Calibration (K-Factor)
11.1
Setting the K-Factor
K-Factor is a proportional calibration factor of litres dispensed per revolution of the meter.
To calibrate the dispenser/pump, dispense fuel into a certified measuring container, and
compare the display value with the amount dispensed.
Example:
Display shows 10.00
True volume 20.00
To calculate the correct 'K' Factor from the information above; firstly record the existing
'K' Factor.
2
Factor
K'
'
Existing
10.00
20.00
Factor
K'
'
Existing
Amount
Displayed
Amount
Dispensed
Factor
K'
'
Existing
Factor
K'
'
New
Change the existing 'K' Factor to this new value.
11.2
Sealing the K-Factor switch
After calibration the K-factor switch should be sealed as shown