background image

16

COMUNELLO

  ®Copyright 2014 - All right reserved

maximum speed.
Initial starting torque can be set for each movement by feeding the operator 
at full power for 2 seconds, even if operator force control is enabled. Note: 
initial starting torque is disabled automatically if the Soft Start function is 
enabled.

Important: If the “SPEED” trimmer is adjusted the self-learning 
procedure must be repeated because the movement and deceleration 
times may change.

DECELERATION:

The operators deceleration function is used on gates to prevent the moving 
leaves from slamming at speed into the limit stops at the end of the opening 
and closing strokes.
During Operator Time programming (see Main menu) the control unit also 
allows programming of deceleration in the desired points (immediately 
before full opening and full closing); in addition, using the “DELAY” trimmer 
the force intensity can be adjusted during the deceleration phase.

1. OPENING DIRECTION (DIR):

In the default configuration the control unit is set with “OPEN TO RIGHT” 
logic (seen from the operator side, with operator installed to the right of 
the sliding leaf); if the “OPEN TO LEFT” logic must be enabled (seen from 
operator side, operator installed to the left of the sliding leaf), proceed as 
follows: use the SELECT key to select the blinking DIR LED and press the 
SET key: the OPEN DIRECTION LED will light steady and programming will 
be completed. Repeat the procedure if you wish to restore the previous 
configuration.

2. STEP-BY-STEP:

In the default configuration the control unit is set with “Automatic” operating 
logic enabled (LED n2  off); if the “Step-by-Step” operating logic is required 
(LED n2 on), proceed as follows; use the SELECT key to select blinking 
LED n2 and then press the SET key: LED n2 becomes steady on and 
programming will be completed.
If the “Step-by-Step 1” operating logic is required, repeat the operation 
above described, by pressing the SEL key twice instead only one (to obtain 
the quick blinking of LED. Repeat the procedure if you wish to restore the 
previous configuration.

3. TX CODE: (Remote control code)

Up to 120 remote controls with different codes of either the fixed or the 
rolling code type can be saved on the control unit. 

Programming:

Programming of the transmission code is performed as follows: use the 
SELECT key to select blinking LED L3. Press SET once; the LED will change 
its blinking mode (longer 1 0 1 0) to show that the first level is being saved. 
On sending the selected code with the desired remote, the CODE LED will 
remain steady on to indicate that programming has been completed.
To save the code for pedestrian opening / single leaf proceed as follows: 
use the SELECT key to select blinking CODE LED L3. Press SET twice 
consecutively; the LED will change its blinking mode (1 1 0 1 1 0) to show 
that the pedestrian code is being saved. On sending the selected code 
with the desired remote CODE LED L3 will remain steady lit to indicate that 
programming has been completed.
If all 120 codes have been saved, repeating the programming operation will 
cause all the programming LEDs to start blinking to signal that no further 
codes can be saved.

Deletion:

Use SELECT to go to LED L3; activate blinking of the code to be deleted 
(CODE or PEDESTRIAN identified by the respective blinking); press and 
hold down SET for > 5 s. After this interval the LED will switch off for 2 
seconds and the procedure is completed. If all CODE and PEDESTRIAN 
codes are deleted, the LED will remain off.
If only PEDESTRIAN codes remain stored, the LED blinking mode will 
change (1 1 1 1 0 1 1 1 1 0).

Rule of the first saved Remote control:

When programming remotes the following rule is applied: if the first remote 
to be saved is of the rolling code type, the receiver will subsequently 
accept only rolling code remotes, thus providing enhanced anti-intrusion 
security; if the first remote to be saved is a fixed code type, the receiver will 
subsequently accept both fixed code remotes and rolling code remotes, 
although only the fixed part of the latter will be controlled (thus effectively 
relinquishing the security of the rolling code system).

4. CONDO:

The Condominium function means that during the opening movement or 
during the pause time the control unit will not respond to commands sent 

by Pushbuttons or remotes. In contrast, during the closing movement a 
command sent by the Pushbuttons or the remotes will reverse the direction 
of movement. This operating mode is invaluable when the automation 
includes a loop detector.
In the default configuration the control unit is set with the Condominium 
function disabled; if the Condominium function is required, proceed as 
follows: use the SELECT key to select blinking LED L4 and then press 
the SET key: LED L4 will light steady and programming will be completed. 
Repeat the procedure if you wish to restore the previous configuration.

5. MOTOR TIME

 

(Programming of the motor run time of the 

operators with max 4 minutes):

The control unit is factory set with preset motor time of 30 seconds 
without deceleration. If the motor time of the operators must be changed, 
programming must be carried out with the gate closed as follows: use 
the SELECT key to select blinking LED L5 and then press the SET key 
momentarily; the operator will start the opening movement; when the 
desired deceleration starting point is reached press the SET key again; at 
the same time the operator will decelerate and reach the desired position; 
press SET to terminate the opening cycle. Thereafter LED L5 will start 
blinking rapidly; now repeat the motor time and deceleration programming 
procedure for the closing cycle. If you do not require the control unit to 
perform the deceleration, during programming, when the open-close cycle 
has been completed press the SET key twice consecutively rather than 
just once.
During programming, instead of the SET key on the control unit you can use 
the button on the remote, providing the remote has been saved beforehand.

6. PAUSE TIME: (Programmazione tempo chiusura aut. 4 min. max.):

The control unit is factory set with automatic closing disabled. If you wish 
to enable automatic closing proceed as follows: use the SELECT key to 
select blinking LED L6 and press the SET key momentarily; now wait for 
a time equivalent to the desired time interval; press the SET key again 
momentarily and at the same time the automatic closing time will be saved 
and LED L6 will remain steady on. If you wish to restore the initial condition 
(no automatic closing) select blinking LED L6 and then press the SET key 
twice consecutively in a time period of 2 seconds. The LED will switch off 
and the operation will be completed.
During programming, instead of the SET key on the control unit you can use 
the button on the remote, providing the remote has been saved beforehand.

7. AUTOMATIC PROGRAMMING:

The control unit provides allows Automatic Programming (SIMPLIFIED).
First bring the gate leaves to an intermediate position, use the SELECT 
key to select blinking LED L7 and then hold down the SET key; the 
control unit executes the Auto programming procedure by performing a 
complete opening and closing cycle (keep the SET key pressed until Auto 
Programming is completed). During the Auto Programming procedure, 
the Deceleration cycle is set automatically at approximately 15% of the 
complete cycle.
During Automatic Programming, instead of the SET key on the control unit 
you can use the button on the remote, providing the remote has been 
saved beforehand.

EXTENDED MENU 1

The control unit is factory set to allow direct selection exclusively of the main 
menu functions. If you wish to enable the functions described in Extended 
Menu 1, proceed as follows: select blinking LEV LED and press SET once. 
The LED will start blinking. This means there will be 30 seconds to select 
the functions of Extended Menu 1 using the SELECT and SET keys; once 
an additional 30 seconds have elapsed the control unit reverts to the main 
menu.

 

L1

FOTOTEST

ON

OFF

L2

PEDESTRIAN TIME

ON

OFF

L3

DECELERATION

OFF

ON

L4

REMOTE CODE PGM

ON

OFF

L5

RELEASE STROKE 

ON

OFF

L6

SLAM LOCK

ON

OFF

L7

COURTESY LIGHT

ON

OFF

LEV LEV

1 FLASH

1. PHOTOCELLS TEST:

The control unit is factory set with the photocells test disabled; proceed 

Summary of Contents for CU-24V-1M

Page 1: ...USER S MANUAL Control unit comunello com ISTRUZIONI D USO E DI INSTALLAZIONE INSTALLATIONS UND GEBRAUCHSANLEITUNG INSTRUCIONS D UTILISATION ET D INSTALLATION INSTRUCCIONES DE USO Y DE INSTALACION Cod...

Page 2: ...ON OFF L5 RELEASE STROKE ON OFF L6 SLAM LOCK ON OFF L7 COURTESY LIGHT ON OFF LEV LEV 1 FLASH ID LED L1 SOFT STOP ON OFF L2 SOFT START ON OFF L3 DS 1 IN OPEN ON OFF L4 HOLD TO RUN ON OFF L5 FOLLOW ME...

Page 3: ...C 24V SLIDING GATE CU 24V 1M ID Description Cable type Lenght 1m to 20m Lenght 20m to 50m 1 Main power supply FG7 CEI 20 22 CEI EN 50267 2 1 2x1 5mm2 2x2 5mm2 2 Flashing light 2x0 5mm2 2x1 0mm2 4A 6A...

Page 4: ...RSA CHIUDI N C END CLOSE N C FOTOCELLULA DS N C ATTIVA IN CHIUSURA PHOTCELL DS N C ACTIVE IN CLOSING FOT GND STOP GND GND FCA DS1 GND PP ANT ANT FCC CN2 LAMPEGGIANTE FLASHING LIGHT 24V 4W CN1 M MOTORE...

Page 5: ...reserved ITALIANO FORT like below Led opening direction OFF OPENS TO THE RIGHT Inner side view OPENING DIRECTION 1 MOTOR CONFIGURATION FORT FORT like below Led opening direction ON OPENS TO THE LEFT I...

Page 6: ...SALIENT DO NOT CHANGE the configuration Opens to the left closes to the right left profile view as in the image SALIENT BLACK ON M1 RED ON M1...

Page 7: ...directives 2004 108 EC Directive EMC Directive 2006 95 CE Directive and that all the rules and or technical specifications shown below have been applied EN61000 6 2 EN61000 6 3 EN62233 2008 EN301489 1...

Page 8: ...The rear of the box is equipped with knockouts for wall fixing knockouts for fixing holes using anchor bolts or holes for fixing with screws Take all the measures required to ensure the installation p...

Page 9: ...ttons are used to control the gate operation is as follows the first command opens the gate until motor time or until the gate reaches its opening limit position the second command closes the gate if...

Page 10: ...the latter will be controlled thus effectively relinquishing the security of the rolling code system 4 CONDO The Condominium function means that during the opening movement or during the pause time th...

Page 11: ...become steady on and programming will be completed Repeat the procedure if you wish to restore the previous configuration 2 PED MOT T Programming of pedestrian opening motor time of max 4 minutes The...

Page 12: ...upward each additional LED corresponds to a higher power level Use the SEL key to scroll through the different power levels for each selected power level the top LED will blink for example selecting l...

Page 13: ...FRATELLI COMUNELLO S P A AUTOMATION GATE DIVISION Via Cassola 64 C P 79 36027 Ros Vicenza Italy Tel 39 0424 585111 Fax 39 0424 533417 info comunello it www comunello com...

Reviews: