10
COMPARATO NELLO SRL
• OPERATING TIME VARIATION – “OPERATING TIME”
It is possible to select different operating times referring to the 90° rotation. The following table shows the possible configurations according to the model and power supply type:
• COMMAND REVERSE – “COMMAND REVERSE”
When activated, this feature reverses the relationship between the command signal and the opening & closing positions.
NOTE: THE POSITION FEEDBACK IS NOT REVERSED
• DEAD BAND ADJUSTMENT – “DEAD BAND”
The dead band is defined as a percentage on the proportional control scale. If the command variation is below the set %, the actuator keeps its position and does not move.
It is possible to select a dead band of 1%, 3% or 5%.
OPERATING TIME
[s]
POWER SUPPLY
12V dc
24V ac / dc
100... 240V 50/60Hz
15
NO
YES YES
30 YES YES YES
60 YES YES YES
120 YES YES YES
DIAMANT SMART PRO
OPERATING TIME
[s]
POWER SUPPLY
12V dc
24V ac / dc
100... 240V 50/60Hz
15 NO YES YES
30 YES YES YES
60 YES YES YES
120 YES YES YES
COMPACT SMART PRO
OPERATING TIME
[s]
POWER SUPPLY
12V dc
24V ac / dc
100... 240V 50/60Hz
15 NO NO NO
30 YES YES YES
60 YES YES YES
120 YES YES YES
UNIVERSAL SMART PRO
• 2-POSITION COMMAND (2 POINTS OR 3 POINTS) – “2 POS”
Logic states table
BLUE BROWN BLACK POSITION
I I 0 Opening
I 0 I Closing
I I I Closing
• COMANDO A 3 POSIZIONI – “3 POS”
Tabella degli stati logici
BLUE BROWN BLACK POSITION
I I 0 Opening
I 0 I Closing
I I I Intermediate (45°/90°)
• PROPORTIONAL CONTROL
0-10V 0V = opening 10V = closing
2-10V 2V = opening 10V = closing
0-20 mA 0mA = opening 20mA = closing
4-20 mA 4mA = opening 20mA = closing
→
→
→
→
DIAMANT SMART PRO / COMPACT SMART PRO / UNIVERSAL SMART PRO