background image

3. PROGRAMMING THE THERMOSTAT

3.1 A brief introduction to programming

Programming means the setting of switching times and selection of

accompanying temperature levels. The device can be programmed for

a one-week period. Its operation is automatic, and it will cyclically repeat

the programs that have been keyed in. For each day, beside 1 fixed 

(

PROG

switching time, 6 adjustable 

(

PROG

 

 ‒ 

PROG

 

switching times can be set. 

For all switching times a different temperature can be assigned between 

5 and 35°C, in 0.5°C increments. The temperature set for a given switch 

will remain valid until the start time of the next switch. Accordingly, the 

thermostat will keep the temperature set for switching time 

PROG

 

 until 

switching time 

PROG

 

 

 is reached. After switching time 

PROG

 

 the temperature 

selected to switch 

PROG

 

 

 will be valid until the time of the next switch 

(

PROG

 

)

.

The start time of switch 

PROG

 

 is

, which cannot be changed, only 

its temperature can be adjusted. So under the factory default settings, the 

thermostat performs only one switch (

PROG

 

) every day, which is in effect 

from 

 until 

 the next day. 

Note:

 

Setting just one switch for a day (factory default setting) is reasonable 

only if a constant temperature is needed all day. (For example, if for every 

weekday a constant 16°C, and for every weekend a constant 22°C is 

needed.) Otherwise, from both a comfort and an energy-efficiency point 

of view, it is recommended to activate more than one switch for each day. 

Furthermore, it is advised that a comfort temperature is used only those 

times, when the room or building is in use, since every 1°C decrease of 

temperature  saves  approximately  6%  energy  during  a  heating  season. 

As opposed to common belief, keeping a flat warm requires more energy 

than heating it up. (When using a stove, more gas is needed to keep a pan 

of water boiling than to just keep it warm.)

 

The

 

PROG

 

  ‒ 

PROG

 

 

switches are deactivated by factory default (their

start time is 

), but they can be activated at need. Their start time

can be freely set between 

 

and

 

 at 10-minute intervals given

the constraint, that their start time should be in increasing order and a

difference of at least 10 minutes should be between them. This minimum

10-minute difference is going to be preserved even if a previously activated 

switch is modified, in order to avoid co-occurring or overlapping switches.

In such a case, the device automatically increases the start time of the

affected switches until a difference of at least 10 minutes between them is

reached. If the start time of a switch would be later than 

 because of

this automatic modification, then that switch is deactivated instead.

In order to enter the programming mode, press the “

SET

” button and hold

it down and press the “

PROG

” button, too. 

During the programming the

values being adjusted are flashing on the display. The modification

of these values can always be done using the large 

 

and

buttons. 

The  confirmation  of  a  value  is  always  done  by  pressing  the

PROG

” button, after which the next value can be adjusted. The program

- 7 -

Summary of Contents for Q8RF(TX)

Page 1: ...COMPUTHERM Q8RF TX Multi zone programmable wireless radio frequency digital room thermostat Operating Instructions NEW design...

Page 2: ...ure at the dates and times specified by you to reduce energy costs while maintaining comfort Separate temperature programs can be prepared for each day of the week For each day beside 1 fixed switchin...

Page 3: ...9 8 C or below and switches it off at 20 2 C or above Please refer to Section 2 4 for the modification of the factory default switching sensitivity of 0 2 C The thermostat is equipped with a pump prot...

Page 4: ...e thermostatic head may disturb the temperature control of the flat 2 PUTTING THE THERMOSTAT INTO OPERATION BASIC SETTINGS 2 1 Inserting batteries Pressing the lock on the upper side of the housing of...

Page 5: ...between the heating and cooling mode There is a possibility to easily switch between the heating and cooling mode of the thermostat The output terminals of the receiver unit No 1 NO and No 2 COM are c...

Page 6: ...deactivate this function using the large and buttons The notices and indicate activated and deactivated state respectively Finally confirm the setting by pressing the SET button if no buttons are pres...

Page 7: ...ctivate more than one switch for each day Furthermore it is advised that a comfort temperature is used only those times when the room or building is in use since every 1 C decrease of temperature save...

Page 8: ...s should be copied using the COPY button A separate program can be created for the heating and cooling mode and these programs are preserved when switching between the modes Therefore if the thermosta...

Page 9: ...ich is indicated on the display of the device by flashing the temperature value to be set C by default Set the desired temperature using the large and buttons then press the PROG button e Then the sta...

Page 10: ...the flashing abbreviation MON indicating Monday shows that conditions are ready for copying a program Select the day whose program you wish to copy to another day or other days using the large and but...

Page 11: ...the new program as described in Sections 2 and 3 3 6 Program inspection First press the SET button to go to the main screen then press the PROG button At this point the abbreviation indicating the da...

Page 12: ...program switch Set the required temperature using the large and buttons on the front panel of the device At this time the icon appears on the display indicating that the thermostat is operated with m...

Page 13: ...anual control e g that is 3 days After this time has elapsed the icon disappears and the device resumes the program that has been set If you wish to return to the set program before the time set for t...

Page 14: ...voltage appears on the display the batteries should be replaced see Section 2 1 The exact time should be set again after the batteries have been replaced but the device saves the program that has bee...

Page 15: ...spectively When the receiver unit fails to receive signals sent by the thermostat then the receiver unit is outside the transmission distance of the wireless radio frequency transmitter thus they have...

Page 16: ...Start time Temp C Start time Temp C Start time Temp C Start time Temp C Start time Temp C Start time Temp C Start time Temp C MONDAY MON SUNDAY SUN SATURDAY SAT FRIDAY FRI THURSDAY THU WEDNESDAY WED T...

Page 17: ...t the temperature using the and buttons for a period of 1 to 9 hours set the temperature using the and buttons then press the DAY button and finally set the duration using the and buttons for a period...

Reviews: