CAUTION:
WHEN THE ACTUATOR IS POWERED BY THE FAIL SAFE SYSTEM, THE WI-FI CONNECTION (OPTIONAL) IS AUTOMATICALLY DISABLED IN ORDER TO REDUCE THE POWER
CONSUMPTION.
WHEN THE POWER SUPPLY IS RESTORED, THE WI-FI SIGNAL IS REGENERATED AND THE CONNECTION WILL BE AVAILABLE AGAIN.
12
COMPARATO NELLO SRL
FAIL SAFE (OPTIONAL)
The FAIL SAFE function stores energy and then uses it to move the actuator in a programmed “safe” position in case of power supply failure.
The energy is stored inside some supercapacitors which ensure fast recharge times and long-term reliability. With the Wi-Fi interface or the Modbus serial protocol connection you can program the safety position
(opening, closing or intermediate position).
• INTERMEDIATE POSITION CORRECTION – “MID[-10°…+10°]”
Mid[-10°…+10°] = -10
Mid[-10°…+10°] = 10
ROTATION ANGLE 90°
Mid[-10°…+10°] = -10
Mid[-10°…+10°] = 10
ROTATION ANGLE 180°
• HEATING RESISTANCE
Inside the actuator there is a heating resistance which is electronically managed by means of a temperature reading: you can activate (and set the setpoint temperature between 5°C and 30°C) or deactivate it.
•
Heating resistance activation – “Heater active”
YES = active resistance
NO = non active resistance
•
Heating resistance setpoint temperature – “Heater[5°-30°]”
When the internal temperature is below the setpoint temperature, the heating resistance activates; when the detected probe temperature is above the setpoint temperature, the heating resistance deactivates.
The Modbus or Wi-Fi interface shows the temperature reached inside the actuator.
• MANUAL COMMAND – “MANUAL COMMAND”
This function deactivates the positioning command and forces the complete opening, closing or intermediate position.
CLOSE = complete closing position
OPEN = complete opening position
MID = intermediate position
CAUTION:
THE ACTUATOR STAYS IN THE MANUALLY CONTROLLED POSITION UNTIL THE FUNCTION IS DEACTIVATED (OFF).
•
Fail safe position selection – “Fail Safe pos”
CLOSE = complete closure position
OPEN = complete opening position
MID = intermediate position
For more technical information, see the
TECHNICAL SPECIFICATION
chapter
DIAMANT SMART PRO / COMPACT SMART PRO / UNIVERSAL SMART PRO