7 CN8 CN9 CN1...

Page 5: ...FORT opens to RIGHT Inner side view FORT opens to LEFT Inner side view 1 MOTOR CONFIGURATION FORT MOTOR 1 OUTPUT RED ON BLACK ON INV1 INV1 ENCODER MOT N 1...

Page 6: ...OTORS CONFIGURATION ABACUS connection diagram of the motors INV1 INV2 INV1 2 1 2 1 2 INV1 INV2 INV1 2 DELAY OF THE MOTOR n 2 DELAY OF THE MOTOR n 1 Configuration MASTER ON THE LEFT SLAVE ON THE RIGHT...

Page 7: ...INV1 2 INV1 INV2 INV1 2 1 2 DELAY OF THE MOTOR n 2 DELAY OF THE MOTOR n 1 Configuration MASTER ON THE LEFT SLAVE ON THE RIGHT MOTOR n 1 WITH CONTROL UNIT on the left RED with MOT1 BLACK with MOT1 MOT...

Page 8: ...HE RIGHT SLAVE ON THE LEFT MOTOR n 2 WITHOUT CONTROL UNIT on the left MOT2 with M MOT2 with M MOTOR n 1 WITH CONTROL UNIT on the right RED with MOT1 BLACK with MOT1 CONDOR 220 350 2 2 1 2 INV1 INV2 IN...

Page 9: ...INV1 INV2 INV1 2 INV1 INV2 INV1 2 1 2 DELAY OF THE MOTOR n 2 DELAY OF THE MOTOR n 1 Configuration MASTER ON THE LEFT SLAVE ON THE RIGHT MOTOR n 1 on the left RED with MOT1 BLACK with MOT1 MOTOR n 2 o...

Page 10: ...1 2 CONDOR 500 connection diagram of the motors Configuration MASTER ON THE LEFT SLAVE ON THE RIGHT MOTOR n 1 on the left MOT1 with M MOT1 with M MOTOR n 2 on the right MOT2 with M MOT2 with M DELAY O...

Page 11: ...2 CE Direttiva MD 2014 53 EU Direttiva RED e che sono state applicate tutte le norme e o specifiche tecniche di seguito indicate EN61000 6 2 2005 EN61000 6 3 2007 EN62233 2008 EN301489 3 EN60335 2 103...

Page 12: ...re inoltre attenzione a fissare i cavi in modo che siano ancorati in modo stabile e a non danneggiare la scheda con la foratura fig 3B L involucro nella parte posteriore provvisto di opportune predisp...

Page 13: ...i ENC MOT1 E2 Ingresso Encoder Motore 1 ENC MOT2 E1 Ingresso Encoder Motore 2 encoder 2 fili ENC MOT2 E2 Ingresso Encoder Motore 2 CN7 ENC MOT1 Ingresso Alimentazione Encoder Motore 1 ENC MOT1 GND Ing...

Page 14: ...LLA FUNZIONAMENTO MODE DEGLI ACCESSORI FUNZ TIPO 1 FUNZ TIPO 2 FUNZ TIPO 3 FUNZ TIPO 4 FOTOCELLULA RX IN CHIUDE IN APRE IN APRE CHIUDE IN STOP SELETTORE AUTO PP PED APRE CHIUDE AUTO PP STOP SCHEDA IO...

Page 15: ...do AUTO PP apri chiudi IN2 COM ingresso optoisolato N O Aziona il comando STOP blocco automazione Uscita Sono disponibili due uscite impostate con funzionalit SPIA che si attivano contemporaneamente s...

Page 16: ...iene intercettata in chiusura effettua l inversione apertura completa del serramento In apertura non agisce FOTOCELLULA RX di TIPO 2 IN APRE Se la fotocellula viene intercettata in apertura effettua l...

Page 17: ...rmale lampeggiante Morsetti di uscita per il collegamento del servizio ausiliario programmabile in alternativa come COMANDO ELETTROSERRATURA LAMPEGGIANTE AUSILIARIO ATTENZIONE Carico massimo 24V 5W co...

Page 18: ...empre i DS se presenti Disabilitare temporaneamente solo in fase di manutenzione ATTENZIONE Una variazione dei dip switches richiede la pressione del tasto RESET sulla centrale per rendere attiva la n...

Page 19: ...cessori presenti sul BUS viene effettuato anche 1 Prima della manovra di autoapprendimento della corsa massima AUTOSET In questa fase vengono rilevati gli accessori presenti e salvata la configurazion...

Page 20: ...ella battuta meccanica GARANZIA a La presente garanzia nei rapporti commerciali o in caso di vendita di beni per uso professionale limitata alla riparazione o sostituzione del pezzo del Prodotto ricon...

Page 21: ...ale In caso di necessit di avere una alimentazione diretta a 24VDC sempre presente servizi si pu usare l uscita dedicata OUT AUX rinunciando alla funzionalit LAMP AUX o COMANDO ELETTROSERRATURA che pu...

Page 22: ...10 DIP 7 ON Lampeggiante Ausiliario DIP 7 OFF Comando Elettroserratura O N 1 2 3 4 5 6 7 8 9 10 DIP 5 ON Funzionamento a 1 Motore DIP 5 OFF Funzionamento a 2 Motori O N 1 2 3 4 5 6 7 8 9 10 DIP 2 ON...

Page 23: ...irective 2014 53 EU RED Directive and that all the rules and or technical specifications shown below have been applied EN61000 6 2 2005 EN61000 6 3 2007 EN62233 2008 EN301489 3 EN60335 2 103 2015 EN60...

Page 24: ...with screws Take all the measures required to ensure the installation procedures do not affect the IP rating If required a pushbutton panel for manual control of the gate must be installed in a posit...

Page 25: ...ut NC ENC MOT1 E1 Operator 1 Encoder Input 2 wire encoder ENC MOT1 E2 Operator 1 Encoder Input ENC MOT2 E1 Operator 2 Encoder input 2 wire encoder ENC MOT2 E2 Operator 2 Encoder Input CN7 ENC MOT1 Ope...

Page 26: ...OPERATION MODE OF THE ACCESSORIES OPER TYPE 1 OPER TYPE 2 OPER TYPE 3 OPER TYPE 4 PHOTOCELL RX ON CLOSE ON OPEN ON OPEN CLOSE IN STOP KEY SWITCH AUTO PP PED OPEN CLOSE AUTO PP STOP INTERFACE I O In A...

Page 27: ...NO Voltage free NO contact output 24V 1A max C Voltage free contact output common Flashing light output moving gate Output enabled ON open gate Output disabled OFF closed gate I O INTERFACE TYPE 4 In...

Page 28: ...ser will have to send a subsequent command to restore operation of the automation OPENING AND CLOSING LIMIT SWITCHES The control unit allows the connection of an opening limit switch FCA and a closing...

Page 29: ...onnection of the single operator to terminal MOT 1 CHANGING ROTATION DIRECTION AND START PRIORITY The control unit features three slide switches that allow you to set or change the direction of rotati...

Page 30: ...MING To start the auto learning cycle position the half open gate press the AUTOSET button until the respective LED lights up positioned above the AUTOSET button and release the button The AUTOSET led...

Page 31: ...stem and plan maintenance ADDITIONAL ADJUSTMENTS FROM THE APP Guided procedure to check direction of rotation of the operators and change their settings Commands Set the pause time automatic closing 0...

Page 32: ...uthorized personnel or due to incorrect use installation in this regard system maintenance at least every six months is recommended or the use of non original spare parts defects caused by chemical ag...

Page 33: ..._YZKS with the app I can no longer change the basic parameters through the dip switches of the control unit 5TIK _U NG K IUT M XKJ _U X Y_YZKS through the app the command is automatically disabled by...

Page 34: ...liary Flashing Light DIP SWITCH 7 OFF Electric lock command O N 1 2 3 4 5 6 7 8 9 10 DIP SWITCH 5 ON Operation with 1 Operator DIP SWITCH 5 OFF Operation with 2 Operators O N 1 2 3 4 5 6 7 8 9 10 DIP...

Page 35: ...ED Richtlinie und dass alle folgenden Normen und oder technischen Spezifikationen angewendet wurden EN61000 6 2 2005 EN61000 6 3 2007 EN62233 2008 EN301489 3 EN60335 2 103 2015 EN60335 1 2012 sowie ih...

Page 36: ...on ohne Ver nderung des IP Schulzgrades vorzusehen und zu implementieren Falls eine Druckknopftafel f r die manuelle Bedienung montiert wird ist diese so zu positionieren dass sich der Benutzer nicht...

Page 37: ...ENC MOT1 E2 Eingang Encoder Motor 1 ENC MOT2 E1 Eingang Encoder Motor 2 Encoder 2 Leiter ENC MOT2 E2 Eingang Encoder Motor 2 CN7 ENC MOT1 Eingang Speisung Encoder Motor 1 ENC MOT1 GND Eingang Common E...

Page 38: ...ON BETRIEBSART TIPO 4 DIP2 ON Die Betriebsart ist vom ber cksichtigten Zubeh r abh ngig TABELLE BETRIEBSART MODE DER ZUBEH RE BETR ART 1 BETR ART 2 BETR ART 3 BETR ART 4 FOTOZELLE RX BEI SCHLIESSUNG...

Page 39: ...f r Kontrolllampe 24V NO Ausgang sauberer N O Kontakt 24V 1A max C Ausgang sauberer Kontakt Common I O INTERFACE TYP 3 In AUTP PP STOP Out KONTROLLLAMPE Eingang Durch Benutzung der Eing nge IN1 COM o...

Page 40: ...s Betriebs der einzelnen Fotozelle RX Empf nger mit entsprechendem Dip Switch auf der Karte Abs EINSTELLUNG DES BETRIEBS DER ZUBEH RE unterscheidet man die folgenden verschiedenen Betriebsarten FOTOZE...

Page 41: ...ativ Elektroschl sser mit 24V 12W iStossstrom oder Blinkleuchten mit 24V 5W Dauerstrom gesteuert werden k nnen Wenn der Ausgang als ELEKTROSCHLOSSSCHALTUNG programmiert ist wird die Schaltung bei jede...

Page 42: ...ng zu dr cken AUSSCHALTUNG DER SICHERHEITSVORRICHTUNGEN Es besteht die M glichkeit die vorhandenen und an die BUS Leitung der Zubeh re angeschlossenen Sicherheitsvorrichtungen wie z B die Fotozellen u...

Page 43: ...g ist mit der Funktion AUX 2 Hilfskanal gespeichert L schen Zur L schung aller gespeicherten Funkcodes ist auf den Taster CODE TX zu dr cken und der Zustand der entsprechenden LED oberhalb der Taste C...

Page 44: ...Sicherheitsprobleme verursachen w rde sondern nur die nicht mehr funktionierenden Fotozellen Neuerfassung der fehlenden DS Defektbehebung Falls sich auf einer Fotozelle DS ein Defekt ereignet hat scha...

Page 45: ...N JOK HKN XK Blinkleuchten Fotozellen W hlschalter usw anderer Hersteller benutzen Das System ONE setzt die Verwendung JKX JOMOZGRKT HKN XK 54 SOZ OTZKMXOKXZKX Intelligenz voraus die auf der BUS Leitu...

Page 46: ...aus der Ferne 1UTZXURROKXKT JGYY JKX 5NS Impedanzabschluss der Antenne OTYZGRROKXZ OYZ 1UTZXURROKXKT JGYY JKX Impedanzabschluss auch bei Benutzung JKY 1UG OGRQGHKRY UXNGTJKT OYZ JGY 1UG OGRQGHKR UNTK...

Page 47: ...lverz gerung Aktiv feste 4 beim ffnen und Schlie en DIP 6 OFF Fl gelverz gerung Nicht Aktiv feste 4 nur beim Schlie en O N 1 2 3 4 5 6 7 8 9 10 DIP 8 ON Druckstoss Aktiv DIP 8 OFF Druckstoss Nicht Akt...

Page 48: ...E Directive MD 2014 53 EU Directive RED Et qui ont t soumis toutes les norms et ou sp cifications techniques ci apr s indiqu es EN61000 6 2 2005 EN61000 6 3 2007 EN62233 2008 EN301489 3 EN60335 2 103...

Page 49: ...les ou vis Adopter toutes les pr cautions n cessaires en vue d une installation conforme l indice IP pr vu En cas de montage d un clavier manuel viter toute situation dangereuse pour l utilisateur L o...

Page 50: ...commun moteur 1 FC MOT1 FCA Entr e fin de course ouverture moteur 1 NF ENC MOT1 E1 Entr e codeur moteur 1 codeur 2 fils ENC MOT1 E2 Entr e codeur moteur 1 ENC MOT2 E1 Entr e codeur moteur 2 codeur 2 f...

Page 51: ...N Le type de fonctionnement varie selon l accessoire TABLEAU FONCTIONNEMENT MODE DES ACCESSOIRES FONCT TYPE 1 FONCT TYPE 2 FONCT TYPE 3 FONCT TYPE 4 PHOTOCELLULE RX EN FERMETURE EN OUVERTURE EN OVERT...

Page 52: ...ctiver les commandes suivantes IN1 COM entr e opto isol e NO Actionne la commande AUTO PP ouverture fermeture IN2 COM entr e opto isol e NO Actionne la commande STOP arr t automatisme Sortie Deux sort...

Page 53: ...OTOCELLULE RX de TYPE 2 EN OUVERTURE Si la photocellule est intercept e en ouverture elle d clenche l arr t du portail et le mouvement d ouverture ne reprend qu apr s lib ration du faisceau La photoce...

Page 54: ...COMMANDE LECTROSERRURE CLIGNOTANT AUXILIAIRE ATTENTION Charge maximum 24V 5W continus 12W impulsifs O N 1 2 3 4 5 6 7 8 9 10 DIP 7 ON Clignotant auxiliaire DIP 7 OFF Commande lectroserrure ATTENTION A...

Page 55: ...t durant la phase d entretien ATTENTION Apr s toute modification des dip switch appuyer sur la touche RESET de l unit centrale pour activer la nouvelle configuration ENTR E 8K2 BLOCAGE L unit centrale...

Page 56: ...es pr sents et sauvegarde la configuration du syst me ex en cas de nouveau syst me 2 chaque pression de la touche RESET Cette phase relit tous les accessoires pr sents mais ne modifie pas la configura...

Page 57: ...enti rement ouvert man uvre de s curit la man uvre peut entra ner son blocage en ouverture et le besoin de transmettre une nouvelle commande pour refermer le portail GESTION BLACKOUT Le syst me au man...

Page 58: ...raccord RK ZU Z KZ IUT M X RKY param tres de base au moyen des dip switch r glages manuels les moteurs n actionnent pas le portail sur pression du bouton STEP BY STEP XO KX RKY XGIIUXJKSKTZY G KI RKY...

Page 59: ...ion Le syst me ONE permet il de g rer un portail JU HRK IU ROYYGTZf NON Avec l unit centrale ONE il n est pas possible de g rer un double coulissant synchronis Quelle sont les r glages possibles des d...

Page 60: ...S 2006 42 CE Directiva MD 2014 53 EU Directiva RED Y que han sido aplicadas todas las normas y o especificaciones t cnicas en lo sucesivo indicadas EN61000 6 2 2005 EN61000 6 3 2007 EN62233 2008 EN301...

Page 61: ...trasera est preparada para la fijaci n a la pared predisposici n para la fijaci n con tacos u orificios para la fijaci n con tornillos Prevea y tome todas las medidas de precauci n para realizar una i...

Page 62: ...Motor 1 N C ENC MOT1 E1 Entrada Encoder Motor 1 encoder 2 hilos ENC MOT1 E2 Entrada Encoder Motor 1 ENC MOT2 E1 Entrada Encoder Motor 2 encoder 2 hilos ENC MOT2 E2 Entrada Encoder Motor 2 CN7 ENC MOT1...

Page 63: ...IP2 DIP1 ON FUNCIONAMIENTO TIPO 4 DIP2 ON El tipo de funcionamiento depende del accesorio tenido en cuenta TABLA DEL FUNCIONAMIENTO MODE DE LOS ACCESORIOS FUNC TIPO 1 FUNC TIPO 2 FUNC TIPO 3 FUNC TIPO...

Page 64: ...Entrada Utilizando las entradas IN1 COM o IN2 COM se activan los siguientes mandos IN1 COM entrada optoaislada N A Acciona el mando AUTO PP abrir cerrar IN2 COM entrada optoaislada N A Acciona el man...

Page 65: ...uncionamiento de cada fotoc lula RX receptor mediante el dip switch en la tarjeta apdo CONFIGURACI N DEL FUNCIONAMIENTO DE LOS ACCESORIOS se distinguen las siguientes funciones FOTOC LULA RX TIPO 1 DU...

Page 66: ...o MANDO ELECTROCERRADURA el mando se activa durante 3 segundos cada vez que comienza un movimiento de apertura Si la salida est programada como LUZ INTERMITENTE AUXILIAR ser gobernada por el cuadro de...

Page 67: ...lulas y la entrada 8K2 lo cual permite hacer funcionar el automatismo inclusive en los casos de posibles fallos en los DS agilizando as el mantenimiento o los controles t cnicos del sistema De todas m...

Page 68: ...ador CODE TX con la siguiente asociaci n 1 Cuatro presiones del pulsador CODE TX presione el pulsador 4 vez el LED correspondiente se enciende con luz fija Para confirmar la cancelaci n presione de nu...

Page 69: ...rente las configuraciones de ajuste de los DS presentes En definitiva inhabilitando los dispositivos de seguridad DS no se eliminan las fotoc lulas presentes y que funcionan creando problemas de segur...

Page 70: ...os de terceros inclusive digitales no son compatibles con el sistema Se pueden utilizar dispositivos de terceros utilizando la INTERFACE I O ONE que permite gestionar pulsadores N A luces testigo y di...

Page 71: ...XG correspondiente En este caso el cuadro JK IUTZXUR H YIG KR ZUVK SKI TOIU U KR TGR de carrera m ximo memorizado mediante el encoder No se producen fallos de funcionamiento pero se pierde la segurida...

Page 72: ...NOTES...

Page 73: ...73 COMUNELLO Copyright 2019 All rights reserved NOTES...

Page 74: ...FRATELLI COMUNELLO S P A AUTOMATION GATE DIVISION Via Cassola 64 C P 79 36027 Ros Vicenza Italy Tel 39 0424 585111 Fax 39 0424 533417 info comunello it www comunello com...

Reviews: